TABLE OF CONTENT

S.NO CONTENT TITLE PAGE NO

1. Geometric Parameters 2

2. Occupancy Category 3

3. Site location & Associated Parameters 4

4. Design life 5

5. Material Specifications 6

6. Exposure and Cover 7

7. Fire Requirements 8

8. Serviceability Requirements 9

9. Loads 11

10. Load Combinations 15


1. Geometric Parameters

Client Name is Johnson and Johnson Pvt. Ltd, Gujarat. Building Classification is
Place of business. Its Structure has G+7. The length of the structure is 56 m, width of
the structure is 20 m, level of the structure is 34 m, Ground floor level is 3.6 m and
any remaining floors is 3.9 m , Plinth level is 0.6 m, Head room level is 2.5 m.

Building Description:

The following Geometric parameter required for an office building with as per Indian
Standard code and National Building code 2016.

7F

6F

5F

4F

3F

2F

1F

STILT FLOOR

BASEMENT

FOUNDATION
2. Occupancy Category NBC Vol. 1 pg. 427

Primary Occupancy

a. Rooms without separate storage

b. Banking halls

c. Business computing machine rooms

Secondary Occupancy

a. Record/files store rooms and storage space

b. Cafeterias and dining rooms

c. Corridors, passages, lobbies, staircases including fire escapes

d. Bath and toilets rooms


3. Site location and Associated Parameter

The site situated as Ahmedabad. It has medium dense soil SPT value is 30 and SBC
value is 250 kN/m2 , Site wind speed is 39 and seismic zone will be zone III
4. Design Life

The Design life of the office building is 50 years


5. Material Specification

Grade of the concrete is M40 for vertical member and M30 for horizontal member.
For sub structure M30 for foundation and use Fe500 grade steel reinforcement to IS
1786-2008

Structural element Concrete grade

Slabs and beam M30

Columns M30

Footing M30

Normal weight aggregates shall be considered for all concrete works


6. Exposure & Cover Requirements

From durability requirement, exposure conditions is interior structural elements


above ground level is considered moderate, and for exterior members is
considered mild .The following nominal cover to be provide in the structural
elements

Structural Elements Nominal Cover

Slabs 20 mm

Beams 25mm

Column 40 mm

Footing 50 mm (bottom & sides), 30 mm (top)


7. Fire requirements

The building floor area is 1120 sq.m and plot area is 3040 sq.m.

Floor area index is 0.368, type of construction is Type 4 and fire resistance rating is
120 minutes, minimum beam width 20 mm and rid width of slabs 125 mm minimum
thickness of floor 125 mm, column dimensions 300 mm

Nominal Cover to meet specified period of fire resistance for continuous beam. 30
mm, slabs 25 mm, ribs 35 mm, column 40 mm
8. Serviceability requirements

Following aspects are considered in terms of serviceability: drift, deflection, crack


width

a. Drift

Following aspects are considered for drifts under wind and earthquake loads

Lateral Load Drift Limit

Wind H/500

Earthquake H/250

Limit both drift to H/500 for wind load & H/250 for seismic load
H = height of the building
Wind load drift = 34/500 =0.068
seismic load drift = 34/250 = 0.136

b. Control of Deflection:
Following limitations are considered for floor deflections:
Total long-term deflection - Span / 250
Long term deflection after non-structural components is installed - Span / 350
or 20 mm whichever less
glass facade = span/500
c. Control of crack width
Member type Crack width (mm)
Interior members protected from external 0.3
weather
External members exposed to weather 0.2
Members below ground & retaining walls 0.2
(Interior & Exterior face)

0.1 mm under aggressive conditions


d. Floor Vibration
Frequency of the Minimum floor vibration 4 Hz (we consider nil)
Heavy machinery follows as Euro code
9. Loads and Load combination
Dead loads
Unit weight for building materials (IS 875 Part 1) page no 7
Materials Unit weight kN/m2
Reinforced Cement concrete 25
Plain cement concrete 24
Brick 18 - 20
Steel 78.5
Soil 18
Aluminum 28
Cement concrete screed 24
Cement mortar screed 21

Super imposed dead load


Dead load other than self weight of the structure itself its called super imposed dead
load
1. Block walls and finishes
2. Light partitions
3. Floor finishes
4. MEP service
5. False ceiling
Description Load Intensity (kN/m2)
Floor finish (screed) 1.8
300 mm sunken slab 4.5
Brick wall 12.42 kN/m
Parapet wall/Hand rail wall 4.96 kN/m
Weatherproof course 3.19
Light weight partitions 1.0
False ceiling 0.5
MEP Services 0.5
Live loads – IS 875 part 2
Description Classification (IS 875 part 2) Load Intensity
(kN/m2)
Office area Exhibition hall
Rooms without storage Stairs, 4.0
Corridors,
Passages & Lobbies
Lobby Areas Whole Areas 4.0
Roof (Head Room) With Access 2.0
Service Rooms AHU & Electrical Rooms 5.0
Pantry 3.0
Toilets 2.0

Wind loads – IS 875 part 3


• Location : Ahmedabad
• Basic wind speed Vb= 39 m/s
Floor Height K2
G 4.2 0.91
1F 8.1 0.91
2F 12 0.93
3F 15.9 0.98
4F 19.8 1.01
5F 23.7 1.03
6F 27.6 1.05
7F 31.5 1.06
Roof 34 1.07

Topography factor, k3 = 1.00 (Paragraph in Cl 6.3.3.1, page 12)


Importance factor for cyclonic regions, k4 =1.00 (paragraph in cl 6.3.4, page 12)
Gujarat coast to Ahmedabad = 336 km
Floor Height K2 Vb = 39
G 4.2 0.91 35.49
1F 8.1 0.91 35.49
2F 12 0.93 36.27
3F 15.9 0.98 38.22
4F 19.8 1.01 39.39
5F 23.7 1.03 40.17
6F 27.6 1.05 40.95
7F 31.5 1.06 41.34
Roof 34 1.07 41.73

Design wind pressure (clause 5.4)


Floor Height Pz = 0.6 v2 2 /1000 K2 Vb = 39
G 4.2 0.76 0.91 35.49
1F 8.1 0.76 0.91 35.49
2F 12 0.80 0.93 36.27
3F 15.9 0.87 0.98 38.22
4F 19.8 0.93 1.01 39.39
5F 23.7 0.97 1.03 40.17
6F 27.6 1.00 1.05 40.95
7F 31.5 1.0 1.06 41.34
Roof 34 1.05 1.07 41.73

Wind directionality factor , kd = 1.0


Area Leveraging Factor, Ka = 0.8 ( per floor height x width of the building or floor
area x floor height ) 110
Combination Factor:
Kc = 0.9 ( cl 7.3.3.1.)
Floor Height Pz = 0.6 v2 2 /1000 Pd = k d k a k c
G 4.2 0.76 0.54
1F 8.1 0.76 0.54
2F 12 0.80 0.57
3F 15.9 0.87 0.63
4F 19.8 0.93 0.67
5F 23.7 0.97 0.70
6F 27.6 1.00 0.72
7F 31.5 1.0 0.74
Roof 34 1.05 0.76

Tribute Height
Floor Height Tribute Height (m)
G 4.2 0.5*4.2 + 0.5*3.9 =4.05
1F 8.1 0.5*3.9 + 0.5*3.9 =3.90
2F 12 3.90
3F 15.9 3.90
4F 19.8 3.90
5F 23.7 3.90
6F 27.6 3.90
7F 31.5 0.5*3.9 + 0.5*2.5 =3.20
Roof 34 0.5*2.5 = 1.25

Length of the building, a= 56 m


Width of the building, b= 20 m
Height of the building, h= 34 m
X direction Y direction
a/b or b/a = 56/20 = 2.80 0.36
h/b or h/a= 34/20=1.70 0.61

Refer cl 7.4. in IS 875 part 3 2015, pg 35


Force coefficient in x direction 1.0 from Refer cl 7.4. in IS 875 part 3 2015, pg 35
Force coefficient in X direction, Fx =b (tribute height) pd Cfx
Fore coefficient in Y direction , Fy =a (tribute height) pd Cfy
Floor Height Tribute Height (m) Fx Fy
G 4.2 0.5*4.2 + 0.5*3.9 =4.05 35.26 148.09
1F 8.1 0.5*3.9 + 0.5*3.9 =3.90 33.95 142.60
2F 12 3.90 35.77 150.22
3F 15.9 3.90 39.15 164.44
4F 19.8 3.90 41.69 175.11
5F 23.7 3.90 43.37 182.16
6F 27.6 3.90 45.03 189.13
7F 31.5 0.5*3.9 + 0.5*2.5 =3.20 38.12 160.11
Roof 34 0.5*2.5 = 1.25 15.10 63.43
Seismic load
As per IS 1893, Ahmedabad is considered on seismic zone III as per code and this is
used to determine the earthquake loads on the building
Ductile detailing of reinforced concrete elements is considered as per IS 13920
Seismic zone factor, z = 0.16
Reduction factor R=5 [ Dual systems buildings with Ductile RC wall with SMRF] as
per IS 1893 , pg 23
Importance factor I = 1.2 for office building as per IS 1893 , pg 18
Time period , T= 0.09 h/ sq.root d
Tx= 0.69
Ty= 0.40
10. Load combination
Scheme setting floor
L/d = L/d (basic) x kt x kc
kt = tension reinforcement factor
kc = compression reinforcement factor
L/d= 26 ( for continuous beam from IS 456,Cl.23.2.1)
l/b = 1.42 < 2
its two way slab
fs = 290 (from IS 456 , fig 4)
kt=1.25
kc = 1(from IS 456,pg 34)
L/d = 32.5
Thickness of slab (d) = shortest span length / (L/D)
Thickness of slab d = 107.69 mm
Thickness of slab with cover d = 107 +20 = 127 mm = 150 mm
Load combination
Load Hall Pantry Toilets Stair AHU Head Roof
rooms room
office
space
DL 3.75 3.75 3.75 3.75 3.75 3.75 3.75 kN/m2
SDL 1+1+1.8 1.8+1 3.6+1+1.8+1 1.8 1+1.8 1.8 3.19 kN/m2
LL 4 3 2 4 5 2 0 kN/m2
TL 11.5 9.55 13.15 9.58 12.55 7.55 6.94 kN/m2
FL 17.25 14.325 19.7 14.37 18.83 11.325 10.41 kN/m2
Scheme setting- Beam:
Span = 7m
l/d=15 (for continuous beam)
depth required = 7000/15 = 466.67 mm
add cover thickness = 25 mm
depth = 466.67+25 = 491 mm ; take as d= 500mm
% steel reinforcement

Analysis Methods
3D analysis of the office building is carried out using ETABS software package.