Device test report for compilance with the Standard PN-EN 50438
Date of test: 2018-10-27 Name of test Engineer: mgr inż. Szymon Surma
Under-frequency Over-frequency
Parameter Frequency [Hz] Time [s] Passed Frequency Time [s] Passed
[Hz]
Protection 47,50 0,30÷0,5 52,00 0,3÷0,5
Limit +/- 0,05Hz 0 +/- 0,05Hz
Trip Value 47,50 0,39 YES 52,00 0,37 YES
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 1
Fig. 2: Measure reaction time of over-frequency
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 2
Fig. 3: Measure reaction time of under-voltage
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 3
Fig. 5: Measure reaction time of over-Voltage – stage 2
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 4
2.4.2 Detailed values of AC loads (RLC)
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 5
Fig. 9: LoM test no. 3 PEUT = 5358 W
Test No. Voltage [V] Frequency [Hz] Outout power [W] Power source [W] Passed
Test 1 195,5 47,5 4,717 kW @ 23,74 4914 YES
A
Test 2 253,0 51,5 5.504 kW @ 21,87 5733 YES
A
Test No. Output power [W] Frequency [Hz] Power source [W] Passed
Test a) 5518 50 5748 YES
Test b) 5520 49,55 5748 YES
Test c) 5500 47,55 5748 YES
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 6
Test at Output Power [W] Frequency [Hz] Power Source [W]
power level
P
(40-60)% Pn
Test a) 2325 50 2421
Test b) 2275 50,25 2421
Test c) 2090 50.70 2421
Test d) 1925 51.15 2421
Test e) 1925 50.70 2421
Test f) 1925 50.25 2421
Test g) 2317 50.00 2421
Passed YES
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 7
2800
2600
2400
2200
2000
P [W]
1800
1600
1400
1200
1000
49,8 50 50,2 50,4 50,6 50,8 51 51,2 51,4
f [Hz]
cos
Limit +0,95 -0,95 Passed
210 V 230 V 250 V
20% Pn (1100 W) 0.998 (8 var) 0,999 (6 var) 0,998 (7 var) YES
50% Pn (2750 W) 0.999 (28 var) 0,999 (28 var) 0.999 (29 var) YES
75% Pn (4125 W) 0.999 (47 var) 0,999 (46 var) 0,999 (44 var) YES
100% Pn (5500 W) 0,999 (50 var) 0,999 (60 var) 0,999 (62 var) YES
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 8
3.5. Connection and starting to generate electrical power
Test sequence after trip Connection Connection Primary Power gradient Passed
allowed power source after connection
[W]
Step a) f<47,45Hz U=230V No No 5670 10% Pn/min YES
Step b) f>=47,45Hz U=230V Yes Yes 5670 10% Pn/min YES
Step c) f>50,1 U=230V No No 5670 10% Pn/min YES
Step d) f<=50,1 U=230V Yes Yes 5670 10% Pn/min YES
Step e) f=50Hz U<193,2V No No 5670 10% Pn/min YES
Step f) f=50Hz U>=193,2V Yes Yes 5670 10% Pn/min YES
Step g) f=50Hz U>255,3V No No 5670 10% Pn/min YES
Step h) f=50Hz U<=255,3V Yes Yes 5670 10% Pn/min YES
Test sequence after trip Connection Connection Primary Power gradient Passed
allowed power source after connection
Step a) f<47,45Hz U=230V No No 5670 10% Pn/min YES
Step b) f>=47,45Hz U=230V Yes Yes 5670 10% Pn/min YES
Step c) f>50,15 U=230V No No 5670 10% Pn/min YES
Step d) f<=50,15 U=230V Yes Yes 5670 10% Pn/min YES
Step e) f=50Hz U<193,2V No No 5670 10% Pn/min YES
Step f) f=50Hz U>=193,2V Yes Yes 5670 10% Pn/min YES
Step g) f=50Hz U>255,3V No No 5670 10% Pn/min YES
Step h) f=50Hz U<=255,3V Yes Yes 5670 10% Pn/min YES
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 9
Power gradient after start of generating electrical power
t [min] P [W]
0 0
0,5 250 6000
1 523
1,5 781 5000
2 1064 4000
2,5 1350
3 1630 3000
P [W]
3,5 1890
4 2177 2000
4,5 2440 1000
5 2708
5,5 3000 0
6 3250 0 2 4 6 8 10 12
6,5 3535 t [min]
7 3810
7,5 4075
8 4350
Fig. 11: Power gradient after start of generating electrical
8,5 4625 power
9 4910
9,5 5185
10 5455
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 10
3.7. Power quality - harmonic current emission
P = 5500 W
I = 24 A
U = 230 V
THD = 1,2%
Harmonic order n Current Magnitude [A] at Harmonic current limit [A] Passed
100% rated output power
1 23,92 - -
2 0,17 1,08 YES
3 0,1 2,3 YES
4 0,02 0,43 YES
5 0,02 1,14 YES
6 0,02 0,3 YES
7 0,05 0,77 YES
8 0,02 0,23 YES
9 0,01 0,4 YES
10 0,02 0,23 YES
11 0,05 0,33 YES
12 0,01 0,23 YES
13 0,05 0,21 YES
14 0,01 0,23 YES
15 0,05 0,15 YES
16 0,02 0,23 YES
17 0,05 0,15 YES
18 0,01 0,23 YES
19 0,02 0,15 YES
20 0,01 0,23 YES
21 0,05 0,15 YES
22 0,01 0,23 YES
23 0,07 0,15 YES
24 0,02 0,23 YES
25 0,02 0,15 YES
26 0,01 0,23 YES
27 0,01 0,15 YES
28 0,01 0,23 YES
29 0,02 0,15 YES
30 0,01 0,23 YES
31 0,01 0,15 YES
32 0,01 0,23 YES
33 0,02 0,15 YES
34 0,01 0,23 YES
35 0,01 0,15 YES
36 0,01 0,23 YES
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 11
Harmonic order n Current Magnitude [A] at Harmonic current limit [A] Passed
100% rated output power
37 0,01 0,15 YES
38 0,01 0,23 YES
39 0,01 0,15 YES
40 0,01 0,23 YES
PS 100 inverter test report for compilance with the Standard PN-EN 50438 – ZE TWERD 12