PACK CONTENTS
Premier Plus unvented water heater incorporating immersion heater(s) and thermal controls
Factory fitted Temperature/Pressure Relief Valve Cold Water Combination Valve Expansion
Vessel Expansion Vessel Mounting Bracket Tundish Motorised Valve (Indirect models
only) Compression nuts and olives Immersion heater spanner Installation Instructions
36 00 5803 Issue 7 1
CONTENTS
SECTION CONTENT PAGE
1 INTRODUCTION . . . . . . . 2
2 GENERAL REQUIREMENTS . . . . . . 3
3 INSTALLATION - GENERAL . . . . . . 4
6 COMMISSIONING . . . . . . . 11
7 MAINTENANCE . . . . . . . 12
9 USER INSTRUCTIONS . . . . . . 15
10 GUARANTEE . . . . . . . . 16
11 SPARES STOCKISTS . . . . . . . 16
1.0 INTRODUCTION
The Santon Premier Plus is a purpose designed This appliance complies with the requirements of
unvented water heater. The unit has a stainless steel the CE marking directive and is WRAS approved to
inner vessel which ensures an excellent standard of show compliance with Building Regulations (Sec-
corrosion resistance. The outer casing is a combina- tion G3).
tion of resilient thermoplastic mouldings and plastic
coated corrosion proofed steel sheet. All Premiers The following instructions are offered as a guide to
are insulated with CFC free polyurethane foam to installation which must be carried out by a competent
meet the latest European heat loss requirements (see plumbing and electrical installer in accordance with
Table 3). Building Regulation G3, The Building Standards
(Scotland) Regulations 1990, or The Building Regula-
The unit is supplied complete with all the necessary
safety and control devices needed to allow connec- NOTE: Prior to installation the unit should be stored
tion to the cold water mains. All these components in an upright position in an area free from excessive
are pre-adjusted. damp or humidity.
COLD MAINS
CONNECTION COLD�
(22mm) COLD� SUPPLY
INLET � CHECK�
CONNECTION VALVE
SECONDARY�
RETURN
PRESSURE OUTLET
REDUCING CONNECTION
VALVE (22mm)
HOUSING
SECONDARY�
PRESSURE CIRCULATION�
REDUCING PUMP
VALVE
CARTRIDGE (3.5 bar)
SWEPT�
TEE
FIG. 1 Cold Water Combination Valve
3.4 DRAIN TAP
A suitable draining tap should be installed in the cold FIG. 2 Secondary circulation connection
water supply to the Premier Plus unit between the
Cold Water Combination Valve and the heater at as 3.7 OUTLET
low a level as possible. It is recommended that the The hot water outlet is a 22mm compression fitting
outlet point of the drain pipework be at least 1 metre located at the top of the cylinder. Hot water distribu-
below the level of the heater (this can be achieved by tion pipework should be 22mm pipe with short runs
attaching a hose to the drain tap outlet spigot). of 15mm pipe to terminal fittings such as sinks and
basins. Pipe sizes may vary due to system design.
P P 100B 21m ins 15m ins Indirec tly heated. P rim ary flow 82deg. C at 15l/m in
P P 150B 24m ins 20m ins Indirec tly heated. P rim ary flow 82deg. C at 15l/m in
P P 210B 32m ins 29m ins Indirec tly heated. P rim ary flow 82deg. C at 15l/m in
Test results obtained by WRc-NSF in accordance with Test Criteria 1-50-220 and 1-50-222
Table 4 Sizing of copper discharge pipe (D2) for common temperature relief valve outlet
Safety device
(e.g. Temperature
relief valve)
Metal discharge pipe (D1) from
Temperature relief valve to tundish
Trapped
gully
FIG. 4 Typical discharge pipe arrangement (extract from Building Regulation G3 Guid-
ance section 3.9)
7
ELEMENT / ISOLATING
CONTROLS VALVE (NOT
HOUSING SUPPLIED)
TUNDISH
PRIMARY SECONDARY
RETURN RETURN
TAPPING (IF DISCHARGE
REQUIRED) PIPE
PRIMARY
FLOW DRAIN COCK
(NOT SUPPLIED)
NOTE: PRIMARY HEATING COIL
FITTED ON PP100B TO PP300B INLET
MODELS ONLY
EARTH
INDIRECT THERMAL CUT-OUT
B CONNECTION
INDIRECT THERMOSTAT
A
GREEN/YELLOW
THERMOSTAT 1 2 1 2 3
BROWN
BLUE
GREEN / YELLOW
DIRECT THERMOSTAT
FUSED (13A) DOUBLE
POLE ISOLATING 1 2 3
SWITCH GREEN/
YELLOW
B BLUE
1.5mm 3 CORE
2
13 AMP MAINS
SUPPLY. 1.5mm2
Note: On models fitted with two or three elements each element must be MIN. CABLE SIZE
wired individually in accordance with the diagram above.
1 2 3 2 1 2 3
(SUPPLY)
ADOUBLE POLE ISOLATING L N
SWITCH MUST BE INSTALLED
IN THE MAINS SUPPLY. 1 2 3 4 5 6 7 8 9 10
ALL EARTH CONNECTIONS JUNCTION BOX
1 2 3 4 5 6 7 8 9 10
BE CONNECTED BACK TO
THE MAINS EARTH SUPPLY
1 2 3 2 3
L
L N HTG
ON
DHW
ON L N 3
2 N
PROGRAMMER BOILER PUMP
2 3 1 2 3
(SUPPLY)
FIG. 8 Schematic wiring diagram - 3 port mid position valve system. N.B. Must be used in
conjunction with 2 port zone valve suuplied
10
11
Direct models: When completely full and purged check system for
Open the cover(s) to the immersion heater housing(s) leaks. The heating source (immersion heater(s) or
and disconnect wiring from the thermostat mounted on boiler) can then be switched on.
top of the immersion heater(s). Remove the thermostat
by carefully pulling outwards from the immersion 7.7 BENCHMARKTM LOG BOOK
heater. Unscrew immersion heater backnut(s) and re- On completion of any maintenance or service of the
move immersion heater from the unit. A key spanner is Premier Plus the BenchmarkTM “Installation, Com-
supplied with the Premier Plus unit for easy removal/ missioning and Service Record Log Book” should be
tightening of the immersion heater(s). Over time the filled in to record the actions taken and the date the
immersion heater gasket may become stuck to the work was undertaken.
mating surface. To break the seal insert a round bladed
12
FAU L T P O S S IB L E C A U S E REMEDY
N o ho t w a te r flo w 1 . M ains s u pp ly o ff 1 . C h ec k a nd o p en s t op c o c k
2 . S t ra ine r b lo c k ed 2 . Tu rn o ff w a te r s up p ly .
R e m o ve s t ra in er a n d c lea n (s e e
S e c tio n 7 .3 )
3 . C o ld W a te r C o m bina tio n 3 . C h ec k a nd re fit as re qu ired
V a lve in c orre c tly fitt ed
W a te r fro m h o t t a p s is 1 . D IR E C T im m e rs ion 1 . C h ec k a nd s w itc h on
c old h ea te r n ot s w itc he d o n
2 . D IR E C T im m e rs ion 2 . C h ec k . R e s e t by pu s h in g
h ea te r t he rm al c u t -o ut h a s b ut to n.
o pe ra t ed
3 . IN D IR E C T p ro gra m m er 3 . C h ec k . S e t to a D om e s tic
s et t o C e n tral H e a tin g o nly H o t W ate r prog ram m e
4 . IN D IR E C T b oiler n ot 4 . C h ec k b oiler o pe rat ion . If fa ult
w o rk in g is s us p ec te d c o ns ult bo ile r
m a nu fa c t ure r's in s t ru c tio n s
5 . IN D IR E C T t he rm a l c u t- 5 . C h ec k . R e s e t by pu s h in g
o ut h a s op e ra te d b u t ton o n c u t -o ut . C h ec k
o pe ra tion o f ind irec t th e rm o s ta t
6 . IN D IR E C T m o to ris e d 6 . C h ec k w irin g a nd /o r p lum bin g
va lve no t c on n ec te d c on ne c tio n s to m ot oris ed va lve
c orre c tly (s e e F ig . 7)
W a te r dis c h arge s 1 . IN TE R M ITTE N TLY
from E x p an s ion V a lve E x p an s ion V e s s el c ha rg e 1 . S e e S e c t io n 7.5 fo r re -
p re s s u re h a s re d uc ed be lo w c ha rg in g pro c e d ure
3 .5 ba r
2 . C O N TIN U A L LY
a . C o ld W a te r C o m bina tio na . C h ec k p re s s u re fro m C old
W at e r C o m bina tio n V alve . If
V a lve P re s s u re R ed u c e r n ot
w o rk in g c orre c tly g re ater th an 3 . 5b ar re pla c e
P res s ure R e d uc e r c a rt rid g e
b . E x pa n s io n V alve s e at b . R e m ove E x p a ns io n V a lve
d am a g ed . c artridg e . C h ec k c on d itio n o f
s ea t. If n ec e s s a ry fit n e w
E x p an s ion V alve c a rt rid g e.
W a te r dis c h arge s from 1 . Th e rm a l c o ntro l failure 1 . S w it c h off p ow er t o
T& P R e lie f V a lve N O TE w a te r w ill b e very h ot im m e rs io n h ea te r(s ) an d s hu t
d ow n bo ile r. D O N O T t urn o ff
w a te r s up p ly . W h e n dis c ha rge
s to ps c he c k all t he rm a l
c on trols , rep la c e if fa u lty .
" M ilk y " w a t er O x y g e n a te d w a te r W at e r fro m a pres s uris ed
s y s te m re le as es ox y g e n
b ub bles w he n flo w ing . Th e
m ilk in es s w ill d is ap p ea r a fte r a
s ho rt w hile.
14
15
This product is guaranteed against faulty materials Santon products are manufactured from many recyclable
and manufacture for a period of 25 years from date materials. At the end of their useful life they should be
of purchase (with the exception of the Expansion disposed of at a Local Authority Recycling Centre in order
Vessel which is guaranteed for a period of 5 years to realise the full environmental benefits.
and valves, fittings and electrical parts which are
guaranteed for a period of 2 years) provided that: Insulation is by means of an approved CFC/HCFC free
polyurethane foam with an ozone depletion factor of
• The unit has been installed in accordance with the
Installation and Service instructions and all relevant
Codes of Practice and Regulations in force at the time 11.0 SPARES STOCKISTS
of installation, and that all necessary inlet controls and
safety valves have been fitted correctly.
For the fast and efficient supply of spares
• Any valves and controls are of the Santon recom- please contact the stockists listed below.
mended type and specification.
Electric Water Heating Co.
• It has only been used for the storage of potable 2 Horsecroft Place, Pinnacles, Harlow,
water. Essex, CM19 5BT
Tel: 0845 0553811
• The unit has not been modified or tampered with E-mail: sales@ewh.co.uk
in any way, and has been regularly maintained as
detailed in the Installation and Service instructions. SPD Special Product Division
Units 9 & 10, Hexagon Buisness Centre, Spring-
• Within 60 days of installation, the user completes field Road, Hayes, Middlesex, UB4 0TY
and returns any Certificate of Registration that may Tel: 020 86063567
be supplied with the unit in order to register the prod-
uct.
Parts Center
Unit 6 Revolution Park, Buckshaw Village, Chorley,
The unit is not guaranteed against damage by frost, and
Lancashire, PR7 7DW
the inner container with integral immersion heater(s)
Tel: 0845 2709801
is not guaranteed against excessive scale build-up.
www.partscenter.co.uk
Periodic loss of charge pressure from the Expan-
sion Vessel is normal (indicated by an intermittent Newey & Eyre
discharge of water from the Expansion Valve) and Specialist Products Division
is not covered under the product guarantee. Refer to Please contact your local branch
Section 7.5 for details on how to restore the Expansion
Vessel charge pressure. UK Spares Ltd.
Tower Lane, Warmley, Bristol, BS30 8XT
This guarantee does not affect your statutory rights. Tel: 0117 961 6670
The policy of Santon is one of continuous product development and, as such, we reserve the right to change
specifications without notice.