You are on page 1of 1

Close loop : .

Pid controller : P- Controller


a system that has a feedback loop (or) a control system that uses a feedback  An open loop control system is the one in which the output signal is The term PID stands for proportional integral derivative and it is one kind of
signal to generate the output. The stability of this system can be controlled not fed back to the input of the system. Therefore, an open loop control device used to control different process variables like pressure, flow, Proportional or P- controller gives an output that is proportional to current
by a feedback system. So by providing a feedback system, any open-loop system is also referred to as a non-feedback control system. temperature, and speed in industrial applications. In this controller, a control error e (t). It compares the desired or set point with the actual value or
control system can be changed into a closed loop.The desired output can loop feedback device is used to regulate all the process variables.This type of feedback process value. The resulting error is multiplied with a proportional
be achieved and maintained by evaluating the actual condition & control is used to drive a system in the direction of an objective location constant to get the output. If the error value is zero, then this controller output
generated output. If the generated output is moved away from the actual otherwise level. It is almost everywhere for temperature control and used in is zero.
output, then this control system produces a faulty signal which is fed to the scientific processes, automation & myriad chemical. In this controller, closed-
i/p of the signal. Once the error signal is added to the input signal, then the loop feedback is used to maintain the real output from a method like close to
next loop output can be corrected which is known as automatic control the objective otherwise output at the fixe point if possible. In this article, the
systems . PID controller design with control modes used in them like P, I & D are
S.No. Open-Loop Control System Closed-Loop Control System
discussed.
1. It easier to build. It is difficult to build.
PID Controller Block Diagram
It can perform better if the It can perform better because A closed-loop system like a PID controller includes a feedback control
2.
calibration is properly done. of the feedback. system. This system evaluates the feedback variable using a fixed point to I-Controller
generate an error signal. Based on that, it alters the system output. This
3. It is more stable. It is comparatively less stable. procedure will continue till the error reaches Zero otherwise the value of the Due to the limitation of p-controller where there always exists an offset
feedback variable becomes equivalent to a fixed point.This controller provides between the process variable and setpoint, I-controller is needed, which
Optimization for desired Optimization can be done good results as compared with the ON/OFF type controller. In the ON/OFF provides necessary action to eliminate the steady-state error. It integrates the
4. type controller, simply two conditions are obtainable to manage the system. error over a period of time until the error value reaches zero. It holds the value
When the control system includes a feedback loop, then the systems are output can not be performed. very easily. Once the process value is lower than the fixed point, then it will turn ON. to the final control device at which error becomes zero.
known as feedback control systems. So the output can be controlled Similarly, it will turn OFF once the value is higher than a fixed value. The
accurately by providing feedback to the input. This type of control system It does not consists of Feedback mechanism is output is not stable in this kind of controller and it will swing frequently in the
can include more than one feedback.In the above diagram, the
5.
feedback mechanism. present. region of the fixed point. However, this controller is more steady & accurate
error detector generates an error signal, so this is the variation of the input as as compared to the ON/OFF type controller.
well as the feedback signal these systems are also named as automatic 6. It requires less maintenance. Maintenance is difficult.
control systems.
7. It is less reliable. It is more reliable.
Advantages : These systems are very precise & less error-prone.
 Errors can be corrected through the feedback signal 8. It is comparatively slower. It is faster.
 High bandwidth D-Controller
 It supports automation It can be easily installed and Complicated installation is
High noise margin
9. I-controller doesn’t have the capability to predict the future behavior of error.
 is economical. required and is expensive. So it reacts normally once the setpoint is changed. D-controller overcomes
 They cannot affect by means of noise.
this problem by anticipating the future behavior of the error. Its output
Disadvantages : depends on the rate of change of error with respect to time, multiplied by
Working of PID Controller
 The designing of this system is complicated derivative constant. It gives the kick start for the output thereby increasing
 They are very complex With the use of a low cost simple ON-OFF controller, only two control states system response.
 Expensive are possible, like fully ON or fully OFF. It is used for a limited control
 Huge maintenance is needed application where these two control states are enough for the control
 The control system oscillates sometimes due to feedback signals. objective. However oscillating nature of this control limits its usage and hence
it is being replaced by PID controllers.

The branches start at the open-loop poles and end at the open-loop TRANSFER FUNCTION :
zeros. In addition to the Z explicit open-loop zeros in the transfer
Rule 7 The transfer function of a control system is defined as the ratio of the Laplace transform of
function, there are P-Z open-loop zeros at infinity. the output variable to Laplace transform of the input variable assuming all initial conditions
to be zero.
Rule 3 If there are two or more excess poles than zeros ( ), then for
any gain K, the sum of the real parts of the closed-loop poles (or the
Branches of the root locus lie on the real axis to the left of an odd
number of poles and zeros. Complex-conjugate pairs of poles and average distance from the -axis) is constant3. Procedure for determining the transfer function of a control system are as
zeros are not counted, since they contribute no net angle to the real Rule 8 follows:
axis.
Ignore remote poles and zeros when considering the root locus near 1. We form the equations for the system.
The Root Locus Rules Rule 4 : If a branch on the real axis lies between a pair of poles, the root the origin of the s-plane, and combine the poles and zeros near the 2. Now we take Laplace transform of the system equations, assuming
locus must break away from the real axis somewhere between the poles. initial conditions as zero.
To assist in the construction of root locus plots, the `` Root Locus Rules'' for origin when considering the root locus for remote poles and zeros.
3. Specify system output and input.
plotting the loci are summarized here. These rules are not universal, and Similarly, if a branch on the real axis lies between a pair of zeros, there
Rule 9 4. Lastly we take the ratio of the Laplace transform of the output and the
every author has his own favorite set and ordering of the rules. In his must be an entry point between that pair of zeros. Laplace transform of the input which is the required transfer function.
landmark textbook, Walter Evans lists approximately ten rules, but does not The departure angle from a complex-conjugate pole can be found by
order or number them [1, Appendix B], while Roberge enumerates eight Rule 5
considering the angle condition on a small circle around the pole. The
rules [9, pages 121-126].
As K gets very large, P-Z branches go to infinity. These branches result is found by summing all the angles from open-loop zeros and
Advantages of Transfer function
All root locus rules can be directly traced to the characteristic equation, approach asymptotes at angles to the real axis of subtracting all the angles from all other poles 1. If transfer function of a system is known, the response of the system to any
1+L(s)=0. If we assume that the loop transfer function can be written
as L(s)=KL0(s), where K is a positive gain, then we can write the magnitude input can be determined very easily.
condition and the angle condition as 2. A transfer function is a mathematical model and it gives the gain of the
where and the centroid of these asymptotes is on the The approach angle to a complex-conjugate zero follows similarly
|L(s)|=|KL0(s)|=1 system.
real axis at
3. Since it involves the Laplace transform, the terms are simple algebraic
This sum only needs to be calculated once for each complex pair, since expressions and no differential terms are present.
We assume that the loop transfer function has P open loop poles the root-locus diagram is symmetric above and below the real axis.
and Z open loop zeros, and that there are at least as many poles as zeros ( Rule 6 4. Poles and zeroes of a system can be determined from the knowledge of
Rule 10 the transfer function of the system.
). The departure angles of the branches from an mth-order pole on the
The break-away (entry) points from (to) the real axis between a pair of
real axis are Disadvantages of Transfer function
Rule 1 poles (zeros) can be found either by geometric construction4 or by 1. Transfer function does not take into account the initial conditions.
The number of branches, which are the paths of the closed-loop poles, finding the local maxima (minima) of the gain function , solving
2. The transfer function can be defined for linear systems only.
is equal to the number of open-loop poles, P.
if the mth-order pole is to the left of a even number of poles and 3. No inferences can be drawn about the physical structure of the system.
Rule 2 zeros. If the mth-order pole is to the left of a odd number of poles and
zeros, then the departure angles are

Unit Ramp Signal 1. Delay time (td) – It is the time required for the response to reach 50% of the final Let us now apply the principle of argument to the entire right half of the ‘s’ Explain the requirements of an ideal control system.:
A ramp function or ramp signal is a type of standard signal which starts at 𝑡 = 0 and increases
value in the first instance. plane by selecting it as a closed path. This selected path is called a) Accuracy: Accuracy must be very high as error arising should be corrected.
linearly with time. The unit ramp function has unit slop. the Nyquist contour. Accuracy can be improved by the use of feedback element.
2. Rise time (tr) – It is the time required for the response to rise from 10% to 90%
We know that the closed loop control system is stable if all the poles of the b) Sensitivity: A good control system senses quick changes in the output due to an
of the final value for underdamped systems and from 0 to 100% of the final value in
closed loop transfer function are in the left half of the ‘s’ plane. So, the poles environment, parametric changes, internal and external disturbances.
the case of underdamped systems, in the first instance.
of the closed loop transfer function are nothing but the roots of the c) Noise: Noise is a unwanted signal and a good control system should be sensitive to
3. Peak time (tp) – It is the time required for the response to reach the peak value characteristic equation. As the order of the characteristic equation increases, these type of disturbances. d) Stability: The stable systems has bounded input and
of the time response. it is difficult to find the roots. So, let us correlate these roots of the bounded output. A good control system should response to the undesirable changes in
characteristic equation as follows. the stability.
4. Peak overshoot (Mp) – It is the normalised difference between the peak value of e) Bandwidth: To obtain a good frequency response, bandwidth of a system should
the time response and the steady state value.  The Poles of the characteristic equation are same as that of the poles of be large.
the open loop transfer function. f) Speed: A good control system should have heigh speed that is the output of the
Parabolic signals: 5. Settling time (ts) – Time required for the response to reach and stay within a  The zeros of the characteristic equation are same as that of the poles of
specified tolerance band of its final value or steady state value. This tolerance system should be fast as possible.
When a signal gives the constant acceleration distinction of actual input signal, such a the closed loop transfer function. g) Oscillation: For a good control system oscillation in the output should be constant
signal is known as parabolic signal or parabolic function. It is also known as band is usually 2% to 5%.
We know that the open loop control system is stable if there is no open loop and must follow Barkhausein's Criteria.
unit acceleration signal. The unit parabolic signal starts at t = 0.
pole in the the right half of the ‘s’ plane.
i.e.,P=0⇒N=−Z=0⇒=−
p(t)={t22fort≥0 0fort<0
We know that the closed loop control system is stable if there is no closed Gain Margin
loop pole in the right half of the ‘s’ plane. The greater the Gain Margin (GM), the greater the stability of the system. The
i.e.,Z=0⇒N=P=0⇒ gain margin refers to the amount of gain, which can be increased or decreased
Nyquist stability criterion states the number of encirclements about the without making the system unstable. It is usually expressed as a magnitude in
critical point (1+j0) must be equal to the poles of characteristic equation, dB.
which is nothing but the poles of the open loop transfer function in the right Phase Margin
half of the ‘s’ plane. The shift in origin to (1+j0) gives the characteristic
equation plane. The greater the Phase Margin (PM), the greater will be the stability of the
system. The phase margin refers to the amount of phase, which can be
sinusoidal wave signal Rules for Drawing Nyquist Plots increased or decreased without making the system unstable. It is usually
A sinusoidal wave signal is a type of periodic signal that oscillates (moves Follow these rules for plotting the Nyquist plots. expressed as a phase in degrees.
up and down), periodically. The geometrical waveform of a sinusoidal signal Gain Crossover frequency
Nyquist Stability Criterion  Locate the poles and zeros of open loop transfer
forms an S-shape wave in one complete cycle. A sinusoidal can be a sine
function G(s)H(s)�(�)�(�) in ‘s’ plane. The gain crossover is the frequency at which the open-loop gain first
functioned signal or cosine functioned signal. Thus, a sinusoidal signal can The Nyquist stability criterion works on the principle of argument. It states
 Draw the polar plot by varying ω� from zero to infinity. If pole or zero reaches the value 1 and so is 0.005 Hz. Thus, the phase margin is
be defined as, that if there are P poles and Z zeros are enclosed by the ‘s’ plane closed path,
present at s = 0, then varying ω� from 0+ to infinity for drawing polar 180° − 120°=60°.
y=sinxy=sinx then the corresponding G(s)H(s) plane must encircle the origin P−Z times. So,
plot. Phase Crossover frequency
we can write the number of encirclements N as,
y=cosx  Draw the mirror image of above polar plot for values of ω� ranging from
N=P− Z
−∞ to zero (0− if any pole or zero present at s=0). The phase crossover frequency is the frequency at which the phase angle
 If the enclosed ‘s’ plane closed path contains only poles, then the  The number of infinite radius half circles will be equal to the number of first reaches −180° and thus is the point where the Nyquist plot crosses the
direction of the encirclement in the G(s)H(s) plane will be opposite to the poles or zeros at origin. The infinite radius half circle will start at the point real axis
direction of the enclosed closed path in the ‘s’ plane. where the mirror image of the polar plot ends. And this infinite radius half
 If the enclosed ‘s’ plane closed path contains only zeros, then the circle will end at the point where the polar plot starts.
direction of the encirclement in the G(s) H(s) plane will be in the same .
direction as that of the enclosed closed path in the ‘s’ plane.

What is a Bode Plot?

A Bode plot is a graph commonly used in control system engineering to


determine the stability of a control system. A Bode plot maps the frequency
response of the system through two graphs – the Bode magnitude plot
(expressing the magnitude in decibels) and the Bode phase plot (expressing
the phase shift in degrees).
Bode Plot Stability
Below is a list of criterion relevant to drawing Bode plots (and calculating
their stability):

1. Gain Margin: Greater will the gain margin greater will be the
stability of the system. It refers to the amount of gain, which can be
increased or decreased without making the system unstable. It is
usually expressed in dB.
2. Phase Margin: Greater will the phase margin greater will be the
stability of the system. It refers to the phase which can be increased
or decreased without making the system unstable. It is usually
expressed as phase.
3. Gain Crossover Frequency: It refers to the frequency at which the
magnitude curve cuts the zero dB axis in the bode plot.
4. Phase Crossover Frequency: It refers to the frequency at which the
phase curve cuts the negative times the 180o axis in this plot.
5. Corner Frequency: The frequency at which the two asymptotes cuts
or meet each other is known as break frequency or corner frequency.
6. Resonant Frequency: The value of frequency at which the modulus
of G (jω) has a peak value is known as the resonant frequency.
7. Factors: Every loop transfer function {i.e. G(s) × H(s)} product of
various factors like constant term K, Integral factors (jω), first-order
factors ( 1 + jωT)(± n) where n is an integer, second-order or
quadratic factors.
8. Slope: There is a slope corresponding to each factor and the slope for
each factor is expressed in the dB per decade.
9. Angle: There is an angle corresponding to each factor and the angle
for each factor is expressed in the degrees.

You might also like