Professional Documents
Culture Documents
G1 THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL DESIGNER'S AND OTHER M1 ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS3700 EXCEPT WHERE LB1 THE CENTRE LINE OF EACH WALL SHALL BE CONCENTRIC OVER ITS FULL HEIGHT UNLESS
CONSULTANT'S DRAWINGS, THE SPECIFICATIONS AND WITH SUCH OTHER WRITTEN INSTRUCTIONS AS VARIED BY THE CONTRACT DOCUMENTS. OTHERWISE NOTED. REFER TO DRAWINGS FOR THE WALL THICKNESS AND DETAILS.
MAY BE ISSUED DURING THE COURSE OF THE CONTRACT. M2 THE DESIGN STRENGTH OF MASONRY SHALL BE IN ACCORDANCE WITH THE MASONRY LB2 DETAILS OF ALL OPENINGS IN WALLS NOT SHOWN ON STRUCTURAL DRAWINGS SHALL BE
G2 ANY DISCREPANCY ON THE DRAWINGS OR BETWEEN THE DRAWINGS AND/OR THE SCHEDULE SHOWN ON THIS DRAWING. MORTAR ADMIXTURES SHALL NOT BE USED WITHOUT WRITTEN SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO CONSTRUCTION.
SPECIFICATION AND/OR THE AUSTRALIAN STANDARDS SHALL BE REFERRED TO THE CLIENT AND A APPROVAL. LB3 CARE SHOULD BE TAKEN IN PLACING CONCRETE IN CORE-FILLED WALLS TO ENSURE THAT THE
WRITTEN INSTRUCTION RECEIVED PRIOR TO PROCEEDING WITH THE WORK. M3 NO CHASES SHALL BE CUT INTO LOAD BEARING MASONRY WITHOUT THE APPROVAL OF THE CONCRETE IS PROPERLY PLACED AND COMPACTED.
G3 THE DOCUMENTED DESIGN CONSTITUTES THE MAIN STRUCTURAL FRAMING BUT DOES NOT ENGINEER.
INCLUDE A FULL SCOPE OF SECONDARY STEEL OR TIMBER FRAMING TO SUPPORT FACADE CLADDING, M4 MORTAR JOINTS SHALL BE 10mm THICK AND HAVE A MAXIMUM TOOLED DEPTH OF 3mm U.N.O.
FORMWORK NOTES
INTERNAL PARTITION WALLS, ETC. ALL PERPENDS AND BED JOINTS ARE TO BE FULLY FILLED WITH MORTAR.
G4 THE DRAWINGS SHOW TYPICAL CONNECTION DETAILS ONLY. THE SHOP DRAFTER IS REQUIRED M5 CLEANOUT HOLES SHALL BE PROVIDED AT THE BASE OF ALL CORES OR CAVITIES WHICH ARE TO
TO DEVELOP ALL CONNECTION DETAILS NOT SPECIFICALLY SHOWN. THE CONTRACTOR IS REQUIRED BE GROUTED OR FILLED. FW1 FORMWORK SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH AS3610 EXCEPT
TO PRICE FOR ALL CONNECTIONS NOT SPECIFICALLY SHOWN. M6 ALL MORTAR OBSTRUCTIONS IN CORES OR CAVITIES SHALL BE REMOVED PRIOR TO GROUTING. WHERE VARIED BY THE CONTRACT DOCUMENTS.
G5 THE STRUCTURAL DRAWINGS DO NOT SHOW ALL DETAILS OF FIXTURES, INSERTS, SLEEVES, THIS MAY BE DONE USING A ROD FROM THE TOP OF THE WALL. ALL MORTAR THUS REMOVED SHALL FW2 THE CLASS AND COLOUR OF THE CONCRETE SURFACE FINISH SHALL BE AS SPECIFIED ON THE
OPENINGS, ETC. REQUIRED BY THE VARIOUS TRADES. ALL SUCH DETAILS INCLUDING OPENINGS FOR BE CLEANED FROM THE BOTTOM OF THE WALL BEFORE THE CLEANOUT HOLES ARE CLOSED FOR DESIGN DRAWINGS. APPROVAL OF THE CONCRETE MIX DOES NOT ABSOLVE THE CONTRACTOR OF
CONSTRUCTION PURPOSES, MUST BE APPROVED BY THE CLIENT BEFORE PROCEEDING WITH GROUTING. THE NEED TO COMPLY WITH THE REQUIRED CONCRETE COLOUR REQUIREMENTS.
CONSTRUCTION. M7 REINFORCING STEEL SHALL BE SECURELY FIXED IN POSITION BEFORE GROUTING. FW3 EITHER BACKPROPPING OR AN UNDISTURBED SUPPORT SYSTEM OF FORMWORK IS TO BE
G6 WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH THE RELEVANT CURRENT M8 GROUT FOR BOND BEAMS, CORE FILLING OR CAVITY FILLING SHALL COMPROMISE OF 1 PART ADOPTED. A RESHORING SYSTEM IS NOT TO BE USED.
AUSTRALIAN STANDARDS INCLUDING ALL AMENDMENTS, AND THE REQUIREMENTS OF THE LOCAL CEMENT, 0.25 PART LIME, 3 PARTS 10mm AGGREGATE U.N.O. MAXIMUM SLUMP TO BE 230mm. FW4 MINIMUM FORMWORK STRIPPING TIMES ARE TO BE AS FOLLOWS - VERTICAL SURFACES MAY
M9 CORES AND CAVITIES SHALL BE FILLED IN 1000mm MAXIMUM LIFTS. GROUTING OF CAVITIES BE STRIPPED OF FORMWORK WHEN THE MINIMUM MEAN COMPRESSIVE STRENGTH OF CONCRETE fcm
STATUTORY AUTHORITIES, EXCEPT WHERE VARIED BY THE CONTRACT DOCUMENTS.
BETWEEN MASONRY SKINS IS NOT TO TAKE PLACE UNTIL 3 DAYS AFTER MASONRY HAS BEEN LAID. HAS REACHED 5.0 MPa. IF THE STRENGTH CANNOT BE ACCURATELY ASSESSED VIA THE USE OF TEST
G7 ALL DIMENSIONS ARE IN MILLIMETRES UNLESS NOTED OTHERWISE. ALL LEVELS ARE IN METRES
M10 GROUT SHALL BE THOROUGHLY COMPACTED USING A PLAIN BAR. CYLINDERS STORED ON SITE AND CURED IN A SIMILAR MANNER TO THE PERMANENT STRUCTURE
UNLESS NOTED OTHERWISE.
M11 WALL TIES SHALL BE PROVIDED AT 600mm MAXIMUM CENTRES HORIZONTALLY AND VERTICALLY THEN THE MINIMUM FORMWORK STRIPPING TIME IS TO BE 2 DAYS PROVIDED THE AVERAGE AMBIENT
G8 ALL DIMENSIONS RELEVANT TO SETTING OUT AND OFF-SITE WORK SHALL BE VERIFIED BY THE
AND CONSIST OF 3.1mm DIAMETER GALVANISED WIRE U.N.O. TEMPERATURE OVER THAT PERIOD IS BETWEEN 12 AND 20 DEGREES CELSIUS. REMOVAL OF
CONTRACTOR BEFORE CONSTRUCTION OR FABRICATION COMMENCES. THE ENGINEER'S DRAWINGS
M12 CONTROL JOINTS SHALL BE PLACED IN ALL MASONRY WALLS AT 6000mm MAXIMUM CENTRES FORMWORK SUPPORT (PROPS) TO BEAM AND SLABS MAY BE UNDERTAKEN WHEN THE MINIMUM MEAN
SHALL NOT BE SCALED. HORIZONTALLY AND 4000mm MAXIMUM CENTRES VERTICALLY U.N.O. REFER TO THE DRAWINGS FOR COMPRESSIVE STRENGTH OF THE CONCRETE fcm HAS REACHED 28 MPa. IF THE STRENGTH CANNOT
G9 DURING CONSTRUCTION THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE SPECIFIC LOCATIONS. CONTROL JOINTS SHALL ALSO BE PLACED ABOVE ONE CORNER OF ALL DOOR BE ACCURATELY ASSESSED VIA THE USE OF TEST CYLINDERS STORED ON SITE AND CURED IN A
STRUCTURE AND ADJACENT STRUCTURES IN A STABLE CONDITION AND ENSURING NO PART SHALL BE AND WINDOW OPENINGS U.N.O. SIMILAR MANNER TO THE PERMANENT STRUCTURE THEN THE MINIMUM FORMWORK STRIPPING TIME
OVERSTRESSED UNDER CONSTRUCTION ACTIVITIES. M13 MORTAR DROPPINGS OR OTHER HARD MATERIALS SHALL BE KEPT CLEAR OF ALL CONTROL IS TO BE 18 DAYS PROVIDED THE AVERAGE AMBIENT TEMPERATURE OVER THAT PERIOD IS BETWEEN
G10 THE APPROVAL OF A SUBSTITUTION SHALL BE SOUGHT FROM THE CLIENT BUT IT IS NOT AN JOINTS. PLACE POLYSTYRENE OR SIMILAR IN ALL VERTICAL JOINTS TO AVOID MORTAR DROPPINGS 12 AND 20 DEGREES CELSIUS.
AUTHORISATION FOR A VARIATION. ANY CLAIM FOR A VARIATION MUST BE SUBMITTED TO THE CLIENT FILLING THE JOINTS DURING CONSTRUCTION FW5 HORIZONTAL LOADS ON FORMWORK ARE TO BE RESISTED BY THE FORMWORK BRACING.
BEFORE THE WORK COMMENCES. M14 JOINTS IN WALLS SHALL BE FILLED WITH COMPRESSIBLE FILLER STRUTTING OF THE FORMWORK FROM THE PERMANENT STRUCTURE TO RESIST HORIZONTAL LOADS
G11 ALL PROPS AND FORMWORK FOR FLOOR BEAMS AND SLABS SHALL BE REMOVED BEFORE M15 WALL FINISHES MUST BE JOINTED AT THE SAME LOCATION AS THE MASONRY CONTROL JOINTS
IS NOT PERMITTED.
CONSTRUCTION OF ANY MASONRY WALLS OR PARTITIONS ON THE FLOOR. TO AVOID UNCONTROLLED CRACKING IN WALL FINISHES.
G12 ALL NON-LOAD BEARING WALLS SHALL BE KEPT 20mm CLEAR OF THE UNDERSIDE OF SLABS AND FW6 REFER TO THE DRAWINGS FOR LOCATIONS OF CONSTRUCTION JOINTS.
M16 ALL MASONRY IS TO BE FIXED TO ADJOINING CONCRETE, STEEL OR TIMBER FRAMED
BEAMS ABOVE UNLESS NOTED OTHERWISE. SUPPORTING MEMBERS BY MFA 3/3 MASONRY ANCHORS (OR AN APPROVED EQUIVALENT) AT 600mm FW7 THE SEQUENCE OF CONCRETE PLACEMENT IS TO BE SPECIFIED BY THE CONTRACTOR.
G13 DESIGN WIND LOADINGS ARE IN ACCORDANCE WITH AS1170.2 AND AS4055 AS FOLLOWS: MAXIMUM CENTRES VERTICALLY AND MFA4/M MASONRY ANCHORS (OR APPROVED EQUIVALENT) AT FW8 PROPPING OF COMPOSITE CONSTRUCTION IS TO BE AS SPECIFIED ON THE DRAWINGS.
WIND REGION: A1 WIND CLASS: N2 1000mm MAXIMUM CENTRES HORIZONTALLY U.N.OI. FW9 DESIGN LOADS FOR THE PERMANENT STRUCTURES ARE NOTED ON THE DRAWINGS.
TERRAIN CATEGORY: TC2.5 SERVICEABILITY DESIGN GUST WIND SPEED: 26 m/s M17 MASONRY ANCHORS ARE TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S FW10 DETAILS OF THE REQUIREMENTS OF PERMANENT FORMWORK SHALL BE AS SPECIFIED ON THE
TOPOGRAPHY: T1 ULTIMATE DESIGN GUST WIND SPEED: 40 m/s SPECIFICATIONS. DRAWINGS.
SHIELDING: PS M18 SOLID BRICKS, SOLID BLOCKS OR CORE FILLED HOLLOW BLOCKS ARE BE USED AT ALL MASONRY
G14 DESIGN LIVE LOADINGS ARE IN ACCORDANCE WITH AS1170.1. THE STRUCTURAL WORK ON ANCHOR LOCATIONS.
THESE DRAWINGS HAS BEEN DESIGNED FOR THE FOLLOWING LOADS:
EXCAVATION NOTES
M19 MILD STEEL LINTELS IN NON-LOAD BEARING MASONRY WALLS SHALL BE IN ACCORDANCE WITH
THE FOLLOWING TABLE. PROVIDE 200mm MIN. BEARING EACH END. LONG LEG VERTICAL ON ALL EX1 THE CONTRACTOR IS TO NOTIFY ALL SERVICE AUTHORITIES AND ARRANGE FOR
AREA SDL kPa LIVE LOAD kPa UNEQUAL ANGLES. LINTEL SIZES ASSUME MASONRY ARCHING IS POSSIBLE, AND NO OTHER VERTICAL DISCONTINUANCE OF SERVICES OR SUPPLY AS APPLICABLE AND DO ALL CUTTING, DISCONNECTION
INTERNAL FLOORS 0.2 1.5 LOADS ARE APPLIED TO THE MASONRY WALL EXCEPT FOR SELF-WEIGHT OF THE MASONRY. OR SEALING OFF OF SERVICES AND DRAINS AS REQUIRED. SERVICES OR SUPPLY LINES THAT ARE TO
0.2 2.0 BE RETAINED SHALL REMAIN UNDAMAGED AND GIVEN ALL NECESSARY PROTECTION.
STAIRS AND LANDINGS MASONRY SCHEDULE EX2 THE CONTRACTOR SHALL PROVIDE AND DO ALL BRACING OR SHORING NECESSARY TO RETAIN
ROOF 0.1 0.25 MIN EARTH BANKS, ROADS, PAVEMENTS, WALLS AND FOOTINGS OF ADJOINING PROPERTIES AND
CHARACTERISTIC MORTAR MIX
NON-HABITABLE ROOF SPACES 0.2 0.5 PREVENT CAVING AND DISPLACEMENT OF ADJACENT SOIL OR STRUCTURES AND PROVIDE ALL
ELEMENT UNCONFINED
COMPRESSIVE NECESSARY COMPONENTS OF SUCH BRACING.
CEMENT LIME SAND EX3 THE CONTRACTOR SHALL PROVIDE PUMPS, TEMPORARY SUMPS, AND DRAINS TO DO ALL
STRENGTH (MPa)
FOOTING NOTES
BAILING ETC. AS MAY BE NECESSARY TO ENSURE THAT NO WATER IS PERMITTED TO REMAIN IN THE
NON LOAD BEARING BLOCKWORK WALLS 12 1 1 6
F1 THE MINIMUM SAFE BEARING CAPACITY OF THE FOUNDATION MATERIAL IS TO BE: EXCAVATION.
100 kPa FOR RAFT FOOTINGS LOAD BEARING BLOCKWORK WALLS 15 1 0.25 3 EX4 EXCAVATION BATTERS AROUND THE PERIMETER OF THE SITE ARE TO BE AS SHOWN BELOW
REFER TO GEOTECHNICAL BOREHOLE LOGS FOR GUIDANCE. UNLESS NOTED OTHERWISE ON THE DRAWINGS:
NON LOAD BEARING BRICKWORK WALLS 40 1 1 6
F2 THE ASSUMED FOUNDING LEVELS OF THE FOOTINGS ARE TO BE ON NATURAL GROUND TYPICAL
AS DESCRIBED IN THE GEOTECHNICAL BOREHOLE LOGS. BEFORE ANY REINFORCEMENT OR 40 3 EDGE OF STRUCTURE
LOAD BEARING BRICKWORK WALLS 1 0.25
CONCRETE IS PLACED, THE SAFE BEARING CAPACITY OF THE GROUND IS TO BE VERIFIED BY THE
GEOTECHNICAL ENGINEER.
F3 THE CONTRACTOR IS TO ALLOW FOR THE ENGAGEMENT OF THE GEOTECHNICAL ENGINEER TO 1:1 BATTER
VERIFY THE FOUNDING MATERIAL.
F4 OVER-EXCAVATION WITHIN THE INFLUENCE ZONE (DEFINED BY A 45 DEGREE LINE DOWN FROM
THE BASE OF EXISTING FOOTINGS) OF ANY FOOTINGS IS NOT ALLOWED WITHOUT THE PRIOR
APPROVAL OF THE EXCAVATION SEQUENCE BY THE CLIENT. 1000
C1 ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS3600 EXCEPT WHERE C24 BARS SHALL BE EVENLY DISTRIBUTED OVER THE WIDTH OF THE STRIP INDICATED ON THE S9 UNLESS SHOWN OTHERWISE ON THE DRAWINGS, ALL CONNECTIONS SHALL BE IN ACCORDANCE
VARIED BY THE CONTRACT DOCUMENTS. DRAWINGS UNLESS NOTED OTHERS. WITH THE FOLLOWING MINIMUM REQUIREMENTS:
C2 BEAM DEPTHS ARE WRITTEN FIRST U.N.O AND INCLUDE SLAB THICKNESS. BEAMS AND SLABS C25 ALL EMBEDMENTS SHALL BE HOT DIP GALVANISED. ALL WELDS SHALL BE 6mm CONTINUOUS FILLET WELDS ALL AROUND.
ARE TO BE POURED TOGETHER UNLESS NOTED OTHERWISE. C26 CONCRETE SHALL BE SEPARATED FROM SUPPORTING MASONRY BY TWO LAYERS OF MALTHOID ALL BOLTS SHALL BE M20 8.8/S WITH A MINIMUM OF 2 BOLTS PER CONNECTION.
C3 SIZES OF CONCRETE ELEMENTS DO NOT INCLUDE THICKNESS OF APPLIED FINISHES. (OR AN APPROVED EQUIVALENT). VERTICAL FACES OF CONCRETE SHALL BE KEPT FREE OF ADJOINING PURLIN BOLTS TO BE M12 8.8/S WITH A MINIMUM OF 2 BOLTS PER PURLIN END.
C4 NO HOLES, CHASES OR EMBEDMENT OF PIPES OTHER THAN THOSE SHOWN ON THE SURFACES BY 10mm THICKNESS OF ABLEFLEX (OR APPROVED EQUIVALENT) U.N.O. ALL NON-LOAD ALL GUSSET AND CLEAT PLATES SHALL BE 10mm THICK
STRUCTURAL DRAWINGS SHALL BE MADE IN CONCRETE MEMBERS WITHOUT PRIOR APPROVAL OF BEARING WALL SHALL BE KEPT CLEAR OF THE UNDERSIDE OF SLABS AND BEAMS BY 20mm UNLESS ALL CAP PLATES SHALL BE 6mm THICK
NOTED OTHERWISE ON THE DRAWINGS. ALL BASE PLATES SHALL BE 16mm THICK
THE ENGINEER.
C27 BRICKWORK MUST NOT BE BUILT ON CONCRETE SLABS OR BEAMS UNTIL FORMWORK S10 COLUMNS AND MULLIONS SHALL HAVE THEIR BASE PLATES FULLY GROUTED IN ACCORDANCE
C5 CONSTRUCTION JOINTS SHALL BE PROPERLY FORMED AND USED ONLY WHERE SHOWN ON THE
SUPPORTING THE CONCRETE HAS BEEN REMOVED. WITH THE SPECIFICATIONS AFTER PLUMBING AND LEVELLING ON NEOPRENE PACKERS.
DRAWINGS OR SPECIFICALLY APPROVED BY THE ENGINEER.
S11 SUBSTITUTIONS FOR STEEL SECTIONS SHOWN ON DRAWINGS SHALL NOT BE MADE WITHOUT
C6 ALL EXPOSED CONCRETE CORNERS TO HAVE 15mm CHAMFER U.N.O.
REINFORCING BAR SPLICE SCHEDULE (mm) THE WRITTEN APPROVAL OF THE ENGINEER.
C7 CAMBER TO SUSPENDED SLABS SHALL BE POSITIVE UPWARD CAMBER OF 3mm PER 1000mm S12 ALL STEELWORK BELOW GROUND OR FINISHED SURFACE LEVEL IS TO BE ENCASED IN 75mm
SPAN UNLESS NOTED OTHERWISE. VERTICAL BAR, OR BAR WITH LESS THAN BAR WITH MORE THAN 300 mm OF MINIMUM CONCRETE ALL AROUND.
C8 FORMWORK AND BACK PROPPING SHALL BE DESIGNED, CONSTRUCTED AND STRIPPED IN BAR SIZE 300 mm OF CONCRETE BELOW BAR CONCRETE BELOW BAR S13 THE ENDS OF ALL TUBULAR MEMBERS ARE TO BE SEALED WITH NOMINAL THICKNESS PLATES
ACCORDANCE WITH AS3610. REFER TO DESIGNER'S DRAWINGS AND THE SPECIFICATION FOR AND CONTINUOUS FILLET WELDED U.N.O.
CONCRETE GRADE CONCRETE GRADE
CLASSES OF SURFACE FINISH. S14 ALL HOT DIP GALVANISED MEMBERS SHALL BE PROVIDED WITH VENT AND DRAINAGE HOLES IN
25 MPa 32 MPa OR MORE 25 MPa 32 MPa OR MORE
C9 CONCRETE COMPONENTS AND QUALITY SHALL BE AS FOLLOWS: ACCORDANCE WITH THE GALVANISER'S RECOMMENDATIONS.
N10 250 250 350 350 S15 WHERE MEMBERS SHOWN ON THE STRUCTURAL OR DESIGNER'S DRAWINGS ARE REQUIRED TO
ELEMENT f'c MPa SPECIAL REQUIREMENTS
BE CURVED, BENT OR ROLLED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE METHODS
N12 350 300 400 400
TRENCH PIERS S25 - REQUIRED TO ACHIEVE THE REQUIRED SHAPES WITHOUT LOCALISED DISTORTION OF THE MEMBERS.
N16 550 500 650 600 S16 THE CONTRACTOR SHALL PROVIDE AND LEAVE IN PLACE, UNTIL PERMANENT BRACING
SWIMMING POOL S40 -
ELEMENTS ARE CONSTRUCTED, SUCH TEMPORARY BRACING AS IS NECESSARY TO STABILISE THE
- N20 800 700 950 850
SLABS, BEAMS, FOUNDATIONS, U.N.O. S25 STRUCTURE DURING CONSTRUCTION.
ITEMS NOT OTHERWISE NOTED S32 - N24 1050 950 1300 1150 S17 STEEL PURLIN AND GIRT DESIGN HAS BEEN BASED ON LYSAGHT PURLINS. ALTERNATIVE
PURLINS OF EQUAL OR GREATER LOAD CAPACITY MAY BE SUBSTITUTED ONLY WITH THE WRITTEN
MAXIMUM AGGREGATE SIZE SHALL BE 20mm. APPROVAL FROM THE ENGINEER.
C10 ALL CEMENT IS TO BE "GP" GENERAL PURPOSE PORTLAND CEMENT OR "GB" GENERAL PURPOSE STRUCTURAL STEELWORK NOTES S18 BRIDGING SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S DETAILS U.N.O.
BLENDED CEMENT OR TYPE "SR" SULFATE RESISTING CEMENT AS REQUIRED COMPLYING WITH S19 TRIMMING MEMBERS FOR PENETRATIONS ARE NOT NECESSARILY SHOWN.
AS3972 UNLESS NOTED OTHERWISE ON THE DRAWINGS. EXTRA RAPID HARDENING S1 ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS4100, AS/NZS4600, S20 TRIMMING MEMBERS FOR VALLEYS, FREE EDGES, RIDGES, ETC. ARE NOT NECESSARILY SHOWN,
SUPER-SULPHATED AND HIGH ALUMINA CEMENTS AND CEMENTS CONTAINING CHLORIDE SHALL NOT AS/NZS1554 AND AS/NZS HB62 U.N.O. BUT SHALL BE PROVIDED AT NO ADDITIONAL COST TO ALL EDGES OF SHEETING AT AN ANGLE OF
BE USED. THE USE OF FLY ASH AND/OR SILICA FUME AS A CEMENT SUBSTITUTE. OTHER THAN THAT S2 UNLESS NOTED OTHERWISE, ALL STEEL SHALL BE: OTHER THAN 90 DEGREES TO THE PURLIN/GIRT. REFER TO PURLIN MANUFACTURER FOR DETAILS.
PROPORTION ALLOWED AS PART OF THE "GB" CEMENT CONTENT WILL ONLY BE PERMITTED AS PART S21 THE CONTRACTOR SHALL PROVIDE ALL CLEATS AND DRILL ALL HOLES NECESSARY FOR FIXING
GRADE 300 PLUS FOR HOT ROLLED SECTIONS
OF A DESIGNED CONCRETE MIX WHICH HAS BEEN APPROVED IN WRITING BY THE CLIENT. GRADE 300 PLUS FOR MERCHANT BAR (ROUND, SQUARE AND FLAT) STEEL, TIMBER AND OTHER ELEMENTS TO STEEL WHETHER OR NOT DETAILED ON THE STRUCTURAL
C11 CONCRETE SLUMP TO BE A MAXIMUM OF 80mm UNLESS NOTED OTHERWISE ON THE DRAWINGS. GRADE 250 FOR PLATES DRAWINGS.
C12 FREE DROPPING OF CONCRETE FROM A HEIGHT GREATER THAN 1000mm IS NOT PERMITTED. GRADE C350 FOR RHS, SHS AND CHS S22 THE FABRICATION AND ERECTION OF THE STRUCTURAL STEELWORK SHALL BE SUPERVISED BY
S3 COMMERCIAL GRADE BOLTS SHALL CONFORM TO AS/NZS1111 AND AS4100. HIGH STRENGTH QUALIFIED PERSONNEL EXPERIENCED IN SUCH SUPERVISION TO ENSURE THAT ALL REQUIREMENTS
C13 SURFACES RECEIVING GROUT SHALL BE LEFT ROUGH AND FREE OF LAITANCE.
BOLTS SHALL CONFORM TO AS/NZS1252 AND AS4100. WELDS SHALL CONFORM TO AS/NZS1554 AND OF WORKPLACE HEALTH AND SAFETY AND THE DESIGN ARE MET.
C14 CONCRETE MUST BE CURED FOR SEVEN DAYS AFTER POURING.
WELDING ELECTRODES TO AS/NZS1553. THE INSPECTION AND TESTING OF WELDS SHALL BE IN S23 STRUCTURAL STEELWORK SHALL HAVE THE FOLLOWING SURFACE TREATMENT IN ACCORDANCE
C15 REINFORCEMENT IS REPRESENTED DIAGRAMMATICALLY AND NOT NECESSARILY SHOWN IN
ACCORDANCE WITH THE FOLLOWING: WITH AS/NZS2312 AND THE SPECIFICATION.
TRUE PROJECT OR SCALE.
C16 REINFORCEMENT SYMBOLS: AREA TESTING METHOD EXTENT (% OF TOTAL LENGTH) ELEMENT SURFACE PREPARATION PRIME COAT TOP COAT/S
N - NORMAL DUCTILITY CLASS HOT ROLLED DEFORMED BARS OR MESH TO AS/NZS4671 WITH fsy
SHOP FILLET WELDS VISUAL EXAMINATION 100 ALL MEMBERS (EXCEPT CLASS 1 75 MICRONS NIL
= 500 MPa HDG) NOT EXPOSED TO
SITE FILLET WELDS VISUAL EXAMINATION 100 WEATHER
R - NORMAL DUCTILITY CLASS 250 N PLAIN ROUND BAR TO AS/NZS4671 WITH fsy = 500 MPa
L - LOW DUCTILITY CLASS 500L REINFORCEMENT IS NOT TO BE USED OTHER THAN WHERE SITE FILLET WELDS ULTRASONIC OR MAGNETIC 10 ALL MEMBERS (EXCEPT CLASS 2.5 EPOXY PRIMER ACRYLIC 2-PACK
SHOWN ON DRAWINGS. LOW DUCTILITY CLASS L REINFORCEMENT IS NOT TO BE USED OTHER THAN PARTICLE TESTING HDG) EXPOSED TO 75 MICRONS 50 MICRONS
WHERE SHOWN ON DRAWINGS. BUTT WELDS, GP OR SP VISUAL EXAMINATION 100 (SITE OR SHOP) WEATHER
C17 MINIMUM COVER (mm) TO ALL REINFORCEMENT SHALL BE AS FOLLOWS U.N.O.: BUTT WELDS, GP OR SP ULTRASONIC OR MAGNETIC 100 (SITE) MEMBERS TO BE ENCASED IN CONCRETE OR FIRE SPRAYED MUST NOT BE PAINTED AND MUST BE
ELEMENT PARTICLE TESTING 10 (SHOP)
MINIMUM COVER NOTES FREE OF SCALE
S4 ALL DETAILS, GAUGE LINES, ETC., WHERE NOT SPECIFICALLY SHOWN ARE TO BE IN S24 CAMBERS - ALL RAFTERS AND BEAMS OVER 6000mm IN LENGTH SHALL BE CAMBERED 5mm
SLABS ON GROUND 30 mm CAST AGAINST 0.2 mm FORTECON DPM.
FORTECON TO BE LAPPED AND TAPED AT ALL ACCORDANCE WITH AISC DESIGN CAPACITY TABLES FOR STRUCTURAL STEEL AND AISC UPWARDS FOR EVERY 2000mm OF LENGTH UNLESS NOTED OTHERWISE ON THE DRAWINGS.
JOINTS AND TEARS. STANDARDISED STRUCTURAL CONNECTIONS.
STRIP FOOTINGS 40 mm CAST AGAINST 0.2 mm FORTECON DPM. S5 BEFORE FABRICATION COMMENCES THE CONTRACTOR SHALL SUBMIT COPIES OF THE SHOP
FORTECON TO BE LAPPED AND TAPED AT ALL DRAWINGS TO THE SUPERINTENDENT FOR REVIEW. REVIEW DOES NOT INCLUDE CHECKING OF THE
JOINTS AND TEARS. DIMENSIONS.
S6 ALL WELDS SHALL BE SP (SPECIAL PURPOSE) IN ACCORDANCE WITH AS1554. ALL BUTT WELDS
C18 MINIMUM LAP FOR ALL FABRICS SHALL BE THE SPACING OF TWO TRANSVERSE WIRES PLUS SHALL BE FULL STRENGTH COMPLETE PENETRATION WELDS. ALL ELECTRODES SHALL BE CLASS
25mm. GRADE 500N BARS SHALL BE LAPPED IN ACCORDANCE WITH THE STANDARD LAP LENGTH E48XX.
TABLE U.N.O. S7 BOLT DESIGNATION SHALL BE:
C19 WELDING OF REINFORCEMENT SHALL NOT BE PERMITTED WITHOUT THE APPROVAL OF THE 4.6/S REFERS TO COMMERCIAL BOLTS OF STRENGTH GRADE 4.6 TO AS1111 TIGHTENED TO A
ENGINEER. SNUG TIGHT CONDITION.
C20 ALL REINFORCEMENT SHALL BE SECURELY SUPPORTED IN ITS CORRECT POSITION DURING 8.8/S REFERS TO HIGH STRENGTH STRUCTURAL BOLTS OF GRADE 8.8 TO AS1252 TIGHTENED TO
CONCRETING BY APPROVED BAR CHAIRS, SPACERS OR SUPPORT BARS AT 1000mm MAXIMUM c/c A SNUG TIGHT CONDITION.
SPACING. THE CHAIR MATERIAL SHALL SUIT THE EXPOSURE CONDITIONS. 8.8/TB REFERS TO HIGH STRENGTH STRUCTURAL STEEL BOLTS OF GRADE 8.8 TO AS1252 FULLY
C21 2N12 DIAGONAL CORNER BARS 1200mm LONG ARE REQUIRED AT ALL RE-ENTRANT CORNERS TENSIONED TO AS4100 AS A BEARING JOINT (SOME SLIP ALLOWED).
AND AROUND OPENINGS IN SLABS. S8 ALL BOLTS, NUTS AND WASHERS TO BE HOT DIP GALVANISED.
C22 REINFORCEMENT LENGTHS INDICATED ARE IN THE MILLIMETRES AND ARE PLAN LENGTH ONLY.
TURN DOWNS AND CRANKS ARE NOT INCLUDED IN THAT DIMENSION.
C23 BARS SHOWN STAGGERED ON PLAN SHALL BE PLACED ALTERNATIVELY.
SL1 100mm MIN. THICK RAFT SLAB WITH 300mm WIDE x 700mm DEEP BEAMS.
3N16 BARS BOTTOM AND 2N16 BARS TOP CONTINUOUS IN ALL RAFT
FOOTING BEAMS, R8-1000 LIGATURES THROUGHOUT. SL82 MESH
CENTRAL IN SLAB, CAST ON 0.2mm DAMP PROOF MEMBRANE (DPM).
SL2 200mm MIN. THICK RAFT SLAB. N20-200 BARS TOP AND BOTTOM IN SLAB
PERPENDICULAR TO RETAINING WALL. N12-200 BARS TOP AND BOTTOM
IN SLAB PARALLEL TO RETAINING WALL. 300mm WIDE x 800mm DEEP
BEAMS. 3N16 BARS BOTTOM AND 2N16 BARS TOP CONTINUOUS IN ALL
RAFT FOOTING BEAMS, R8-1000 LIGATURES THROUGHOUT. CAST ON
0.2mm DAMP PROOF MEMBRANE (DPM)
SL2A 150mm MIN. THICK RAFT SLAB. N16-200 BARS CENTRAL IN SLAB
PERPENDICULAR TO RETAINING WALL. N12-200 BARS CENTRAL IN SLAB
PARALLEL TO RETAINING WALL. 300mm WIDE x 700mm DEEP BEAMS.
3N16 BARS BOTTOM AND 2N16 BARS TOP CONTINUOUS IN ALL RAFT
FOOTING BEAMS, R8-1000 LIGATURES THROUGHOUT. CAST ON 0.2mm
DAMP PROOF MEMBRANE (DPM).
CARPORT SETDOWN
3880
4070
4070
SL2 SL2A FFL SL2A
196.890 SL2A SL2A
POOL SLAB
(REFER SHEET 04)
140
SL2
SL1
3300
DIAGONAL BARS AT ALL
4645
RE-ENTRANT CORNERS
FFL 196.890 50mm WET AREA SETDOWN
6550
50D REBATE
23
70
10
50mm WET AREA SETDOWN
40
240 90 3100 3810 1800 90 1700
SL1
FFL 196.940 SL1
75
SL2
240
55
SL1 SL1
4485
560
240 90 SL1
1890
75
54
2720
SL2 SL2
2480
SL2
1780
SL1 SL1
1225
50mm SETDOWN
150mm SETDOWN FOR LIFT
FOUNDATION PLAN
-
PSL1 200mm MIN. THICK RAFT SLAB WITH 300mm WIDE x 700mm DEEP BEAMS.
4N16 BARS BOTTOM AND 3N16 BARS TOP CONTINUOUS IN ALL RAFT
FOOTING BEAMS, R8-300 LIGATURES THROUGHOUT. N12-200 BARS TOP
AND BOTTOM BOTH WAYS IN SLAB WITH ENDS COGGED INTO EDGE
BEAMS, CAST ON 0.2mm DAMP PROOF MEMBRANE (DPM).
4070
4070
INTO NATURAL GROUND. FFL 196.890
=(2)
PSL1
190
140
=(1)
PSL1
3300
500mm LONG N12 DOWELS AT 200mm C/C,
4645
COMPACTED FILL IN BETWEEN
FFL 196.890 100mm INTO POOL SLAB, 400mm INTO 50mm WET AREA SETDOWN
DWARF WALLS TO ACT AS
=(1)
50D REBATE
FORMWORK FOR THE SHOTCRETE 23
ON EMBEDMENT INTO POOL SLAB. 70
10
50mm WET AREA SETDOWN
40
240 90 3100 3810 1800 90 1700
7855
=(1)
PSL1
FFL 196.940
75
240
55
SHOTCRETE AND FINISHES) TO BE CONSTRUCTED AT
4485
APPROXIMATELY 196.940 FSL. TBC ON SITE BASED ON CIVIL
560
240 90 1890
CUT/FILL LEVELS AND ANY BUILDABILITY CONCERNS.
75
54
2720
2480
1780
FFL 196.890
1280
50mm SETDOWN
150mm SETDOWN FOR LIFT
SL3 110mm MIN. THICK RAFT SLAB WITH 300mm WIDE x 700mm DEEP BEAMS.
3N16 BARS BOTTOM AND 2N16 BARS TOP CONTINUOUS IN ALL RAFT
FOOTING BEAMS, R8-300 LIGATURES THROUGHOUT. SL92 MESH IN
SLAB TOP AND BOTTOM, CAST ON 0.2mm DAMP PROOF MEMBRANE
(DPM).
SL4 120mm MIN. THICK SUSPENDED BONDEK SLAB 1.0BMT. SL92 MESH
BOTTOM. f'c = 32MPa
BP2 600mm DIAMETER BORED PIER WITH 3m MINIMUM DEPTH. 8-N16 BARS
WITH R6-200 CIRCULAR LIGATURES FULL LENGTH. LONGITUDINAL BARS
COGGED INTO STIFFENED RAFT AND STRIP FOOTINGS ABOVE.
100 100
100 100
BP2 BP2
20mm Q.R. SUBBASE 20mm Q.R. SUBBASE
(98% MODIFIED COMPACTION) (98% MODIFIED COMPACTION)
990 2065
BP2 BP2
FFL 200.024
550
100mm THICK SLAB
ON GROUND.
1050 1210 SL3 SL3
REFER DETAIL A GARAGE WALL. CORE FILL BOTTOM
- 800mm DIRECTLY ABOVE SHOTCRETE
POOL WALL. N12-200 VERTICAL AND
400 GARAGE HORIZONTAL IN CORE FILLED SECTION
SUSPENDED BONDEK SLAB
SLAB 4
FFL 200.024
SLAB AROUND CORBEL SHEAR LIGS
6190
SL4
B
1000 MAX
-
4750
3815
400
N16-200 STARTER BARS 20mm COMPRESSIBLE FILLER
1430 835 6205 2785 3055 DAMP-PROOFING MEMBRANE
INTO SLAB ABOVE SLIP JOINT BETWEEN
SL3 BEAM
POOL SECTION SHOWN SHOTCRETE WALL AND
INDICATIVELY. REFER BLOCKWORK WALL
SHEET 07 FOR DETAILS
190mm CORE-FILLED
SECTION C - DROP WALL DETAIL BLOCKWORK RETAINING
WALL
N16-200 BARS CENTRAL
1000 MAX
N16-200 STARTER BARS
150
COMPACTED QUARRY SAND
OR RUBBLE (MIN 75mm)
400
UPPER FLOOR FRAMING PLAN N12-300 C/C VERTICAL AND 400mm WIDE x 700mm DEEP
HORIZONTAL BARS CENTRAL STRIP FOOTING. 4-N16 BARS POOL FOUNDATION
-
TOP AND BOTTOM. R8-300 SHOWN INDICATIVELY
SL3 BEAM LIGATURES THROUGHOUT.
DAMP-PROOFING MEMBRANE STRIP FOOTING TO BE POURED HARD
AGAINST POOL FOUNDATION TO
RESTRAIN AGAINST LATERAL MOVEMENT
DPC FLASHING
DPC FLASHING SLAB MESH
DPC FLASHING DPC FLASHING PROVIDE MIN.
SLAB MESH SLAB MESH 400 mm
4 TOP BARS
REBATE DEPTH
REBATE DEPTH SLAB MESH SLAB MESH
30 mm MIN TO
30 mm MAX
100 mm MAX
BEAM DEPTH
1000 mm MAX
150 mm COMPACTED QUARRY SAND
BEAM DEPTH
BEAM DEPTH
OR RUBBLE (MIN 75mm)
COMPACTED QUARRY SAND
BEAM DEPTH
COMPACTED QUARRY SAND
OR RUBBLE (MIN 75mm) OR RUBBLE (MIN 75mm) N12 AT 300 mm C/C VERTICAL AND
COMPACTED QUARRY SAND COMPACTED QUARRY SAND HORIZONTAL BARS CENTRAL
OR RUBBLE (MIN 75mm) DAMP-PROOFING
OR RUBBLE (MIN 75mm)
MEMBRANE
DAMP-PROOFING DAMP-PROOFING
EXTERNAL BEAM
300 mm
MEMBRANE MEMBRANE BEAM WIDTH
250 mm MIN
BEAM DEPTH
REFER TO SCHEDULE DAMP-PROOFING
EXTERNAL BEAM EXTERNAL BEAM MEMBRANE
BEAM WIDTH BEAM WIDTH DAMP-PROOFING
REFER TO SCHEDULE REFER TO SCHEDULE
MEMBRANE
EXTERNAL BEAM
EXTERNAL BEAM EXTERNAL BEAM
A DETAIL A B DETAIL B C INTERNAL BEAM DETAIL BEAM WIDTH
400 mm MIN
REFER TO SCHEDULE
BEAM WIDTH
EXTERNAL BEAM
REFER TO SCHEDULE
3:1 MAX
LONGITUDINAL /
STRAIGHT BARS
TOP AND BOTTOM
LONGITUDINAL /
NEW FOOTING
STRAIGHT BARS
FOOTING BEAM AT "L" FOOTING BEAM AT "T" DIAGONAL FOOTING BEAM TYPICAL BEAM OVERLAP DETAIL EXTERNAL BEAM TO EXISTING FOOTING
F INTERSECTIONS PLAN VIEW G INTERSECTIONS PLAN VIEW H PLAN VIEW I PLAN VIEW J CONNECTION DETAIL
BEAM
REINFORCEMENTS
D
1.5D
BEAM
REINFORCEMENTS
200 mm
CONTINUOUS TRENCH
300 mm MESH LAP 1.5D FOOTING BEAM OR
100 mm
BACKFILL IN
ACCORDANCE
D
WITH AS2870
D
NOTE: UNLESS SHOWN OTHERWISE
ON DRAWINGS PIERS SHALL BE
D
DAMP-PROOFING
DAMP-PROOFING MEMBRANE MINIMUM 1000mm LONG WITH CLEAR
MEMBRANE PIPE SPACING NOT EXCEEDING 1500mm.
ALTERNATE MESH MAY
400 mm MINIMUM BE DRAPED TO SUIT DAMP-PROOFING PIERS SHALL NOT BE USED WHERE
MEMBRANE SOILS HAVE BEEN DESCRIBED AS
COMPACTED QUARRY SAND LINE OF INFLUENCE: HAVING COLLAPSE POTENTIAL OR
OR RUBBLE (MIN 75mm) 30° FOR SAND ARE LOW BEARING STRENGTH.
45° FOR CLAY REFER TO SRFACE SOIL BORELOG.
60° FOR ROCK
TYPICAL SLAB SET-DOWN SECTION TYPICAL FOOTING BEAM SET-DOWN TYPICAL FOOTING BEAM SET-DOWN TYPICAL FOOTING BEAM SET-DOWN FOOTING ADJACENT TO SERVICE
K DETAIL L (STEP < 200 mm) SECTION DETAIL M (STEP > 200 mm BUT < 2D) SECTION DETAIL N (STEP > 2D) SECTION DETAIL O TRENCHES AND SIMILAR EXCAVATIONS
VARIES FROM
POOL BASE. N16-125 BARS TOP AND
BOTTOM, BOTH WAYS. SUPPORTED ON
DWARF WALLS AND COMPACTED FILL TO
POOL FOUNDATION BELOW.
3200 MAX
N12-200 BARS CENTRAL
200
DWARF WALL SUPPORTING
4
SHOTCRETE POOL STRUCTURE
RW2
198.452 TW 198.040
TW 199.864 A BL 196.290
TW 198.240
-
POOL FOUNDATION
ZONE 3
TW 197.640 SHOWN INDICATIVELY 75 MICRON FORTECON
TW 198.240 STARTER BARS TO MATCH MAIN WALL
LAYER TAPED AND
REMCO BENCH SEAT LAPPED AT JOINTS REINFORCEMENT LAPPED INTO
RW1A
(REMOVABLE LID) FOOTING AND BLOCKWORK WALL.
TW 196.890
TW 199.864 FFL 196.890 REFER TO NOTES FOR LAP LENGTHS.
FFL 198.565 FFL 198.999 FFL 199.816 BL 196.390
ZONE 2
RW6 POOL SLAB
FFL 200.024
BL 199.524 SECTION A - POOL WALL & BASE / RW1A DETAIL
RW1A
DIVIDING WALLS. LAP VERTICAL BARS INTO CONCRETE ABOVE
TW 198.240 REFER DETAIL ON WHERE RW1 INTERFACES WITH BONDEK SLAB
198.597 TW 199.864
SHEET 09
TW 199.864 196.787
SKIMMER BOX 190
FFL 198.453 FFL 198.763
198.659 RW1A
ZONE 1
BL 198.474 199.923 FFL 200.024
198.638 198.527
RW5
W1
FFL 199.124 TW 198.445
N16-200 CENTRAL ON 190mm THICK BLOCK WORK
RW3
196.721
198.606 TW 198.240 B
08
FFL 198.212 FFL 199.274 198.327 FFL 196.940
FFL 200.024
RW5
RW1
TW 198.240 TW 198.240
198.069
SITE FILL
3000 MAX
199.149 FFL 196.890
198.224 4 BL 196.390
197.857
198.082 290
197.091 197.307
RW4
1600
197.754
197.333 196.210
195.227 200 mm MIN THICKNESS X 600 mm MIN N20 AT 200 mm C/C TOP AND
DEPTH, 20 mm GRAVEL DRAINAGE LAYER BOTTOM BARS PERPENDICULAR
WITH 80 mm AGRICULTURAL DRAINAGE TO THE RETAINING WALL
PIPE WRAPPED IN FILTER FABRIC AT
SL2 SL1
BASE. LAID ON FALL TO ALLOW FOR
DRAINAGE AWAY FROM WALL.
200
75 MICRON FORTECON SL2 BEAM
LAYER TAPED AND SL2 BEAM
600
LAPPED AT JOINTS N12 AT 200 mm C/C TOP AND
RETAINING WALL PLAN BOTTOM BARS PARALLEL TO THE
- RETAINING WALL
3000 MAX.
2400 MAX.
190mm THICK CORE-FILLED N12-200 BARS CENTRAL N12-400 HORIZONTAL BARS
SITE FILL
BLOCKWORK THROUGHOUT
2000 MAX.
SITE FILL N12-400 HORIZONTAL BARS
SITE FILL 1600 MAX. N12-200 BARS CENTRAL N12-400 HORIZONTAL BARS THROUGHOUT
THROUGHOUT
N16-200 BARS CENTRAL
800
THROUGHOUT N12-200 BARS C/C TOP AND
BLOCKWORK AT HEIGHT 0 TO BLOCKWORK AT HEIGHT 0 TO
400mm 800mm BOTTOM BARS PARALLEL TO
400
RETAINING WALL
200
75 MICRON FORTECON 75 MICRON FORTECON 75 MICRON FORTECON
LAYER TAPED AND STARTER BARS TO MATCH MAIN WALL LAYER TAPED AND STARTER BARS TO MATCH MAIN WALL LAYER TAPED AND STARTER BARS TO MATCH MAIN WALL
LAPPED AT JOINTS REINFORCEMENT DEVELOPED INTO LAPPED AT JOINTS REINFORCEMENT DEVELOPED INTO LAPPED AT JOINTS REINFORCEMENT DEVELOPED INTO
FOOTING AND BLOCKWORK WALL. FOOTING AND BLOCKWORK WALL. FOOTING AND BLOCKWORK WALL. 900
REFER TO NOTES FOR LAP LENGTHS. REFER TO NOTES FOR LAP LENGTHS. REFER TO NOTES FOR LAP LENGTHS.
STARTER BARS TO MATCH MAIN WALL
N12-200 BARS C/C TOP AND
REINFORCEMENT DEVELOPED INTO
BOTTOM BARS PERPENDICULAR
FOOTING AND BLOCKWORK WALL.
TO RETAINING WALL
RW2 (0 TO 1.6m) DETAIL RW2 (1.6 TO 2m) DETAIL RW2 (2m TO 2.4m) DETAIL REFER TO NOTES FOR LAP LENGTHS.
W1 DETAIL
190 190 190
mm MIN DEPTH, 20 mm
GRAVEL DRAINAGE LAYER 190mm THICK CORE-FILLED
BLOCKWORK AT HEIGHT N12-200 BARS C/C TOP AND BOTTOM
WITH 80 mm AGRICULTURAL
400mm TO 2000mm 190mm THICK CORE-FILLED BARS. REFER TO RW4/W1 DETAIL.
DRAINAGE PIPE WRAPPED IN
BLOCKWORK POOL SECTION SHOWN
FILTER FABRIC AT BASE. LAID
ON FALL TO ALLOW FOR N12-200 BARS CENTRAL INDICATIVELY
DRAINAGE AWAY FROM WALL.
190mm THICK CORE-FILLED N12-200 BARS CENTRAL
200 mm MIN THICKNESS X 600 mm MIN BLOCKWORK N12-200 BARS C/C TOP AND BOTTOM
2000
SITE FILL DEPTH, 20 mm GRAVEL DRAINAGE LAYER BARS. REFER TO RW4/W1 DETAIL.
WITH 80 mm AGRICULTURAL DRAINAGE N12-200 STARTER BARS
N12-400 HORIZONTAL BARS
THROUGHOUT PIPE WRAPPED IN FILTER FABRIC AT
BASE. LAID ON FALL TO ALLOW FOR N12-200 BARS CENTRAL
N12-400 HORIZONTAL BARS
DRAINAGE AWAY FROM WALL.
3000 MAX
N12-200 BARS C/C TOP THROUGHOUT
3000
AND BOTTOM BARS
PERPENDICULAR TO 290mm THICK CORE-FILLED
RETAINING WALL BLOCKWORK AT HEIGHT 0 TO
N12-400 HORIZONTAL BARS
400mm
400
THROUGHOUT
+197.94
200
SOIL HEIGHT
1000 MAX
1000
1400 MAX
N12-200 BARS C/C TOP N12-200 BARS C/C TOP
1500 AND BOTTOM BARS AND BOTTOM BARS COMPACTED
PERPENDICULAR TO PERPENDICULAR TO NATURAL
STARTER BARS TO MATCH MAIN WALL GROUND FILL
N12-200 BARS C/C TOP AND RETAINING WALL RETAINING WALL
REINFORCEMENT DEVELOPED INTO
BOTTOM BARS PARALLEL
FOOTING AND BLOCKWORK WALL.
TO RETAINING WALL
REFER TO NOTES FOR LAP LENGTHS. VARRIES FROM +196.94 TO +197.94 +196.94 +196.94
200
200
RW3 DETAIL
2400 MAX
1000 1000
SUSPENDED SPAN
N12-200 BARS C/C TOP AND STARTER BARS TO MATCH MAIN WALL N12-200 BARS C/C TOP AND STARTER BARS TO MATCH MAIN WALL REFER TO RW4/RW5 WALL
BOTTOM BARS PARALLEL REINFORCEMENT DEVELOPED INTO BOTTOM BARS PARALLEL REINFORCEMENT DEVELOPED INTO AND FOOTING DETAIL
TO RETAINING WALL FOOTING AND BLOCKWORK WALL. TO RETAINING WALL FOOTING AND BLOCKWORK WALL.
REFER TO NOTES FOR LAP LENGTHS. REFER TO NOTES FOR LAP LENGTHS.
1100
200mm MINIMUM THICKNESS SHOTCRETE 200mm MINIMUM THICKNESS SHOTCRETE
VARIES FROM
VARIES FROM
POOL BASE. N12-200 BARS TOP AND POOL BASE. N12-200 BARS TOP AND
BOTTOM, BOTH WAYS. SUPPORTED ON BOTTOM, BOTH WAYS. SUPPORTED ON 200mm MINIMUM THICKNESS SHOTCRETE
DWARF WALLS AND COMPACTED FILL TO DWARF WALLS AND COMPACTED FILL TO
VARIES FROM
POOL FOUNDATION BELOW. POOL FOUNDATION BELOW. BOTTOM, BOTH WAYS. SUPPORTED ON
DWARF WALLS AND COMPACTED FILL TO
POOL FOUNDATION BELOW.
200
200
SHOTCRETE POOL STRUCTURE SHOTCRETE POOL STRUCTURE SHOTCRETE POOL STRUCTURE
200
INTO POOL BASE AND POOL INTO POOL BASE AND POOL
WALL. REFER TO NOTES FOR WALL. REFER TO NOTES FOR
LAP LENGTHS. COMPACTED FILL LAP LENGTHS.
COMPACTED FILL
COMPACTED FILL
N12-200 L-BARS TO MATCH MAIN
WALL REINFORCEMENT LAPPED
INTO POOL BASE AND POOL
WALL. REFER TO NOTES FOR
LAP LENGTHS.
POOL FOUNDATION
POOL FOUNDATION
SHOWN INDICATIVELY
SHOWN INDICATIVELY
POOL FOUNDATION
SHOWN INDICATIVELY
POOL WALL DETAIL - ZONE 1 POOL WALL DETAIL - ZONE 2 POOL WALL DETAIL - ZONE 3
HORIZONTAL THROUGHOUT
150
150mm MIN THICKNESS DIVIDING WALL. 150mm MIN THICKNESS DIVIDING WALL.
EXTERNAL POOL WALLS N16-200 BARS VERTICAL EACH FACE, N16-200 BARS VERTICAL EACH FACE,
AND POOL FOUNDATION N12-200 BARS HORIZONTAL EACH FACE N12-200 BARS HORIZONTAL EACH FACE
SHOWN INDICATIVELY
REMCO COVER