AUTOMATIC

SYNCHRONISER
KSQ104NA

 Precision automatic synchronisation

 Volt free Raise/Lower outputs

 Breaker close time compensation

 Synchronise Inhibit input

 Relative frequency indication


 Integral LED Synchroscope
Description Operation
The KSQ104 provides both visual The integral synchronising relay contacts (terminals 11-12) will close
indication, control relay signal and volt only when the two supplies are within the set frequency difference,
free raise/lower outputs necessary to the inhibit input (terminals 8-9) is closed and the generator frequency
permit automatic synchronising of two is greater than the busbar frequency. Indication of this condition is
supplies. given by the green “Sync relay” lamp illuminating on the display.
Any two phases can be used for synchronising as long as it is
The “Rotating LED” lamp display indicates the same two phases on both side of the breaker.
the frequency and phase angle
relationship of the two sources. An external voltage comparator relay, KRV43B, can be connected to
terminals 8-9 to provide voltage error protection.
Indication of relative frequency is by
illumination of the “+” symbol (too fast) The KSQ104 compensates for circuit breaker closing time. This can
and the “-“ symbol (too slow). be adjusted to match the characteristic of the controlled breaker.

The raise/lower outputs are adjustable KSQ104 is rated for continuous operation and therefore can be left
pulses proportional to the relative connected when not in use.
frequency of the monitored supplies.

Voltage:
100-120V AC
220-240V AC
380-415V AC
Relays shown de-energised. 440V AC
Nominal +/- 10%
Relay energises when generator
frequency is within set Frequency:
parameters and not inhibited. 45-65Hz

Terminals 8 and 9 need to be Contact Rating:


linked if external inhibit is not AC : 100VA – 250V/2A max.
used. DC : 50W – 100V/1A max.

The relay contact will remain


closed after synchronising until Adjustments:
one of the inputs is removed or
Max Sync
the breaker is open. Frequency Diff. : 0 – 2Hz

Breaker closing
Delay : 0 to 120mS

Pulse length : 0.1-1.6 sec


Pulse rate : 10-60 ppm

ORDERING Voltage input :


INFORMATION

Megacon – Norway – UK – Denmark www.megacon.com REF: KSQ104NA-MPD-0109