GENERAL NOTES:
95
1. ALL ELECTRICAL WORKS SHALL CONFORM TO THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE,
TO THE RULES AND REGULATIONS OF LOCAL AND NATIONAL AUTHORITIES CONCERNED AND THE
270
400
2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE, 230 V AC, 60 Hz.
95
230
3. MINIMUM SIZE OF WIRE AND CONDUIT SHALL BE 3.5 MM2 THHN AND 15 MM (1/2") NOMINAL DIAMETER
RESPECTIVELY UNLESS OTHERWISE SPECIFIED ON PLANS.
370
250
125
4. FOR EACH SPARE CIRCUIT IN PANEL BOARD, PROVIDE AN EMPTY CONDUIT 20 MM (3/4") DIAMETER
TERMINATING TO A COVERED SQUARE BOX.
5. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL BE BRAND NEW AND OF APPROVED TYPE FOR BOTH
LOCATION AND PURPOSES.
590
CEILING LINE 6. ALL METAL FRAMES SHALL BE PROPERLY AND ADEQUATELY GROUNDED, GROUND WIRE SHALL BE
2990
(VERIFY SPECS)
SCREEN DISPLAY
7. MOUNTING HEIGHTS SHALL BE AS FOLLOWS:
CEILING LINE
2025
C. PANEL BOARD ------------------------------- 1.40 M ABOVE FLOOR FINISH R WITHIN COUNTER OR MODULES
945
PROVIDED THAT IT IS ACCESSIBLE FOR IMMEDIATE MAINTENANCE),
8. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THW" UNLESS OTHERWISE
INDICATED IN THE PLAN. THE MINIMUM SIZE OF WIRE FOR POWER AND LIGHTING CIRCUIT HOMERUN SHALL BE
3.5mm² AND INSULATED FOR 600 VOLTS. SMALLEST RACEWAY SHALL BE 15mmØ TRADE/NOMINAL SIZE. I
9. ALL OUTLET BOXES SHALL BE GALVANIZED GAGE NO. 16 DEEP TYPE WITH FACTORY KNOCKOUTS.
400
CEILING LINE
10. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A DULY
95
REGISTERED ELECTRICAL ENGINEER.
6000
POWER LAYOUT
SCALE 1:50 MTS
5835
(CEILING)
c c
SPARE
590
S S S
ab cd ef
b
c
b
c
590
(PROPERTY)
(CEILING)
125
2835
3000
c c c c
PLYCLOTH
LED BACKLIT
d d c c
SERVICE ENTRANCE RISER DIAGRAM
(VERIFY SPECS)
SCREEN DISPLAY
LEGEND SECONDARY LINES
595
S S S
ab cd ef LIGHTING SWITCH 25 AT,2P
15AT/50AF 20AT/50AF
SCREEN DISPLAY 2P.230V 2P.230V
20AT/50AF 20AT/50AF
2P.230V 2P.230V
LIGHTING LAYOUT
SCALE 1:50 MTS