TECHNICAL DATA FOR CURTAIN WALL FACADE

Document no.
THE PALM SIX SENSES Submittal Ref.:
Project Name _______________

Client SELECT GROUP Revision No. 00

Consultant BREWER SMITH BREWER GULF Date February 16, 2023

SPECIFICATION - SS_25_30_20_25 EXTERNAL DOORSET SYSTEMS

Specification
Item Description Specified Proposal
Reference

Ss_25_30_20/290 Compliance with 2. General requirements: Include details of performance related to Alumil S77 Hinged System a thermal break system for casement, fixed,
performance the elements of construction. Door/ door hardware to be inline with projected windows and heavy‐duty doors.
requirements Dubai Design Building code and international standards.
The system is certified according to the following test method below
from European (EN) Standard by the IFT ROSENHEIM (Germany).

• EN 12207 ‐ Air Permeability


• EN 12208 ‐ Water Penetration
• EN 12210 ‐ Windload Resistance
• EN 13115 – Operating Force
• EN 13115 – Mechanical
• EN 13049 – Impact Resistance

Ss_25_30_20/230 Resistance to wind 1. Resistance to wind load: As per the specialist façade contractor's The system was tested and certified by IFT ROSENHIEM (GERMANY).
load scope to meet the project design requirements.
Test Method: EN 12211
Classification: EN 12210

Typology: Double tilt and turn casement door


Size: 2400mm x 2400mm
Specification
Item Description Specified Proposal
Reference

Design loads up to ±1600 Pa


Safety loads up to ±2400Pa (1.5 of the design load)

Test result: Class C4/B4


Please refer to the attached S77 test report.

Ss_25_30_20/235 Air permeability 1. Air permeability: As per the specialist façade contractor's scope to The system was tested and certified by IFT ROSENHIEM (GERMANY).
meet the project design requirements.
Test Method: EN 1026
Classification: EN 12207

Typology: Double tilt and turn casement door


Size: 2400mm x 2400mm

Test of air infiltration is up to +-600 Pa.


Test result: Class 4

Please refer to the attached S77 test report.

Ss_25_30_20/240 Acoustic performance 1. Sound insulation rating: In line with the Acoustician design General observation varies for specific typologies/ dimensions/
requirements. configurations according to the design and elevation typology and
spans and glazing of your specific project.

Sound transmission coefficient for the assembly curtain wall façade is


to be subjected majorly to the STC of the glass to be use by others