15 Towers - Deviation Sheet - 149182-TRASH CHUTES

Sr.
Category Latest SPEC No. Page Spec Description Deviation
No.
2.1 PERFORMANCE 2.1 PERFORMANCE
REQUIREMENTS REQUIREMENTS 1. Test Pressure:
1. Test Pressure: Test at atmospheric Test at atmospheric (neutral) pressure
(neutral) pressure according to NFPA according to NFPA 252 (82) or UL 10B
252 or finish with 1.5 hr fire rating.
UL 10B. 2. Intake Doors: Side hanged intake door
2.Intake Doors: Labeled, 1-1/2-hour fire- Labeled, NFPA 82 standards and UL
resistance rated with 30-minute 10B, 1-1/2-hour fire-resistance rated
temperature rise of 140 deg C. with 30-minute temperature rise of 140
TRASH CHUTES
B. Discharge-Door Assemblies: Fire- deg C.
149182 -
149182 - resistive door construction Labeled, 1- B.Discharge-Door Assemblies: have no
1 Special Equipment E18066-0100D-FD-
Page 3of 7 1/2-hour fire resistance rated according UL certificate or NFPA 252,but
00-G00-SPC-15A-
to NFPA 252 or UL 10B requirements complied with Fire-resistive door
ME-01 REV 2
for fire-rated door assemblies. construction Labeled, 1-1/2-hour fire
C.Electrical Components, Devices, and resistance rated .
Accessories:Listed and labeled as C.Electrical Components, Devices, and
defined in NFPA 70, by a qualified Accessories:Listed and labeled as
testing agency, and marked for intended defined in NFPA 70,or CE,or IEC,or
location and application. Make List, by a qualified testing agency,
and marked for intended location and
application.

2.3 DOORS 2.3 DOORS


A.3.Finish: Manufacturer's standard A.3. Finish: Manufacturer's standard
satin or No. 3 directional polish. satin or No. 4 directional polish.
9.Baffles: Rubber backdraft baffles at 9. Baffles: 2mm thickness Rubber
each intake backdraft baffles at each intake
C.1.Locate smoke detector outside C.1.Locate smoke detector outside
discharge door with solenoid to close discharge door with no solenoid to
discharge door. close discharge door .
TRASH CHUTES D.Access-Door Assemblies: D.Access-Door Assemblies: Hinged
149182 -
149182 - Manufacturer's standard ASTM A door instead of access dorr, No. 4
2 Special Equipment E18066-0100D-FD-
Page 4of 7 240/A 240M, Type 302/304, stainless- finish manufactured as per NFPA 82 ;
00-G00-SPC-15A- steel doors with trim; constructed as Access door is for manual operation
ME-01 REV 2 required for performance and have no interlocking 。
requirements indicated; with frame
suitable for the enclosing chase
construction; and in satin or No. 3
directional polish finish; equipped
with cylinder locks that release latch
with keys that are removable only
when cylinder is locked.

2.4 DIVERTERS 2.4 DIVERTERS


C. Controls: Integrated, electronic C. Controls: Integrated, electronic
master control unit in discharge room master control unit in discharge room
TRASH CHUTES and electronic controls at each intake and electronic controls at each intake
149182 - door, including self-diagnostic door, have no self-diagnostic
149182 - program for whole system. program .
3 Special Equipment E18066-0100D-FD-
Page 5of 7 D. 1. Phase: Single phase. D. 1. Phase: Single phase or three
00-G00-SPC-15A-
ME-01 REV 2 2. Volts: 220V. phase.
2.5 ACCESSORIES 2. Volts: 220V or 380V.
D. Intake-Door Baffles: Rubber D.Intake-Door Baffles: PVC Rubber
baffles, 3 mm thick. baffles, 2 mm thick.
15 Towers - Deviation Sheet - 149182-TRASH CHUTES
Sr.
Category Latest SPEC No. Page Spec Description Deviation
No.
2.6 FABRICATION 2.6 FABRICATION
C.Roof Vent: Fabricate vent unit as full- C.Roof Vent: Fabricate vent unit as full-
size extension of chute, open to the size extension of chute, open to the
atmosphere. Extend vent to height above atmosphere. Extend vent to height above
roofing surface as indicated on roofing surface as indicated on
TRASH CHUTES Drawings, a minimum of 920 mm as per Drawings, a minimum of 900mm as per
149182 -
149182 - NFPA 82. Equip vent with full insect NFPA 82. Equip vent with full insect
4 Special Equipment E18066-0100D-FD-
Page 6of 7 screening and metal explosion-release screening and metal explosion-release
00-G00-SPC-15A- cap. Fabricate with roof- deck flange, cap or bird mesh is provided along with
ME-01 REV 2 counterflashing, and clamping ring of canopy. Fabricate without roof- deck
nonferrous metal compatible with chute flange counterflashing, and clamping
metal or MOC same as chute body. ring of nonferrous metal compatible with
chute metal or MOC same as chute body.

TRASH CHUTES 2.2 CHUTES 2.2 CHUTES


149182 - External Reinforcing for Offsets: External Reinforcing for Offsets:
149182 - Additional thickness of (2-mm) thick Additional thickness of ( 1.5mm~2-mm )
5 TRASH CHUTE E18066-0100D-FD-
Page 3of 7 chute metal with bracing to structure.
00-G00-SPC-15A- thick chute metal with bracing to
ME-01 REV 2 structure.