Fan Blades made of FRP, propeller with maximum tip speed of 50 meter per
8 second while the supplier proposed speed may accepted subject to submit Noted with thanks
matching standard
Refer to Division 16 "Common Electrical Requirements for HVAC Equipment" The proposed are field erected
9 Not applicable cooling towers.And Division 16 is not The proposed are field erected cooling towers.
for general requirements for factory installed motors as per clause 2.3-A
in SPEC of CUC
Supplier reply about ST. ST. crane and gantry required for motor and gear
removal as per clause 2.3-H may accepted subject to supplier guarantee
1 Comply
the painting material withstand humid site conditions coming from TSE
0
water and giving more details
Not accepted for supplier reply about seismic & vibration control direct
isolation (not applicable) since the supplier/contractor requested to submit
1 Noted Noted Post order activity for structural structural analysis.
seismic/vibration control calculations for approval as per specs clauses 1.5-
1
A, 2.4 & 3.2
Submit coordination drawing between the submitted cooling towers Kelvion will coordinate with the contractor for
1 Comply as remarks
including all accessories and piping with sufficient service area and design cooling tower related inputs.
4
available area
Noted. NFPA 70 refers to the installation of
installations for electrical components to be listed and labeled by NFPA 70 electrical conductors and control panels, which
1 as per clause 1.7-B (NFPA 70 related to bench work of safe electrical design, By contractor is by contractor. However, Kelvion will
5 installation and test to protect people & property from electrical hazard) coordinate with the contractor for cooling tower
related motor.
Provide safety plan comply to OSHA to be applied during delivery, storing, Noted will submit method statement
1 By contractor
handling, assembly and erection separately for approval
6
The proposed cooling towers are sized with 5%
Recheck for the fan power consumption where the motor power to be reserve capacity. Moreover, at 100% capacity the
1 Comply as remarks
25% more than the break fan power difference in actual design fan shaft power to the
7
installed capacity is approximately 20%.