You are on page 1of 8

ABENER

Data sheet
Title:
BSDG
BSDG Generator
Generator set
set catalogue
catalogue data
data sheet
sheet
Client: Saudi Electricity Company

Project: Construction of Waad Al-Shamal ISCCPP


Contract No.: 4400006770

Document No.: 4011-DSH-CAT-079-442-0001


Revision: 01
Date: 2017/05/08
ABENER

Issued by:

Mª del Mar Sanz – Proyect Manager. Finanzauto, S.A.

Checked by:

Mª del Mar Sanz – Proyect Manager. Finanzauto, S.A.

Reviewed by:
S.A.
Eduardo García – Technical Manager. Finanzauto, SA.

Fernando Carrasco Hidalgo-Barquero. Abener Electronic Signature

Approved by:

Victor Trabadela Molina. Engineering Director. Abener Electronic Signature

"© This document is property of Abener. Its total or partial reproduction is strictly forbidden by any means, as well as its distribution to
third parties without the express written consent of client”

If for exceptional reasons, due to specific aspects of the project (eg: project confidential information, legal requirements or local
regulations and/or contractual requirements of the client), there was a need to modify the requirements included in this procedure,
these changes must be properly documented in the quality, environment and health and safety plan of the project, prior approval from
the company headquarters management system department

The original one of this document is approved and filed in document management system application
01

4011-DSH-CAT -079-442-0001
ABENER BSDG Generator set catalogue data sheet

Revision: Date: Page:


01 2017/05/08 3 of 8

Revision control sheet

Purpos Checked Reviewed Approved


Revision Date Reason for revision Issued by
e by by by

00 2017/03/23 FI First edition MSR MSR EGC/FCHB VTM

01 2017/05/08 FI CRS00895 MSR MSR EGC/FCHB VTM

Preliminary or pending information

Edition Sections Concepts Status

Document status:

☐ For approval.

☒ For information.

Critical:

☐ Yes

☒ No

The original one of this document is approved and filed in document management system application
4011-DSH-CAT -079-442-0001
ABENER BSDG Generator set catalogue data sheet

Revision: Date: Page:


01 2017/05/08 4 of 8

Table of contents:

1 Introduction ........................................................................................................ 5

2 Genset technical data sheet............................................................................... 5

The original one of this document is approved and filed in document management system application
4011-DSH-CAT -079-442-0001
ABENER BSDG Generator set catalogue data sheet

Revision: Date: Page:


01 2017/05/08 5 of 8

1 Introduction

The technical data were based on the TSS-DM8858-02-EPG-9410507.pdf and Caterpillar


Technical Marketing Information (TMI).

2 Genset technical data sheet

Model: C175-20

Engine Feature code: 175DR1G

Generator arrangement: 2628300

60 Hz - 1800 rpm – 13800 V

Rating Type: Prime

Fuel Strategy: Low Fuel Consumption

Package performance

Genset Power Rating without Fan @ 0.8 Power Factor: 3600 ekW

Genset Power Rating: 4500 KvA

Aftercooler (Separate Circuit): 48 ºC

Fuel consumption

100% Load: 922,4 l/hr

75% Load: 667,8 l/hr

50% Load: 471,8 l/hr

25% Load: 266,1 l/hr

The original one of this document is approved and filed in document management system application
4011-DSH-CAT -079-442-0001
ABENER BSDG Generator set catalogue data sheet

Revision: Date: Page:


01 2017/05/08 6 of 8

Engine specifications

Engine model: C175-20 SCAC, V-20, 4-stroke Water-Cooled Diesel

Compression Ratio: 15:3:1

Aspiration: Turbo Aftercooled

Governor Type: ADEMTM A4

Fuel system: Common Rail

Bore: 175 mm

Displacement: 105,8 l

Stroke: 220 mm

Cooling system

Engine Coolant Capacity: 440 l

Inlet air

Combustion Air Inlet flow Rate: 309,5 m3/min

Max. Allowable Combustion Air Inlet Temp: 95ºC

Exhaust system

Exhaust Stack Gas Temperature: 458 ºC

Exhaust Gas Flow Rate: 775,3 m3/min

Exhaust System Backpressure (Max. Allowable): 6,7 kPa

The original one of this document is approved and filed in document management system application
4011-DSH-CAT -079-442-0001
ABENER BSDG Generator set catalogue data sheet

Revision: Date: Page:


01 2017/05/08 7 of 8

Heat rejection

Heat Rejection to Jacket Water: 1857 kW

Heat Rejection to Exhaust (total): 3459 kW

Heat Rejection to Aftercooler: N/A

Heat Rejection to Atmosphere from Engine: 194 kW

Heat Rejection to Atmosphere from Generator: 217,6 kW

Alternator

Motor starting Capability @30% Voltage Dip: 10780 skVA

Current: 188,3 A

Frame Size: 3068

Excitation: PM

Temperature Rise: 80ºC (generator temperature rise is based on a 40ºC ambient per NEMA

MG1-32).

Temperature Rise over an ambient temperature of 50ºC: 90ºC

Emissions (Nominal) (Note 1)

NOx: 2816,7 mg/Nm3

The original one of this document is approved and filed in document management system application
4011-DSH-CAT -079-442-0001
ABENER BSDG Generator set catalogue data sheet

Revision: Date: Page:


01 2017/05/08 8 of 8

CO: 303,2 mg/Nm3

HC: 69,9 mg/Nm3

PM: 18,2 mg/Nm3

NOTES:

Note 1: Emissions data measurement procedures are consistent with those described in EPA

CFR 40 Part 89, Subpart D&E and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is

based on steady state operating conditions of 77ºF, 28,42 inHG and number 2 diesel fuel with

35º API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to

instrumentation, measurement, facility and engine to engine variations. Emissions data is

based on 100% load and thus cannot be uses to compare to EPA regulation which use values

based on a weighted cycle.

Applicable Codes
Applicable Codes and
and Standards:
Standards: IEC60034-1,
IEC60034-1, ISO3046,
ISO3046, ISO8528,
ISO8528, NEMA
NEMA MG1-22,NEMA
MG1-22,NEMA
MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.

PRIME: Output available with varying load an unlimited time. Average power output is 70% of

the prime power rating. Typical peak demand is 100% of prime rated ekW with 10% overload

capability for emergency use for a maximum of 1 hour in 12. Overload operation cannot

exceed 25 hours per year.

Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046

standard conditions.

Fuel rates are based on fuel oil of 35º API (16ºC, gravity having an LHV of 42780 kJ/kg when

used at 29ºC and weighing 838,9 g/l.

The original one of this document is approved and filed in document management system application