INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com
Optional accessory:
Signature:
(for printed version)
Date:
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended
STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards
IEC 60079-1:2007-04 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:6
IEC 60079-31:2008 Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'
Edition:1
IEC 60079-7:2006-07 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
Edition:4
This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.
Test Reports:
GB/BAS/ExTR13.0310/00 GB/BAS/ExTR16.0263/00
EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:
The range of induction motor of frame size 160 to 200 comprises a stator frame, endshields and main and auxiliary terminal boxes all
fabricated from cast iron. The single ended drive shaft has an external cooling fan at the non-drive end. The terminal box cover fasteners are
grade 8.8/12.9 steel or grade A2/4-70 or 80 stainless steel.
2. The motors may be provided with integral leads, which must be suitably protected and terminated within an enclosure suitable for the conditions of
use.
3. When provided with a breather-drain to IECEx CSA 12.0005U the motors are excluded from Group I, and are limited to temperature classification T5
to T2 Ta -55oC to + 50oC, or T4 to T2 Ta -55oC to + 80oC, and have an IP rating of IP6X.
4. The maximum surface temperature was determined without a dust layer. The end user shall prevent a dust layer forming on the motors.
6. Only suitably certified cable gland and stuffing boxes can be fitted on the Group I terminal boxes.
IECEx Certificate
of Conformity
Certificate No.: IECEx BAS 13.0142X Page 4 of 4
To permit the construction change for Group I motors only; between the terminal box and motor frame, such that the terminal box shares the
same internal free volume with the winding enclosure.
Annex:
The range of induction motor of frame size 160 to 200 comprises a stator frame, endshields and main and auxiliary terminal boxes all
manufactured from cast iron. The single ended drive shaft has an external cooling fan at the non-drive end. The terminal box cover
fasteners are grade 8.8/12.9 steel or grade A2/4-70 or 80 stainless steel.
The frames are provided with a terminal neck for the main terminal box. A single auxiliary terminal box may be attached to the side of the
main terminal box. The wall between the terminal box and the motor frame is provided with flameproof potted cable bushings for the
winding tails and auxiliary cables for thermal sensors etc. The terminal boxes may be designated flameproof Ex d, increased safety Ex e
within the provisions of this report or increased safety terminal boxes as permitted on IECEx BAS 10.0099X.
The motors have rolling element bearings, are foot or flanged mounted for horizontal and vertical use and may be provided with anti-
condensation heaters rated as indicated below.
The motors are rated from 220V to 1140V when supplied with an Ex d terminal box , or from 220V to 690V when supplied with an Ex e
terminal box, 50/60Hz or variable frequency up to a maximum of 120Hz when supplied from a type PWM inverter manufactured by WEG
or any other inverter having identical parameters affecting the thermal performance of the motor. The maximum voltage on the auxiliary
terminals is 440V.
The motors have a maximum rating as indicated below for use in a maximum ambient temperature of 40 oC when continuously rated for
S1 duty and connected to a 3 phase supply having form and symmetry not worse than that defined in IEC 60034-1 and operated within
the defined voltage and frequency limits for Zone A.
The motors are de-rated in accordance with the manufacturer’s instructions for use with variable frequency supplies, a maximum ambient
temperature between 40oC and 80oC, altitudes above 1000m, S2 to S9 duty and a service factor of 1.0 to 1.25.
The motors can be provided with various seal arrangements and materials for ingress protection IP55, IP65 and IP66.
Options include a double ended shaft, integral leads, anti-condensation heaters, thermal protectors, forced ventilation and a breather-
drain to IECEx CSA 12.0005U.
Cable entry holes are provided as specified on the certified drawings for the accommodation of flameproof cable entry devices, with or
without the interposition of a flameproof thread adapter. Unused entries are to be fitted with suitable certified flameproof stopping plugs.
The cable entry devices, thread adapters and stopping plugs shall be suitable for the equipment, the cable and the conditions of use and
shall be certified as Equipment (not a Component) under an EC Type Examination Certificate to Directive 94/9/EC.
When used in an explosive dust atmosphere the cable entry devices shall maintain the ingress protection of the enclosure.
Variation 1.1
The motors may be alternatively marked for gas groups IIA, IIB I, dust groups IIIB, IIIA, temperature classifications of T3, and T2 without
an increase in ambient temperature above 80oC, ingress protection IP5X, IP6X, gas only and dust only as indicated below.
I M2 G Ex d I T* Ta -**oC to + **oC Mb
Variation 1.2
Group I motors of frame sizes 160 to 200 C2 classified as Category 4, have a single flameproof enclosure. There is no separation
between the terminal box and motor frame. In this arrangement the equipment is marked as follows:
I M2 G Ex d I T4 Mb Mining1
1
Only for category 4