You are on page 1of 9

IECEx Certificate

of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

Certificate No.: IECEx INE 12.0010X Page 1 of 4 Certificate history:


Issue 1 (2016-08-24)
Status: Current Issue No: 2 Issue 0 (2014-11-28)

Date of Issue: 2020-04-02

Applicant: WEGeuro Indústria Eléctrica S.A


Rua Eng. Frederico Ulrich
Zona Industrial da Maia, Sector V
4470-605 Maia
Portugal

Equipment: Three-phase asynchronous tube cooled motors and generators type W22Xdb B...T... 500... up to 710...or
W22Xdb M...T... 500... up to 710...

Optional accessory:

Type of Protection: db, db eb, db ia, db ib, db eb ia, db eb ib, tb, ia tb, ib tb

Marking: Ex db IIB T4 or T3 Gb, Ex db eb IIB T4 or T3 Gb, Ex db ia IIB T4 or T3 Gb, Ex db eb ia IIB T4 or T3 Gb, Ex db ib IIB T4
or T3 Gb, Ex db eb ib IIB T4 or T3 Gb

Ex db I Mb, Ex db eb I Mb, Ex db ia I Mb, Ex db eb ia I Mb, Ex db ib I Mb, Ex db eb ib I Mb

Ex tb IIIC T125°C or T135°C Db, Ex ia tb IIIC T125°C or T135°C Db, Ex ib tb IIIC T125°C or T135°C Db

Approved for issue on behalf of the IECEx Thierry HOUEIX


Certification Body:

Position: Ex Certification Officer

Signature:
(for printed version)

Date:

1. This certificate and schedule may only be reproduced in full.


2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting www.iecex.com or use of this QR Code.

Certificate issued by:


INERIS
Institut National de l'Environnement Industriel et des Risques
BP n2 / Parc Technologique ALATA
F-60550 Verneuil-en-Halatte
France
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0010X Page 2 of 4

Date of issue: 2020-04-02 Issue No: 2

Manufacturer: WEGeuro Indústria Eléctrica S.A


Rua Eng. Frederico Ulrich
Zona Industrial da Maia, Sector V
4470-605 Maia
Portugal

Additional WEGeuro - Indústria Eléctrica, S.A


manufacturing Rua Antonio Joaquim Campos
locations: Monteiro, n°510
Santa Cristina do Couto
4780-165 Santo Tirso
Portugal

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended

STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards

IEC 60079-0:2017 Explosive atmospheres - Part 0: Equipment - General requirements


Edition:7.0

IEC 60079-1:2014-06 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:7.0

IEC 60079-11:2011 Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
Edition:6.0

IEC 60079-31:2013 Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t"
Edition:2

IEC 60079-7:2017 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
Edition:5.1

This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.

TEST & ASSESSMENT REPORTS:


A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in:

Test Report:
FR/INE/ExTR14.0068/01

Quality Assessment Report:


GB/BAS/QAR07.0032/08
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0010X Page 3 of 4

Date of issue: 2020-04-02 Issue No: 2

EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:

Range of three-phase asynchronous motor with frame in welded steel and endshields in welded steel or cast iron. Motors can be fitted with
different terminal boxes and auxiliary boxes protected by flameproof enclosure or by increased safety. This equipment is also protected by
type protection "tb" for using in dust explosive atmospheres.

The motor may be designed with one up to four speed. Mounting position of motor can be either horizontal or vertical.

The terminal boxes made in cast iron, steel or stainless steel can be fitted directly on the motors or by an adaptor. Terminal boxes can be
mounted on the top or left/right side, located in any position of a 180° range around the upper part of the frame.

Cooling types can be IC511, IC516 or IC518 according to IEC 60034-6.

Terminal box or auxiliary boxes don’t communicate with the motor, the compartments are separated by bushing and/or cable glands covered
by Ex component. As a variation the connection can be made through a blanking cap with an unterminated cable. In this case the terminal
boxes can be supplied in separated.

Temperature sensors, with or without certification, may be incorporated in the stator windings and/or in the bearings. Heating resistances, with
or without certification, may be located inside of the motor mounted on each end of the frame or mounted on each end of the winding coil
heads. Heating resistances could be also mounted inside the terminal boxes protected by flameproof enclosures.

The motor could be fitted with intrinsic safety transmitters and sensors for thermal protection and for detection and control of vibrations. They
could be fitted on or inside the motor and the connections of these devices are made in the terminal boxes.

Motors supplied through a frequency inverter and motors with separate ventilation are always fitted with temperature sensors.

The motors get the degrees of protection IP55, IP56, IP65 or IP66 according to IEC 60034 - Part 5.

The terminal boxes type CG47, CEFGH340, CEFGH500, WTBX-XS, WTBX-S, WTBX-M, WTBX-L and WTBX-XL get the degrees of
protection IP66 in accordance with IEC 60529.

The motor and/or terminal boxes can be fitted with different Ex components. All components are stipulated on the descriptive documents.

As a variant, instead of cylindrical flameproof joint, labyrinth flameproof joints can be used between the inner bearing caps and the labyrinth
rings mounted on the shaft or manufactured on the shaft itself.

A drain and breathing device can be mounted on the motor or on the terminal boxes.

SPECIFIC CONDITIONS OF USE: YES as shown below:


• The screws used for the assembly of the various parts of explosion-proof enclosures must be of quality higher or equal to class 12.9 or
stainless steel A2-70 or A4-80.
• The dimensions of flameproof joints are different from the values specified in the tables of the IEC 60079-1 standard. For any repair,
contact the manufacturer.
• During the installation, for group I, the user will take into consideration that this equipment underwent only a shock corresponding to an
energy of a low risk.
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0010X Page 4 of 4

Date of issue: 2020-04-02 Issue No: 2

DETAILS OF CERTIFICATE CHANGES (for issues 1 and above)


regarding Issue 1:

• Introduction of components protected by intrinsic safety "ia" or "ib"


• Update the list of components intended to be mounted on or insiide the motor.
• Modification of the power for the internal heating resistance of the terminal boxes.
• Possibility to use the motor size 630 at ambient temperature down to -55°C
regarding Issue 2:

• Extension of ambient temperature to -55°C for size 500 up to 710 (I, IIB, IIIC).
• Change of designation W22Xdb
• Addition of Santo Tirso address as additional manufacturing location.
• Addition of shaft with sleeving.
• Addition of terminal boxes Ex eb certified as component covered by the certificate IECEx BAS 14.0175U and IECEx BAS 16.0129U.
• Standards update : IEC 60079-0:2017, IEC 60079-1:2014, IEC 60079-7:2017.

Annex:

IECEx INE 12.0010X-02_Annex.pdf


IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0010X
IECEx INE 12.0010X-02_Annex.pdf Issue No.: 02
Page 1 of 5
Annex: IECEx INE 12.0010X-02_Annex.pdf

PARAMETERS RELATING TO THE SAFETY

Maximum supply voltages (for 50Hz or 60Hz):


Low voltage : 220 V to 1140V.
Medium voltage : up to 6600V.
High voltage : up to 13800 V or 11000V when the motor is fitted with terminal box protected by increased safety.

Maximum frequencies:
Without frequency inverter : 50 Hz or 60 Hz.
With frequency inverter : Up to 150Hz.

Maximum powers of motors:


Standard version, service S1
Low voltage : 630 kW to 4500 kW.
Medium voltage : 630 kW to 4500 kW.
High voltage : 500 kW to 3550 kW.
For special versions the different parameters can be adapted.
Maximum powers of internal Heating resistances:
Terminal box CG47 : 6,5 W
Terminal box WTBX-XS : 6,5 W
Terminal box WTBX-S : 56 W
Terminal box WTBX-M : 112 W
Terminal box WTBX-L : 112 W
Terminal box CEFG 340 : 112 W
Terminal box CEFG 500 : 112 W
Terminal box WTBX-XL : 112 W
Maximum operating thresholds of the temperature sensors:
For the winding: 155°C ± 5°C.
For the bearing: 120°C ± 5°C.

MARKING

Marking has to be readable and indelible; it has to include the following indications:
• WEGeuro Indústria Eléctrica S.A
• 4470-605 MAIA or 4780-165 SANTO-TIRSO
• W22XdbB…T… (*) or W22XdbM...T… (*)
• IECEx INE 12.0010X
• (Serial number)
• Ex db IIB T4 or T3 Gb or Ex db eb IIB T4 or T3 Gb or Ex db ia IIB T4 or T3 Gb or Ex db eb ia IIB T4 or T3 Gb or Ex db ib IIB T4 or
T3 Gb or Ex db eb ib IIB T4 or T3 Gb Ex db I Mb or Ex db eb I Mb or Ex db ia I Mb or Ex db eb ia I Mb or Ex db ib I Mb or
Ex db eb ib I Mb
• Ex tb IIIC T125°C or T135°C Db or Ex ia tb IIIC T125°C or T135°C Db or Ex ib tb IIIC T125°C or T135°C Db
• IP65 or IP66
• T.amb: (**)
• T.Cable: (***)
• Cable entries: (type and size)
• WARNINGS:
o DO NOT OPEN WHEN ENERGIZED.
o DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT.

When the terminal box is protected by increased safety the following indications:
• (rated voltage and rated current and/or rated power)
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0010X
IECEx INE 12.0010X-02_Annex.pdf Issue No.: 02
Page 2 of 5
Annex: IECEx INE 12.0010X-02_Annex.pdf

When the terminal box is located outside of the motor and connected with a cable to the motor the following indications:
• IECEx INE 12.0010X
• Ex db IIB T4 or T3 Gb, Ex eb IIB T4 or T3 Gb,
• Ex db ia IIB T4 or T3 Gb, Ex db ib IIB T4 or T3 Gb, Ex eb ia IIB T4 or T3 Gb, Ex eb ib IIB T4 or T3 Gb

• Ex db I Mb, Ex db eb I Mb
• Ex db ia I Mb, Ex db eb ia I Mb, Ex db ib I Mb, Ex db eb ib I Mb

• Ex tb IIIC T125°C or T135°C Db, Ex ia tb IIIC T125°C or T135°C Db, Ex ib tb IIIC T125°C or T135°C Db
• IP65 or IP66
• Rated voltage and rated current and/or rated power are mandatory only for "Ex eb" version

• WARNINGS:
o DO NOT OPEN WHEN ENERGIZED.
o DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT.

(*) Type is completed by numbers and letters corresponding to the manufacturer variations.

(**) Mandatory mention when the range of the ambient temperatures differs from -20°C, -30°C, -40°C, -55°C to +40°C, +50°C, +60°C
(***) 85°C for ambient 50°C or 95°C for ambient 60°C when the cable glands are fitted on the terminal box.
95°C for ambient 40°C, 105°C for ambient 50°C or 115°C for ambient 60°C when the cable glands are fitted on the blanking cover of
motors supplied by flying leads.
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0010X
IECEx INE 12.0010X-02_Annex.pdf Issue No.: 02
Page 3 of 5
Annex: IECEx INE 12.0010X-02_Annex.pdf

ROUTINE EXAMINATIONS AND TESTS

In accordance with clause 16.1 of the IEC 60079-1 standard, each equipment defined above has to have successfully passed, before delivery, an
overpressure test of a period comprised between 10 and 60 seconds under:

Pressure

Ambient temperature down to


Enclosure type
-20°C -30°C -40°C -55°C
Motor W22X…500 26.9 bar 36.9 bar 39 bar 42.5 bar
Motor W22X…560 26.9 bar 36.9 bar 39 bar 42.5 bar
Motor W22X…630 31.5 bar 43.2 bar 45.7 bar 49.8 bar
Motor W22X…710 31.5 bar 43.2 bar 45.7 bar 49.8 bar
Terminal box WTBX-L ------------- 15.3 bar 15.3 bar 15.3 bar
Terminal box WTBX-XL 11.4 bar 15.7 bar 16.6 bar 18 bar
Terminal box CEFGH 340 11.3 bar 15.4 bar 16.3 bar 17.9 bar
Terminal box CEFGH 500 12.2 bar 16.6 bar 17.6 bar 19.2 bar
Adaptor Ex d 14.7 bar 19.2 bar 19.2 bar 19.2 bar

In accordance with § 16.2 of the IEC 60079-1 standard, the following terminal boxes defined above are exempted of routine test due to the fact
that they have undergone a static type test at 4 times the reference pressure under:

Pressure

Ambient temperature down to


Enclosure type
-20°C -30°C -40°C -55°C
Terminal box type WTBX-L 32 bar ----------- ----------- -----------
Terminal box type WTBX-M ----------- ----------- ----------- 37.2 bar
Terminal box type WTBX-S ----------- ----------- ----------- 30.4 bar
Terminal box type WTBX-XS ----------- ----------- ----------- 24.8 bar
Terminal box type CG47 ----------- ----------- ----------- 69.6 bar

In accordance with clause 7.1 of the IEC 60079-7 standard, the intercalary and the terminal boxes type CG47, CEFGH340, CEFGH500, WTBX-
XS, WTBX-S, WTBX-M and WTBX-L protected by increased safety must have successfully passed before delivery a dielectric strength test on
each of the different circuits of the connection units, performed according to the relevant standards, the supply voltage shall be applied during one
minute.
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0010X
IECEx INE 12.0010X-02_Annex.pdf Issue No.: 02
Page 4 of 5
Annex: IECEx INE 12.0010X-02_Annex.pdf

LIST OF THE COMPONENT INTENDED TO BE INSTALLED ON THE MOTOR AND/OR TERMINAL BOXES

Type of Name of IEC IEC IEC IEC IEC


Certificate number
component manufacturer 60079-0 60079-1 60079-7 60079-11 60079-31
Emil A. Peters IECEx PTB
Bushing 2011 ed 6 2007 ed 6 2006 ed.4
GmbH 08.0032U
Emil A. Peters IECEx PTB
Bushing 2011 ed 6 2007 ed 6 2006 ed.4
GmbH 08.0052U
Emil A. Peters IECEx PTB
Bushing 2011 ed 6 2007 ed 6 2006 ed.4
GmbH 08.0054U
Emil A. Peters IECEx PTB
Bushing 2011 ed 6 2007 ed 6 2006 ed.4
GmbH 09.0004U
Emil A. Peters IECEx PTB
Bushing 2004 ed 4 2003 ed 5 2006 ed.4
GmbH 08.0053U
Insulator IECEx CES
CELMEX S.r.l. 2011 ed 6 2014 ed 7 2015 ed.5
bushings 15.0015U
IECEx PTB
Bushing STAHL 2007 ed 5 2007 ed 6 2006 ed.4
06.0080U
IECEx EPS
Line bushing BARTEC GmbH 2017 ed 7 2014 ed 7
13.0045U
IECEx EPS
Line bushing BARTEC GmbH 2017 ed 7 2014 ed 7 2015 ed 5
14.0020U
IECEx PTB
Line entry BARTEC GmbH 2011 ed 6 2007 ed 6 2013 ed.2
13.0050U
IECEx CML
Line bushing BARTEC GmbH 2017 ed 7 2014 ed 7 2015 ed.5
14.0003U
Conductor IECEx CES
CORTEM S.p.A 2011 ed 6 2014 ed 7 2013 ed.2
sealing bushings 10.0003U
Conductor IECEx PTB
STAHL 2011 ed 6 2014 ed 7
bushing 06.0081U
Blanking plug Emil A. Peters IECEx PTB
2011 ed 6 2007 ed 6
GmbH 09.0003U
IECEx BAS
Stopping plugs Hawke 2011 ed 6 2015 ed.5 2013 ed.2
06.0029U
Threaded Emil A. Peters IECEx PTB
2011 ed 6 2007 ed 6
adapter GmbH 09.0006U
IECEx ITS
Adaptors EATON 2011 ed 6 2014 ed 7 2015 ed.5 2013 ed.2
16.0015U
Connecting IECEx PTB
BARTEC GmbH 2011 ed 6 2015 ed.5
terminal 07.0007U
Terminal blocks
PHOENIX IECEx KEM 2017
and protective 2017 ed 7
CONTACT 07.0008U ed.5.1
conductor
Terminals PHOENIX IECEx KEM 2017
2017 ed 7
blocks CONTACT 06.0034U ed.5.1
Protective
PHOENIX IECEx KEM 2017
conductor 2017 ed 7
CONTACT 06.0035U ed.5.1
terminal blocks
IECEx ULD 2017
Terminal block WEIDMULLER 2017 ed 7
14.0005U ed.5.1
IECEx FTZU
Range of rail WEG DRIVES 2011 ed 6 2015 ed.5
12.0005U
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0010X
IECEx INE 12.0010X-02_Annex.pdf Issue No.: 02
Page 5 of 5
Annex: IECEx INE 12.0010X-02_Annex.pdf

Type of Name of IEC IEC IEC IEC IEC


Certificate number
component manufacturer 60079-0 60079-1 60079-7 60079-11 60079-31
IECEx FTZU
Range of rail WEG DRIVES 2011 ed 6 2015 ed.5
12.0006U
IECEx FTZU
Range of rail WEG DRIVES 2017 ed 7 2015 ed.5
12.0007U
Range of IECEx SIR
WEIDMULLER 2004 ed 4 2001 ed.3
terminal strips 05.0036U

Terminals PHOENIX IECEx KEM 2004 ed 4 2006 ed.4


blocks CONTACT 07.0017U
Breathing and IECEx CES
CORTEM/ELFIT 2011 ed 6 2007 ed 6 2006 ed.4 2008 ed.1
Draining valves 14.0016U

IECEx EXA 2011 ed 6 2007 ed 6 2006 ed.4 2008 ed.1


Drain Valve FENEX
13.0001U
IECEx BVS
Control unit STAHL 2011 ed 6 2014 ed 7 2006 ed.4 2011 ed.6
07.0029U
Ring-core F.T.M. s.r.l. Fabbrica
IECEx CES
current Trasformatori di 2011 ed 6 2015 ed.5
13.0015U
transformer Misura
Phase
IECEx SIR 2017
segregated Quartzelec Limited 2017 ed 7 2013 ed.2
10.0147U ed.5.1
terminal box
Range of
WEG Equipamentos IECEx BAS
Auxiliary 2011 ed 6 2015 ed.5 2013 ed.2
Eletricos S.A 16.0129U
terminal Boxes
Main Terminal WEG Equipamentos IECEx BAS
2017 ed 7 2015 ed.5 2013 ed.2
Boxes Eletricos S.A 14.0175U
RSV motor Anti- IECEx SIR
FLEXELEC S A 2011 ed 6 2006 ed.4
condensation 10.0151U
Anti-
ELTRON IECEx ITS
condensation 2011 ed 6 2015 ed.5
CHROMALOX 08.0002U
heater
Self limiting IECEx KEM
BARTEC GmbH 2011 ed 6 2008 ed.1
heating cable 07.0048U
Self-Limiting IECEx KEM
BARTEC GmbH 2011 ed 6 2008 ed.1
Heating Cable 07.0047U
Temperature IECEx IBE
EPHY-MESS Gmbh 2011 ed 6 2015 ed.5 2011 ed.6 2013 ed.2
sensor 14.0058U
Temperature Temperature IECEx TSA
2004 ed 4 2003 ed 5 2001 ed.3
sensor Controls Pty Ltd 09.0044U
Slot resistance –
thermometer PAUL RÜSTER Co IECEx IBE
2011 ed 6 2015 ed.5
and GmbH 14.0011U
thermocouples
Resistance
IECEx DEK
Temperature Minco Products Inc. 2011 ed 6 2007 ed 6 2006 ed.4
15.0018U
Detector

in green: not concerned by major changes of the last standard version