You are on page 1of 8

IECEx Certificate

of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

Certificate No.: IECEx INE 14.0065X Page 1 of 4 Certificate history:

Status: Current Issue No: 0

Date of Issue: 2015-08-03

Applicant: WEGeuro Indùstria Eléctrica S.A


Rua Eng Frederico Ulrich
P - 4470-605 MAIA
Portugal

Equipment: MOTORS TYPE W22XdB...T.800.. or W22XdM...T.800..

Optional accessory:

Type of Protection: d, d e, d ia, d ib, d e ia, d e ib, tb, ia tb and ib tb

Marking: Ex d IIB T4 Gb, Ex d e IIB T4 Gb, Ex d ia IIB T4 Gb, Ex d IIB ib T4 Gb,

Ex d e ia IIB T4 Gb, Ex d e ib IIB T4 Gb.

Ex d IIB T3 Gb, Ex d e IIB T3 Gb, Ex d ia IIB T3 Gb, Ex d IIB ib T3 Gb,

Ex d e ia IIB T3 Gb, Ex d e ib IIB T3 Gb.

Ex d I Mb, Ex d e I Mb, Ex d ia I Mb, Ex d ib I Mb, Ex d e ia I Mb, Ex d e ib I Mb.

Ex tb III C T125°C or T135°C Db, Ex ia tb III C T125°C or T135°C Db,

Ex ib tb III C T125°C or T135°C Db.

Approved for issue on behalf of the IECEx Olivier COTTIN


Certification Body:

Position: Head of Equipment and Corporate Services Unit

Signature:
(for printed version)

Date:

1. This certificate and schedule may only be reproduced in full.


2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting www.iecex.com or use of this QR Code.

Certificate issued by:


INERIS
Institut National de l'Environnement Industriel
et des Risques
BP n2
Parc Technologique ALATA
F-60550 Verneuil-En-Halatte
France
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 14.0065X Page 2 of 4

Date of issue: 2015-08-03 Issue No: 0

Manufacturer: WEGeuro Indùstria Eléctrica S.A


Rua Eng Frederico Ulrich
P - 4476-908 MAIA
Portugal

Additional
manufacturing
locations:

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended

STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards

IEC 60079-0:2011 Explosive atmospheres - Part 0: General requirements


Edition:6.0

IEC 60079-1:2007-04 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:6

IEC 60079-11:2011 Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
Edition:6.0

IEC 60079-31:2013 Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t"
Edition:2

IEC 60079-7:2006-07 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
Edition:4

This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.

TEST & ASSESSMENT REPORTS:


A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in:

Test Report:
FR/INE/ExTR14.0065/00

Quality Assessment Report:


GB/BAS/QAR07.0032/04
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 14.0065X Page 3 of 4

Date of issue: 2015-08-03 Issue No: 0

EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:

This three-phase asynchronous motor, size 800, with frame in welded steel and endshieds in welded steel or cast iron.

Motor can be fitted with different terminal boxes and auxiliary boxes protected by flameproof enclosure or by increased safety.

This equipment is also protected by type protection "tb" for using in dust explosive atmospheres.

The motor may be designed with one up to four speed.

Mounting position of motor can be either horizontal or vertical.

Cooling types can be IC511, IC516 or IC518 according to IEC 60034-6.

The terminal boxes can be fitted directly on the motors or by an adaptor. They are made in cast iron, steel or stainless steel.

Terminal or auxiliary boxes don’t communicate with the motor. The compartments are separated by bushing covered by Ex component and by
cable gland covered by separate certificate. As a variation the connection can be made through a blanking cap with an unterminated cable. In
this case the terminal boxes can be supplied in separated.

Temperature sensors may be incorporated in the stator windings and/or in the bearings.

The motor could be fitted with intrinsic safety transmitters and sensors for thermal protection and sensors for detections and control of
vibrations. They could be fitted on or inside the motor and the connexions of these devices are made in the terminal boxes.

Heating resistances may be located inside of the motor mounted on each top of the frame. Heating resistances could be also mounted inside
the terminal boxes protected by flameproof enclosures.

Terminal boxes can be mounted on the top or left/right side, located in any position of a 180° range around the upper part of the frame.

Motors supplied through a frequency inverter and motors with separated ventilation are always fitted with temperature sensors.

The motors present the degrees of protection IP55, IP56, IP65 or IP66 according to IEC 60034 - Part 5.

The terminal boxes type CG47, CEFGH340, CEFGH500, WTBX-XS, WTBX-S, WTBX-M, WTBX-L and WTBX-XL present the degrees of
protection IP66 in accordance with IEC 60529.

The motor and/or terminal boxes can be fitted with different Ex components. All components are stipulated on the annex.

As a variant, instead of cylindrical flameproof joint, labyrinth flameproof joints could be used between the inner bearing caps and the labyrinth
rings mounted on the shaft or manufactured on the shaft itself.

A drain and breathing device can be mounted on the motor or on the terminal boxes.

SPECIFIC CONDITIONS OF USE: YES as shown below:


- The width of the different flameproof joints is superior to the value specified in the tables of IEC 60079-1 standard.

- The gap of the different flameproof joints is inferior to the value specified in the tables of IEC 60079-1 standard.
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 14.0065X Page 4 of 4

Date of issue: 2015-08-03 Issue No: 0

- The yield stress of the fastener elements of the flameproof casing must be equal to class 12.9 or stainless steel A2-70 or A4-80 as specified in the instructions.

Additional condition for Group I:

- During the installation the user will take into consideration that this equipment underwent only a shock corresponding to an energy of a low risk.

The other conditions are stipulated in the instructions.

Annex:

IECEx INE 14.0065X_Annex.pdf


IECEx Certificate
of Conformity
Certificate No.: IECEx INE 14.0065X
Issue No.: 0
Page 1 of 4
Annexe: IECEx INE 14.0065X_Annex.pdf

PARAMETERS RELATING TO THE SAFETY


Maximum supply voltages (for 50Hz or 60Hz):
Low voltage : 220 V to 1100V.
Medium voltage : 6600V.
High voltage : 13800 V or 11000V when the motor is fitted with terminal box
protected by increased safety.

Maximum frequencies:
Without frequency inverter : 50 Hz or 60 Hz.
With frequency inverter : Up to 150Hz.

Maximum powers:
Standard version, service S1:
Low voltage : 2800 kW to 5600 kW.
Medium voltage : 2800 kW to 5600 kW.
High voltage : 2000 kW to 4000 kW.
For special versions the different parameters can be adapted.
Maximum operating thresholds of the temperature sensors:
For the winding : 155°C ± 5°C.
For the bearing : 120°C ± 5°C.
These motors can be used in range of ambient temperatures from -20°C to 40°C, 50°C or 60°C.

MARKING

Marking has to be readable and indelible; it has to include the following indications:

• WEGeuro Indústria Eléctrica S.A


Rua Eng Frederico Ulrich
• P-4471-908 MAIA (Portugal)
• W22XdB…T.800.. or W22XdM…T.800..(*)
• IECEx INE 14.0065X
• (Serial number)

• Ex d IIB T4 Gb or Ex d e IIB T4 Gb or Ex d ia IIB T4 Gb or Ex d IIB ib T4 Gb or Ex d e ia IIB T4 Gb or


Ex d e ib IIB T4 Gb
or

• Ex d IIB T3 Gb or Ex d e IIB T3 Gb or Ex d ia IIB T3 Gb or Ex d IIB ib T3 Gb or Ex d e ia IIB T3 Gb or


Ex d e ib IIB T3 Gb
or

• Ex d I Mb or Ex d e I Mb or Ex d ia I Mb or Ex d ib I Mb or Ex d e ia I Mb or Ex d e ib I Mb
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 14.0065X
Issue No.: 0
Page 2 of 4
Annexe: IECEx INE 14.0065X_Annex.pdf
and/ or

• Ex tb IIIC T125°C or T135°C Db IP65 or IP66 or Ex ia tb IIIC T125°C or T135°C Db IP65 or IP66 or
Ex ib tb IIIC T125°C or T135°C Db IP65 or IP66

• T.amb: (**)
• T.Cable: (***)
• Cable entries: (type and size)
WARNINGS:
• DO NOT OPEN WHEN ENERGIZED.
• DO NOT OPEN IF AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.

When the terminal box is protected by increased safety the following indications:
• (rated voltage and rated current and/or rated power)

When the terminal box is located outside of the motor and connected with a cable to the motor the
following indications:
WARNINGS:
• DO NOT OPEN WHEN ENERGIZED.
• DO NOT OPEN IF AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
• IECEx INE 14.0065X

• Ex d IIB T4 Gb or Ex e IIB T4 Gb or Ex d ia IIB T4 Gb or Ex d ib IIB T4 Gb or Ex e ia IIB T4 Gb or


Ex e ib IIB T4 Gb
or

• Ex d IIB T3 Gb or Ex e IIB T3 Gb or Ex d ia IIB T3 Gb or Ex d ib IIB T3 Gb or Ex e ia IIB T3 Gb or


Ex e ib IIB T3 Gb
or
• Ex d I Mb or Ex e I Mb or Ex d ia I Mb or Ex d ib I Mb or Ex e ia I Mb or Ex e ib I Mb
and/or

• Ex tb IIIC T125°C or T135°C Db IP65 or IP66 or Ex ia tb IIIC T125°C or T135°C Db IP65 or IP66 or
Ex ib tb IIIC T125°C or T135°C Db IP65 or IP66

Rated voltage and rated current and/or rated power are mandatory only for "Ex e" version.

(*) Type is completed by numbers and letters corresponding to the manufacturer variations.
(**) Mandatory mention when the range of the ambient temperatures differs from –20°C to 40°C:
-20°C/+50ºC or -20ºC/+60ºC.
(***) 85°C for ambient 50°C or 95°C for ambient 60°C when the cable glands are fitted on the
terminal box.
95°C for ambient 40°C, 105°C for ambient 50°C or 115°C for ambient 60°C when the cable
glands are fitted on the blanking cover of motors supplied by flying leads.
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 14.0065X
Issue No.: 0
Page 3 of 4
Annexe: IECEx INE 14.0065X_Annex.pdf

ROUTINE EXAMINATIONS AND TESTS

In accordance with clause 16.1 of the IEC 60079-1 standard, each equipment defined above has to have
successfully passed, before delivery, an overpressure test of a period comprised between 10 and 60
seconds under:
- 31.5 bar for the motor.
- 11.4 bar for the terminal box type WTBX-XL.
- 11.3 bar for the terminal box CEFGH 340.
- 12.2 bar for terminal box CEFGH 500.
- 14.7 bar for the adaptor Ex d.
In accordance with § 16.2 of the IEC 60079-1 standard, the following terminal boxes defined above are
exempted of routine test due to the fact that they have undergone a static type test at 4 times the
reference pressure under:

- 32 bar for the terminal box type WTBX-L.


- 29.2 bar for the terminal box type WTBX-M.
- 24.8 bar for the terminal box type WTBX-S.
- 18.4 bar for the terminal box type WTBX-XS.
- 44 bar for the terminal box type CG47.

In accordance with clause 7.1 of the IEC 60079-7 standard, the intercalary and the terminal boxes type
CG47, CEFGH340, CEFGH500, WTBX-XS, WTBX-S, WTBX-M, WTBX-L and WTBX-L protected by increased
safety must have successfully passed before delivery a dielectric strength test on each of the different
circuits of the connection units, performed according to the relevant standards, the supply voltage shall
be applied during one minute.
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 14.0065X
Issue No.: 0
Page 4 of 4
Annexe: IECEx INE 14.0065X_Annex.pdf

LIST OF THE COMPONENT INTENDED TO BE INSTALLED ON THE MOTOR AND/OR TERMINAL BOXES

Type of component Name of the manufacturer Certificate number


Main Bushing/Terminals Emil A. Peters GmbH IECEx PTB 08.0032U
Connecting terminal BARTEC GmbH IECEx PTB 07.0007U
Terminals blocks PHOENIX CONTACT IECEx KEM 06.0034U
Ground Terminals blocks PHOENIX CONTACT IECEx KEM 06.0035U
Mini Terminals blocks PHOENIX CONTACT IECEx KEM 07.0008U
Range of rail WEG DRIVES IECEx FTZU 12.0005U
Range of rail WEG DRIVES IECEx FTZU 12.0006U
Range of rail WEG DRIVES IECEx FTZU 12.0007U
Bushing Emil A. Peters GmbH IECEx PTB 08.0054U
Bushing Emil A. Peters GmbH IECEx PTB 08.0052U
Bushing Emil A. Peters GmbH IECEx PTB 08.0053U
Terminal box Quartzelec Limited IECEx SIR 10.0147U
Drain Valve CORTEM/ELFIT IECEx CES 14.0016U
Conductor bushing STAHL IECEx PTB 06.0081U
Terminal block WEIDMULLER IECEx ULD 05.0008U
Reducers adaptors REDAPT IECEx SIR 05.0042U
Reducers adaptors RAXTON IECEx SIR 09.0086U
Swivel Adapters Ex Innovations (Raxton) IECEx SIR 10.0025U
Stopping Plugs HAWKE IECEx BAS 06.0056U
Mains bushing STAHL IECEx PTB 06.0080U
Control unit STAHL IECEx BVS 07.0029U
Line bushing BARTEC GmbH IECEx EPS 13.0045U
Range of terminal WEIDMULLER IECEx SIR 05.0036U
Line bushing BARTEC GmbH IECEx EPS 14.0020U
ACDP Brainther drains PEPPERLS CABLE GLAND Ltd IECEx SIR 09.0132U
Self limiting heating cable BARTEC IECEx KEM 07.0047U
Self limiting heating cable BARTEC IECEx KEM 07.0048U
Temperature sensor EPHY-MESS Gmbh IECEx IBE 14.0058U
Bushing Emil A. Peters GmbH IECEx PTB 09.0002U
Stopping plug Hawke IECEx BAS 06.0029U

You might also like