You are on page 1of 10

IECEx Certificate

of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

Certificate No.: IECEx INE 12.0037X Page 1 of 4 Certificate history:


Issue 0 (2012-10-31)
Status: Current Issue No: 1

Date of Issue: 2018-09-07

Applicant: WEGeuro Indústria Eléctrica S.A


Rua Eng. Frederico Ulrich, Sector V, P- 4470-605 Maia
Portugal

Equipment: Three-Phase Asynchronous Ribbed Cooled Motors and Generators type W22XdB...315..., 355..., 400..., 450...,
500... and 560... or W22XdM...315..., 355..., 400..., 450..., 500... and 560...

Optional accessory:

Type of Protection: db, db ia, db ib, db eb, db eb ia, db eb ib, tb, ia tb or ib tb

Marking: Ex db IIB T4 (or T3) Gb or Ex db eb IIB T4 (or T3) Gb or Ex db ia IIB T4 (or T3) Gb or Ex db ib IIB T4 (or T3) Gb or Ex
db eb ia IIB T4 (or T3) Gb or Ex db eb ib IIB T4 (or T3) Gb.

Ex db I Mb or Ex db eb I Mb or Ex db ia I Mb or Ex db ib I Mb or Ex db eb ia I Mb or Ex db eb ib I Mb.

Ex tb IIIC T125°C or T135°C Db IP65 or IP66 or Ex ia tb IIIC T125°C or T135°C Db IP65 or IP66 or Ex ib tb IIIC T125°C
or T135°C Db IP65 or IP66.

Approved for issue on behalf of the IECEx Thierry HOUEIX


Certification Body:

Position: Ex Certification Officer

Signature:
(for printed version)

Date:

1. This certificate and schedule may only be reproduced in full.


2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting www.iecex.com or use of this QR Code.

Certificate issued by:


INERIS
Institut National de l'Environnement Industriel
et des Risques, BP n2
Parc Technologique ALATA
France
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0037X Page 2 of 4

Date of issue: 2018-09-07 Issue No: 1

Manufacturer: WEGeuro Indústria Eléctrica S.A


Rua Eng. Frederico Ulrich, Sector V, P- 4470-605 Maia
Portugal

Additional
manufacturing
locations:

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended

STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards

IEC 60079-0:2011 Explosive atmospheres - Part 0: General requirements


Edition:6.0

IEC 60079-1:2014-06 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:7.0

IEC 60079-11:2011 Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
Edition:6.0

IEC 60079-31:2013 Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t"
Edition:2

IEC 60079-7:2015 Explosive atmospheres – Part 7: Equipment protection by increased safety ''e''
Edition:5.0

This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.

TEST & ASSESSMENT REPORTS:


A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in:

Test Reports:
FR/INE/ExTR11.0033/00 FR/INE/ExTR12.0034/00 FR/INE/ExTR12.0034/01
FR/INE/ExTR12.0034/02

Quality Assessment Report:


GB/BAS/QAR07.0032/07
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0037X Page 3 of 4

Date of issue: 2018-09-07 Issue No: 1

EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:

Three-phase asynchronous motor with frame made in cast iron, steel or stainless steel for size 315 up to 500 and in steel or stainless steel for
size 560. The end shields are made in cast iron, steel or stainless steel for size 315 up to 500 and in steel or stainless for size 560. Motor can
be fitted with different terminal boxes and auxiliary boxes protected by flameproof enclosure or by increased safety. This equipment is also
protected by type protection "tb" for using in dust explosive atmospheres. The motor may be designed with one up to four speeds. Mounting
position of motor can be either horizontal or vertical. Cooling types can be IC 411, 416 or 418 according to IEC 60034-6. The terminal boxes
can be fitted directly on the motor or by an adaptor. They are made in cast iron, steel or stainless steel. Terminal or auxiliary boxes do not
communicate with the motor, the compartments are separated by bushing covered by Ex component and/or by certified cable glands. As a
variation the connection can be made through a blanking cap with an unterminated cable. In this case the terminal boxes can be supplied in
separated.

Temperature sensors, with or without certification, could be incorporated in the bearings and eventually in the stator windings. The motor
could be fitted with intrinsic safety transmitters and sensors for thermal protection and sensors for signal and control of vibrations. They could
be fitted on or inside the motor and the connections of these devices are made in the terminal boxes. Heating resistances, with or without
certification, may be located inside of the motor mounted on each end of the frame or mounted on each end of the winding coil heads. Heating
resistances could also be mounted inside the terminal boxes protected by flameproof enclosures. Terminal boxes can be mounted on the top
or left/right side, located in any position of a 180° range around the upper part of the frame. Motor supplied through a frequency inverter and
motor with separate ventilation are always fitted with temperature sensors. The motors get the degrees of protection IP55, IP56, IP65 or IP66
according to IEC 60034 - Part 5. The terminal boxes type CG47, CEFGH340, CEFGH500, WTBX-XS, WTBX-S, WTBX-M, WTBX-L and
WTBX-XL get the degrees of protection IP66 in accordance with IEC 60529. The motor and/or terminal boxes can be fitted with different Ex
components. All components are stipulated in annex and in the descriptive documents. The motor can be fitted with labyrinth flameproof joints
between the inner bearing caps and the labyrinth rings mounted on the shaft or manufactured on the shaft itself. A drain and breathing device
can be mounted on the motor or on the terminal boxes.

SPECIFIC CONDITIONS OF USE: YES as shown below:


Where necessary, and depending on the installation and operating conditions of the machine, provisions such as continuous temperature
monitoring of the bearings shall be taken to protect against any effects due to the presence of circulation currents.

If motors are fitted with thermal protections, these may be connected as an additional protection and source of information for maintenance. In
case of Pt100 or thermocouples, tripping temperature must be regulated to the values indicated by WEG.

If the thermal probes are not connected, the user must ensure that the installation and preventive maintenance are properly performed to
avoid a bearing failure that may result in the occurrence of an ignition source.

Motors fed by variable Speed Drive must be fitted with thermal sensors on windings and, eventually, on the bearings. The connections of
these thermal protections are mandatory.

The following specific conditions of use below concern only the type of protection Ex db:
The yield stress of the fastener elements of the flameproof casing must be equal to class 12.9 or stainless steel A2-70 or A4-80.

The flameproof joints have a different values from those specified in the tables of the IEC 60079-1 standard, for any repair to contact the
manufacturer.

The other specific conditions are stipulated in the instructions.


IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0037X Page 4 of 4

Date of issue: 2018-09-07 Issue No: 1

DETAILS OF CERTIFICATE CHANGES (for issues 1 and above)


ISSUE N°1

- Use new designation for the motor.

- Adding the terminal box type WTBX-L.

- Adding terminal box Euromold manufactured by Quartzelec.

- Application of the IEC 60079-1: 2014, IEC 60079-7: 2015 and IEC 60079-31: 2013.

- Dispense of the routine test for terminal box type CG-47 version Ex db.

- Adding new adaptor with type protection “Ex eb” and “Ex tb”

- Adding a new size motor 560.

- Introduction of protection types "ia" and "ib" according to IEC 60079-11: 2011.

- Introduction of new frame type 315S/M.

- Possibility to install the terminal boxes, without bushing, outside of the motor when the motor is fitted with a permanently cable.

- Addition of terminal box WTBX-XL for gas group IIB.

Annex:

IECEx INE 12.0037X-01_Annex.pdf


IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0037X
IECEx INE 12.0037X-01_Annex.pdf Issue No.: 1
Page 1 of 6
Annex: IECEx INE 12.0037X-01_Annex.pdf

PARAMETERS RELATING TO THE SAFETY

Maximum supply voltages (for 50Hz or 60Hz):


Low voltage : 220 V to 1140V.
Medium voltage : 6600V.
High voltage : 13800 V or 11000V when the motor is fitted with terminal box protected by increased safety.

Maximum frequencies:
Without frequency inverter : 50 Hz or 60 Hz.
With frequency inverter :
- From 1 up to 300 Hz for motor size 315.
- From 1 up to 253 Hz for motor sizes 355, 400 and 450.
- From 1 up to 173 Hz for motor sizes 500 and 560.

Maximum powers of motors:


Standard version, service S1:
Type of motor Output Powers
Low Voltage Medium Voltage Hight Voltage
W22XdB/M …315… 75 kW to 250 kW 90 kW to 150 kW -------------------
W22XdB/M …355… 160 kW to 500 kW 90 kW to 355 kW -------------------
W22XdB/M …400… 355 kW to 800 kW 200 kW to 710 kW 110 kW to 315 kW
W22XdB/M …450… 560 kW to 1000 kW 450 kW to 1000 kW 200 kW to 560 kW
W22XdB/M …500… 710 kW to 1400 kW 560 kW to 1500 kW 400 kW to 900 kW
W22XdB/M …560… 800 kW to 1600 kW 800 kW to 1600 kW 500 kW to 1120 kW

For special versions, the different parameters can be adapted.

Maximum powers of internal Heating resistances:


Terminal box CG47 : 6.5 W
Terminal box WTBX-XS : 6.5 W
Terminal box WTBX-S : 56 W
Terminal box WTBX-M : 112 W
Terminal box WTBX-L : 112 W
Terminal box WTBX-XL : 112 W
Terminal box CEFGH 340 : 112 W
Terminal box CEFGH 500 : 112 W

Maximum operating thresholds of the temperature sensors:


For the winding: 155°C ± 5°C.
For the bearing: 120°C ± 5°C.

These motors can be used in the following range of ambient temperatures:

From -20°C to 40°C, 50°C or 60°C, -30°C to 40°C, 50°C or 60°C, -40°C to 40°C, 50°C or 60°C, -55°C to 40°C, 50°C or 60°C.
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0037X
IECEx INE 12.0037X-01_Annex.pdf Issue No.: 1
Page 2 of 6
Annex: IECEx INE 12.0037X-01_Annex.pdf

MARKING

Marking must be readable and indelible; it must include the following indications:

1. Type W22XdB...:
• WEGeuro Indústria Eléctrica S.A
• Rua Eng. Frederico Ulrich, Sector V
• P 4470-605 MAIA
• W22XdB...(*)
• IECEx INE 12.0037X
• (Serial number)
• Ex db IIB T4 Gb or Ex db eb IIB T4 Gb or Ex db ia IIB T4 Gb or Ex db ib IIB T4 Gb or Ex db eb ia IIB T4 Gb or Ex db eb ib IIB T4 Gb or
• Ex db IIB T3 Gb or Ex db eb IIB T3 Gb or Ex db ia IIB T3 Gb or Ex db ib IIB T3 Gb or Ex db eb ia IIB T3 Gb or Ex db eb ib IIB T3 Gb
and/or
• Ex tb IIIC T125°C or T135°C Db IP65 or IP66 or Ex ia tb IIIC T125°C or T135°C Db IP65 or IP66 or Ex ib tb IIIC T125°C or T135°C Db
IP65 or IP66
• T.amb: (**)
• T.Cable: (***)
• Cable entries: (type and size)
• WARNINGS:
o DO NOT OPEN WHEN ENERGIZED.
o DO NOT OPEN IF AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.

When the terminal box is protected by increased safety the following indications:
• (rated voltage and rated current and/or rated power)

When the terminal box is located outside of the motor and connected with a cable to the motor the following indications:
• IECEx INE 12.0037X
• Ex db IIB T4 Gb or Ex eb IIB T4 Gb or Ex db ia IIB T4 Gb or Ex db ib IIB T4 Gb or Ex eb ia IIB T4 Gb
or Ex eb ib IIB T4 Gb or
• Ex db IIB T3 Gb or Ex eb IIB T3 Gb or Ex db ia IIB T3 Gb or Ex db ib IIB T3 Gb or Ex eb ia IIB T3 Gb
or Ex eb ib IIB T3 Gb and/or
• Ex tb IIIC T125°C or T135°C Db IP65 or IP66 or Ex ia tb IIIC T125°C or T135°C Db IP65 or IP66 or
• Ex ib tb IIIC T125°C or T135°C Db IP65 or IP66
• Rated voltage and rated current and/or rated power are mandatory only for "Ex eb" version
• WARNINGS:
o DO NOT OPEN WHEN ENERGIZED.
o DO NOT OPEN IF AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.

(*) Type is completed by numbers and letters corresponding to the manufacturer variations.
(**) Mandatory mention when the range of the ambient temperatures differs from –20°C to 40°C: see range of ambient temperature
specified in the parameters relating to the safety.
(***) 90°C for ambient 50°C or 100°C for ambient 60°C when the cable glands are fitted on the terminal box.
100°C for ambient 40°C, 110°C for ambient 50°C or 120°C for ambient 60°C when the cable glands are fitted on the blanking cover of
motors supplied by flying leads.
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0037X
IECEx INE 12.0037X-01_Annex.pdf Issue No.: 1
Page 3 of 6
Annex: IECEx INE 12.0037X-01_Annex.pdf

2. Type W22XdM...:
• WEGeuro Indústria Eléctrica S.A
• Rua Eng. Frederico Ulrich, Sector V
• P 4470-605 MAIA
• W22XdM...(*)
• IECEx INE 12.0037X
• (Serial number)
• Ex db I Mb or Ex db eb I Mb or Ex db ia I Mb or Ex db ib I Mb or Ex db eb ia I Mb or Ex db eb ib I Mb
• T.amb: (**)
• T.Cable: (***)
• Cable entries: (type and size)
• WARNINGS:
o DO NOT OPEN WHEN ENERGIZED.
o DO NOT OPEN IF AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.

When the terminal box is protected by increased safety the following indications:
• (rated voltage and rated current and/or rated power)

When the terminal box is located outside of the motor and connected with a cable to the motor the following indications:
• IECEx INE 12.0037X
• Ex db I Mb or Ex eb I Mb or Ex db ia I Mb or Ex db ib I Mb or Ex eb ia I Mb
or Ex eb ib I Mb
• Rated voltage and rated current and/or rated power are mandatory only for "Ex eb" version
• WARNINGS:
o DO NOT OPEN WHEN ENERGIZED.
o DO NOT OPEN IF AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.

(*) Type is completed by numbers and letters corresponding to the manufacturer variations.
(**) Mandatory mention when the range of the ambient temperatures differs from –20°C to 40°C: see range of ambient temperature
specified in the parameters relating to the safety.
(***) 90°C for ambient 50°C or 100°C for ambient 60°C when the cable glands are fitted on the terminal box.
100°C for ambient 40°C, 110°C for ambient 50°C or 120°C for ambient 60°C when the cable glands are fitted on the blanking cover of
motors supplied by flying leads.
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0037X
IECEx INE 12.0037X-01_Annex.pdf Issue No.: 1
Page 4 of 6
Annex: IECEx INE 12.0037X-01_Annex.pdf

ROUTINE EXAMINATIONS AND TESTS

In accordance with clause 16.1 of the IEC 60079-1 standard, each equipment defined above must have successfully passed, before delivery, an
overpressure test of a period comprised between 10 and 60 seconds under:

Overpressure values and ambient temperature


Type of enclosure
Down to -20°C Down to -30°C Down to -40°C Down to -55°C
Motor enclosure in cast iron ------------- ------------- ------------- 14.4
Motor enclosure in welded steel 9.2 bar 12.5 bar 13.2 bar 14.4 bar
Terminal box type WTBX-XL 11.4 bar 15.7 bar 16.6 bar 18 bar
Terminal box type WTBX-L ------------- 15.3 bar 15.3 bar 15.3 bar
Terminal box CEFGH 340 11.3 bar 15.4 bar 16.3 bar 17.9 bar
Terminal box CEFGH 500 12.2 bar 16.6 bar 17.6 bar 19.2 bar
Adaptor Ex d 14.7 bar 19.2 bar 19.2 bar 19.2 bar

In accordance with § 16.2 of the IEC 60079-1 standard, the following equipment are exempted of routine test since they have undergone a static
type test at 4 times the reference pressure under:

Overpressure values and ambient temperature


Type of enclosure
Down to -20°C Down to -30°C Down to -40°C Down to -55°C
Motor enclosure in cast iron ----------- ----------- 35.2 bar -----------
Terminal box type WTBX-L 32 bar ----------- ----------- -----------
Terminal box type WTBX-M ----------- ----------- ----------- 37.2 bar
Terminal box type WTBX-S ----------- ----------- ----------- 30.4 bar
Terminal box type WTBX-XS ----------- ----------- ----------- 24.8 bar
Terminal box type CG47 ----------- ----------- ----------- 69.6 bar

In accordance with clause 7.1 of the IEC 60079-7 standard, the adaptors and the terminal boxes type CG47, CEFGH340, CEFGH500, WTBX-XS,
WTBX-S, WTBX-M and WTBX-L protected by increased safety must have successfully passed before delivery a dielectric strength test on each of
the different circuits of the connection units, performed according to the relevant standards, the supply voltage shall be applied for one minute.
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0037X
IECEx INE 12.0037X-01_Annex.pdf Issue No.: 1
Page 5 of 6
Annex: IECEx INE 12.0037X-01_Annex.pdf

LIST OF THE COMPONENT INTENDED TO BE INSTALLED ON THE MOTOR AND/OR TERMINAL BOXES

Type of component Name of Certificate number IEC STANDARDS


manufacturer
60079-0 60079-1 60079-7 60079-11 60079-31
Bushing Emil A. Peters IECEx PTB 08.0032U 2011 ed 6 2007 ed 6 2006
GmbH (*) ed.4(*)
Connecting terminal BARTEC GmbH IECEx PTB 07.0007U 2011 ed 6 2015 ed.5

Terminals blocks PHOENIX IECEx KEM 06.0034U 2011 ed 6 2006 ed.4


CONTACT (*)
Protective conductor PHOENIX IECEx KEM 06.0035U 2011 ed 6 2006 ed.4
terminal blocks CONTACT (*)
Terminal blocks and PHOENIX IECEx KEM 07.0008U 2011 ed 6 2006 ed.4
protective conductor CONTACT (*)
Range of rail WEG DRIVES IECEx FTZU 2007 ed 5 2006
12.0005U (*) ed.4(*)
Range of rail WEG DRIVES IECEx FTZU 2007 ed 5 2006 ed.4
12.0006U (*) (*)
Range of rail WEG DRIVES IECEx FTZU 2007 ed 5 2006 ed.4
12.0007U (*) (*)
Bushing Emil A. Peters IECEx PTB 08.0054U 2011 ed 6 2007 ed 6 2006 ed.4
GmbH (*) (*)
Bushing Emil A. Peters IECEx PTB 08.0052U 2011 ed 6 2007 ed 6 2006 ed.4
GmbH (*) (*)
Bushing Emil A. Peters IECEx PTB 08.0053U 2004 ed 4 2003 ed 5 2006 ed.4
GmbH (*) (*) (*)
Phase segregated Quartzelec IECEx SIR 10.0147U 2011 ed 6 2006 ed.4 2013 ed.2
terminal box Limited (*)
Breathing and CORTEM/ELFIT IECEx CES 14.0016U 2011 ed 6 2007 ed 6 2006 ed.4 2008 ed.1
Draining valves (*) (*) (*)

Conductor bushing STAHL IECEx PTB 06.0081U 2011 ed 6 2014 ed 7


Terminal block WEIDMULLER IECEx ULD 05.0008U 2004 ed 4 2001 ed.3
(*) (*)
Bushing STAHL IECEx PTB 06.0080U 2004 ed 4 2001 ed 4 2001 ed.3
(*) (*) (*)
Control unit STAHL IECEx BVS 07.0029U 2011 ed 6 2014 ed 7 2006 ed.4 2011 ed.6
(*)
Line bushing BARTEC GmbH IECEx EPS 13.0045U 2011 ed 6 2014 ed 7
Range of terminal WEIDMULLER IECEx SIR 05.0036U 2004 ed 4 2001 ed.3
strips (*) (*)
Line bushing BARTEC GmbH IECEx EPS 14.0020U 2011 ed 6 2007 ed 6 2006 ed.4
(*) (*)
Self Limiting Heating BARTEC GmbH IECEx KEM 07.0047U 2011 ed 6 2008 ed.1
Cable (*)
Self limiting heating BARTEC GmbH IECEx KEM 07.0048U 2011 ed 6 2008 ed.1
cable (*)
Temperature sensor EPHY-MESS IECEx IBE 14.0058U 2011 ed 6 2006 ed.4 2011 ed.6 2013 ed.2
Gmbh (*)
IECEx Certificate
of Conformity
Certificate No.: IECEx INE 12.0037X
IECEx INE 12.0037X-01_Annex.pdf Issue No.: 1
Page 6 of 6
Annex: IECEx INE 12.0037X-01_Annex.pdf

Type of component Name of Certificate number IEC STANDARDS


manufacturer
60079-0 60079-1 60079-7 60079-11 60079-31
Bushing Emil A. Peters IECEx PTB 09.0002U 2004 ed 4 2003 ed 5
GmbH (*) (*)
Range of stopping Hawke IECEx BAS 06.0029U 2011 ed 6 2006 ed.4 2008 ed.1
plugs (*) (*)
Bushing Emil A. Peters IECEx PTB 09.0004U 2011 ed 6 2007 ed 6 2006 ed.4
GmbH (*) (*)
Insulator bushings CELMEX S.r.l. IECEx CES 15.0015U 2011 ed 6 2007 ed 6 2006 ed.4
(*) (*)
Line entry BARTEC GmbH IECEx PTB 13.0050U 2011 ed 6 2007 ed 6 2013 ed.2
(*)
Line bushing BARTEC GmbH IECEx CML 14.0003U 2011 ed 6 2007 ed 6 2006 ed.4
(*) (*)
Conductor sealing CORTEM S.p.A IECEx CES 10.0003U 2008 ed.1
bushings 2011 ed 6 2007 ed 6 (*)
(*)
Threaded adapter Emil A. Peters IECEx PTB 09.0006U
GmbH 2011 ed 6 2007 ed 6
(*)

Accessories for 2008 ed.1


enclosures “d” and/or FEAM IECEx TUN 12.0025U 2011 ed 6 2007 ed 6 2006 ed.4
(*) (*) (*)
“e” and “tb”
Accessories for 2008 ed.1
enclosures “d” and/or FENEX S.r.l IECEx EXA 13001U 2011 ed 6 2007 ed 6 2006 ed.4
(*) (*) (*)
“e” and “tb”
Ring-core current F.T.M. s.r.l.
transformer Fabbrica IECEx CES 13.0015U 2011 ed 6 2015 ed.5
Trasformatori di
Misura
RSV motor Anti- FLEXELEC S A IECEx SIR 10.0151U 2006 ed.4
condensation 2011 ed 6 (*)
Anti-condensation ELTRON IECEx ITS 08.0002U
heater CHROMALOX 2011 ed 6 2015 ed.5

Blanking plug Emil A. Peters IECEx PTB 09.0003U


GmbH 2011 ed 6 2007 ed 6
(*)
Slot resistance – PAUL RÜSTER IECEx IBE 14.0011U
thermometer and Co GmbH 2011 ed 6 2006 ed.4
thermocouples (*)

(*) No Major technical changes between the standard IEC 60079-0 2004 ed 4 and 2007 ed 5.
(*) No Major technical changes between the standard IEC 60079-0 2007 ed 5 and 2011 ed 6.
(*) No impact by the Major technical changes between the standard IEC 60079-1 2001 ed 4 and 2003 ed 5.
(*) No impact by the Major technical changes between the standard IEC 60079-1 2003 ed 5 and 2007 ed 6.
(*) No impact by the Major technical changes between the standard IEC 60079-1 2007 ed 6 and 2014 ed 7.
(*) No impact by the Major technical changes between the standard IEC 60079-7 2001 ed 3 and 2006 ed 4.
(*) No impact by the Major technical changes between the standard IEC 60079-7 2006 ed 4 and 2015 ed 5.
(*) No impact by the Major technical changes between the standard IEC 60079-31 2008 ed 1 and 2013 ed 2.

You might also like