You are on page 1of 4

IECEx Certificate

of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

Certificate No.: IECEx BAS 13.0008X Page 1 of 3 Certificate history:

Status: Current Issue No: 0

Date of Issue: 2013-08-07

Applicant: WEG Equipamentos Eletricos S.A


Av. Prefeito Waldemar Grubba
3000. Jaragua do Sul
SC
CEP: 89256-900
Brazil

Equipment: A Range of Induction Motors of Frame Size 71 and 80

Optional accessory:

Type of Protection: Flameproof and Dust

Marking: Ex d IIC T4 Ta -55°C to + 80°C Gb


Ex tb III C T135°C Ta -55°C to + 80°C Db IP66 see schedule

Approved for issue on behalf of the IECEx R S Sinclair


Certification Body:

Position: General Manager

Signature:
(for printed version)

Date:

1. This certificate and schedule may only be reproduced in full.


2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting www.iecex.com or use of this QR Code.

Certificate issued by:


SGS Baseefa Limited
Rockhead Business Park
Staden Lane
Buxton
Derbyshire
SK17 9RZ
United Kingdom
IECEx Certificate
of Conformity
Certificate No.: IECEx BAS 13.0008X Page 2 of 3

Date of issue: 2013-08-07 Issue No: 0

Manufacturer: WEG Equipamentos Eletricos S.A


Av. Prefeito Waldemar Grubba
3000. Jaragua do Sul
SC
CEP: 89256-900
Brazil

Additional
manufacturing
locations:

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended

STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards

IEC 60079-0:2011 Explosive atmospheres - Part 0: General requirements


Edition:6.0

IEC 60079-1:2007-04 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:6

IEC 60079-31:2008 Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'
Edition:1

This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.

TEST & ASSESSMENT REPORTS:


A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in:

Test Report:
GB/BAS/ExTR13.0016/00

Quality Assessment Report:


GB/BAS/QAR13.0007/05
IECEx Certificate
of Conformity
Certificate No.: IECEx BAS 13.0008X Page 3 of 3

Date of issue: 2013-08-07 Issue No: 0

EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:

The range of induction motor of frame size 71 and 80 comprises a stator frame, endshields and main and auxiliary terminal boxes all
fabricated from cast iron. The single ended drive shaft has an external cooling fan at the non-drive end. All cover fasteners are grade 8.8/12.9
steel or grade A2/4-70 or 80 stainless steel.

For full description please see Annex.

SPECIFIC CONDITIONS OF USE: YES as shown below:


1 The flamepath gaps are less that those permitted by IEC60079-1 for gas group IIC and shall not be enlarged in service.

2 The motors may be provided with integral leads, which must be suitably protected and terminated within an enclosure suitable for the
conditions of use.

3 When provided with a breather-drain to IECEx CSA 12.0005U the motors are excluded from Group I, and are limited to temperature
classification T5 to T2 Ta -55 °C to + 50 °C , or T4 to T2 Ta -55 °C to + 80 °C , and have an IP rating of IP6X.

4 The maximum surface temperature was determined without a dust layer. The end user shall prevent a dust layer forming on the motors.

5 After de-energising a delay 60 minutes is required before opening.

Annex:

IECEx BAS 13.0008X Annex.pdf


SGS Baseefa Limited
Rockhead Business Park
Staden lane, Buxton, Derbyshire
SK17 9RZ
United Kingdom

ANNEX to IECEx BAS 13.0008X Issue No. 0 Date: 07/08/2013

The frames are provided with a terminal neck for the main terminal box. A single auxiliary terminal box may be attached to the side of the
main terminal box.

The motors have rolling element bearings, are foot or flanged mounted for horizontal and vertical use and may be provided with anti-
condensation heaters rated up to 7.5W.

The motors are rated from 220V up to 1100V 50/60Hz or variable frequency up to a maximum of 120Hz when supplied from a type
VPWM, CFW09 or CFW11 invertors manufactured by WEG.
o
The motors have a maximum rating as indicated below for use in a maximum ambient temperature of 40 C when continuously rated for
S1 duty and connected to a 3 phase supply having form and symmetry not worse than that defined in IEC 60034-1 and operated within
the defined voltage and frequency limits for Zone A.

Frame size 71 80
Maximum
0.75 1.5
output (kW)
Poles 2-8 2-10

The motors are de-rated in accordance with the manufacturer’s instructions for use with variable frequency supplies, a maximum ambient
o o
temperature between 40 C and 80 C, altitudes above 1000m, S2 to S9 duty and a service factor of 1.0 to 1.25.

The motors can be provided with various seal arrangements and materials for ingress protection IP55, IP65 and IP66 to a maximum
o
temperature of 160 C.

Options include a double ended shaft, integral leads, anti-condensation heaters, thermal protectors, and a breather-drain to IECEx CSA
12.0005U.

Cable entry holes are provided as specified on the certified drawings for the accommodation of flameproof cable entry devices, with or
without the interposition of a flameproof thread adapter. Unused entries are to be fitted with suitable certified flameproof stopping plugs.
The cable entry devices, thread adapters and stopping plugs shall be suitable for the equipment, the cable and the conditions of use and
shall be certified as Equipment (not a Component) under an EC Type Examination Certificate to Directive 94/9/EC.

When used in an explosive dust atmosphere the cable entry devices shall maintain the ingress protection of the enclosure

Variation 1.1

The motors may be alternatively marked for gas groups IIA, IIB I, dust groups IIIB, IIIA, temperature classifications of T3, and T2 without
o
an increase in ambient temperature above 80 C, ingress protection IP5X, IP6X, gas only and dust only as indicated below.

I M2 G Ex d I T* Ta -** C to + ** C Mb
° °

II 2 D Ex tb III* T*** C Ta -** C to + ** C Db IP**


° o °