Technical Submittal Cover Sheet

Document Information
Document to comply with the Project Information Management Plan and uploaded onto Aconex using the correct project metadata suitable for the document type.

Project: 100BG

Package: 6000 - Mechanical

Originator: Dean Randall

Document Nº / Rev 6000-TS-042/ Rev 01

Title Steel Dirt Separators Below 200mm

Date Raised: 18/09/2019 Date Required: ASAP


Associated Sample
Form No. N/A
Part 1 – Material /Product Details
Material Name: Dirt Separators

Material Description: Dirt Separators


Material Purpose: Dirt Separators Date Received: 18/09/19
Location/Branch/
Material Supplier: Spiro trap Source:
Part 2 – Technical / Supporting Details
☒ Technical Specification ☐ UKAS Accreditation ☐ Test Results
Supplied Data to
support Acceptance ☒ Manufacturers Data Sheet ☐ ISO 14001 Certificate ☐ MSDS
(attachments):
☐ Calculations ☐ BES 6001 Certificate ☐ Analysis Survey/Reports

☐ BBA Certificate ☐ COSHH Assessment ☐ Clean & Maintenance


Responsible Sourcing The Water Supply
Environmental Product
☐ Certificates / Chain of ☐ Regulations 1999 ☐
Declaration
Custody Regulation 4 Certificate
☐ CE Marking Certificate

☐ Drawing Reference
☐ Specification Reference

☐ Other Information

Part 3 – Environmental Assurance & Compliance


• Is the material compliant with the requirements in the Project Responsible Sourcing ☐ ☐ ☒
Plan? If no, please supply justification report Yes No N/A

Part 4 – Subcontractor / Supplier Comments

Part 5 – Material / Product Acceptance

Subcontractor Manager

MPX Package Manager

MPX Design Manager

MPX Sustainability Manager

Design Team Representative (If Applicable)

Client Representative (If Applicable)


Name Signature Date Comments

Reference UK-DC-F-002 Revision 5.0 Information Classification Internal


Date 10/10/2018 Author Nisha Khetani Page 1 of 1
Technical submittal sheet

Michael Lonsdale Group Form reference: MJL.043


Contract
Contract title: 100 Bishopsgate ME2758 Mechanical Electrical
number:

Originator: Dean Randall Submission reference:


6000-TS-042
Issued to: Revision number: 01

Copy(s) to: Issue to CAD? Yes No

Specification compliant? Yes No Critical to procurement? Yes No

Electrical interface required? Yes No Date: 18/09/19


Items for approval(description):
Rev 01 updates:
Steel Dirt Seperators 200mm and below: 1. DS/-03/06 is a CHW system separator
2. DS/-03/09 has a flow rate of 42.2 l/S as per data sheet

REFERENCE: DS/-03/05 REFERENCE: DS/-03/06


LOCATION: LEVEL BASEMENT LOCATION: LEVEL BASEMENT
SYSTEM SERVED: TERTIARY CHW SYSTEM SERVED: TERTIARY CHW
REFERENCE: DS/-03/09 REFERENCE: DS/-03/10 REFERENCE: DS/-03/11
LOCATION: LEVEL BASEMENT LOCATION: LEVEL BASEMENT LOCATION: LEVEL BASEMENT
SYSTEM SERVED: TERTIARY LTHW SYSTEM SERVED: TERTIARY LTHW SYSTEM SERVED: UNDERFLOOR
REFERENCE: DS/06/04 REFERENCE: DS/06/05
REFERENCE: DS/06/03 LOCATION: LEVEL 6
LOCATION: LEVEL 6 LOCATION: LEVEL 6
SYSTEM SERVED: TERTIARY LTHW
SYSTEM SERVED: TERTIARY LTHW SYSTEM SERVED: TERTIARY LTHW
REFERENCE: DS/39/03 REFERENCE: DS/39/04 REFERENCE: DS/06/06
LOCATION: LEVEL 39 LOCATION: LEVEL 39 LOCATION: LEVEL 6
SYSTEM SERVED: TERTIARY LTHW SYSTEM SERVED: TERTIARY LTHW SYSTEM SERVED: TERTIARY LTHW

Reply:

Status A – The above item(s) has been reviewed and is accepted.

Status B - The above item(s) is accepted, subject to the following comments:

Status C – The above item(s) has been rejected for the following reasons:

Name: Date:

On behalf of:

Revised 7/08/2014
1. Technical Submission Contents Page

Description Included in Doc Ref


Submission
Technical submission front sheet  Section 1
Specifications/Schedules  Section 2
Certified Performance  Section 3
Manufacturers Information  Section 4
Certified Drawings  Section 5
Design Calculation Check x Section 6 N/A
BMS Interface  Section 7
List of Recommended Spares x Section 8 N/A

Samples x Section 9 N/A

Signed by Trade Contractor : D.Randall

Date: 18/09/19
Technical submittal sheet

2. Specifications
Contract
TS-6000-042 ME2758 100 Bishopsgate
number:

This document has been submitted in compliance with the "Particular Specification for Mechanical
and Public Health"

Services -3.29 Dirt Seperators and De-aerators (REV 03)

Mechanical services

The following items are offered as compliant those specified for this project.

Particular Specification Reference M-X50XX-002 Rev 03


Standard Specification Reference M-X50XX-001 Rev 05

Please see section 5 for MJL relocation schematics


Technical submittal sheet

3. Certified performance
Contract
TS-6000-042
number: ME2758 100 Bishopsgate

The Following items are spec complaint with the particular specification for this
project - Reference - M-X50XX-002_03, the standard specification - M-X50XX-001_05
!

*.* * *M ) 9/ 69 1 ) 9/ 69
X7 D
2" ' ! 2" ' !
/ 6 / 6

" B " B
3 ( C A 3 ( C % A
' *" 5 B 5
) "" ) ""
' !" " ! ' "% 3Y 5 =9 6 =9 6
. ( " 39 5 16 3 2 5 1 3 2 5
& ! H 3 25
"4 '%' ( ; ! % 3$" 5
% 3$" 5 1 1
. "! 3& 5 & &
%! ! !/ ! !/ !

/01 00/ ! , 63 -* .5 6/ ?
!

*.* * *M ) 9 / 69 @ ) 9/ 69
X7 D
2" ' ! 2" ' !
/ 6 / 6

" B " B
' 32" ' ! 5 32" ' ! C % 5
) "" ) ""
' !" " ! ' "% 3Y 5 >>91 >>91
. ( " 39 5 > 13 2 5 1 63 2 5
& ! H 3 25 1
"4 '%' ( ; ! % 3$" 5
% 3$" 5 1 1
. "! 3& 5 & &
%! ! !/ ! !/ !

*.* * *M ) 9 / 69
X7 D
2" ' !
/ 6

*! "! $$
7! #
" ! 9 !
' '
) ""
' !" " ! ' "% 3Y 5 619>1 >9 ?
. ( " 39 5 >=>
& ! H 3 25 1
"4 '%' ( ; ! % 3$" 5
% 3$" 5 1
. "! 3& 5 &
%! ! !/ !

/01 00/ ! , 63 -* .5 6/ =
!

*.* * *M ) 9 9 6 ) 9 9 >
X7 D

" B " B
3 ( A 3 ( C % A
' B 5 *" 5
) "" ) ""
' !" " ! ' "% 3Y 5 >>91 >>91
. ( " 39 5 =6 = ??
& ! H 3 25
"4 '%' ( ; ! % 3$" 5
% 3$" 5 1 1
. "! 3& 5 & &
%! ! !/ ! !/ !

/01 00/ ! , 63 -* .5 6/ @
!

*.* * *M ) 9 9 1 ) 9 9
X7 D

" B " B
' 3 5 3 C % 5
) "" ) ""
' !" " ! ' "% 3Y 5 >>91 >>91
. ( " 39 5 > ?? > =?
& ! H 3 25 1 1
"4 '%' ( ; ! % 3$" 5
% 3$" 5 1 1
. "! 3& 5 & &
%! ! !/ ! !/ !

/01 00/ ! , 63 -* .5 6/
!

*.* * *M ) 96@9 6 ) 96@9 >


X7 D
6@ 6@

" B " B
' 3 5 3 C % 5
) "" ) ""
' !" " ! ' "% 3Y 5 >>91 >>91
. ( " 39 5 1 =3 2 5 1 @3 2 5
& ! H 3 25 1 3 2 5 1 3 2 5
"4 '%' ( ; ! % 3$" 5
% 3$" 5 1 1
. "! 3& 5 & &
%! ! !/ ! !/ !

/01 00/ ! , 63 -* .5 6/
Technical submittal sheet

4. Manufacturers information
Contract
TS-6000-042 ME2758 100 Bishopsgate
number:

This section contains all of the relevant manufacturers information relating to the Dirt Seperators to be provided
spiroTRAP®

DIRT SEPARATORS FOR


HEATING, COOLING AND
PROCESS SYSTEMS

SPIRO

EXCEPTIONAL
GUARANTEE

DOMESTIC | COMMERCIAL | INDUSTRY


The smallest particle of dirt
can cause the biggest problems
Dirt in system water can cause problems and heavy wear to components. This
dirt largely consists of corrosion particles which seek out the magnetic fields in Total solutions
pumps, valves and control valves. Other dirt particles will be pumped round by Spirotech offers an extensive range of
the system and will eventually collect in critical components. The result? total solutions for HVAC and process
Unnecessary energy consumption, recurring complaints, reduced efficiency, systems: accessories, additives and
faults and failure. advice to ensure optimum efficiency
and guarantee the quality of the system
A filter is often installed in order to rectify maintenance-free and continuously removes fluid. These products and services
problems caused by dirt but this is not the all dirt particles. Independent tests have reduce faults, wear and maintenance as
optimal solution. Filters clog up and have to shown that even microscopic particles are well as improve system performance
be cleaned and replaced on a regular basis, removed from the fluid flow and the and lower energy consumption. And
resulting in additional work and costs. accumulated dirt does not affect the what is more, these total solutions
Spirotech has developed the most effective operation of the SpiroTrap. What is more, provide major benefits and save time
solution: the SpiroTrap dirt separator. A the SpiroTrap - unlike a filter - has a very low during the design, installation, start-up
SpiroTrap dirt separator is virtually and constant flow resistance. and commissioning of systems.

Just how small are dirt par�cles?


Scope of SpiroTrap
Visible to the naked eye
Scope of standard filter

Welding grains
Hair
Haema�te
Sand

Magne�te

0.001 0.01 0.1 1 10 mm “The presence of dirt causes un-


1µm 1000 µm necessary maintenance and costly
callouts.”
Especially the smallest dirt particles (5-10 µm) cause problems.

2
SpiroTrap dirt separators: time-saving and effective
At the heart of the SpiroTrap is a spiral structure through which the fluid flows.
This is the “Spirotube”, which ensures that dirt particles sink automatically.
Although the Spirotube can trap the smallest dirt particles, it has a very open
structure which means that the SpiroTrap does not clog up. The flow and the
low pressure drop are not affected by the accumulated dirt, since it is collected
outside the main flow.

Dirt trapped can be discharged while the are installed, the system will have to be 1. Lifting eyes make installation of bigger
system is in operation. This saves a great partially drained before the filter can units very easy.
deal of time and therefore represents a be cleaned or replaced. When the drain 2. Solid construction guarantees a very long
major advantage over filters since with valve is opened, the dirt collected is life.
standard filters, the system has to be discharged quickly and effectively. This 3. The unique Spirotube is the heart. This
switched off to enable cleaning to be action - opening and closing the valve - component has been specially designed
carried out. If no additional shut-off valves only takes a few seconds. for optimum dirt separation and has a
very low flow resistance.
4. Drain valve for removing dirt collected.
5. Many different connection options. Brass
with compression fittings or female
thread, horizontal and vertical. Steel with
1
5 welded ends or flanges.
6. The flow is not obstructed by the dirt
collected.
7. Large capacity dirt collection chamber
reduces the need for frequent draining.

6
2

3 7

Benefits of SpiroTrap
• Very small particles, from 5 µm • No unnecessary shutdown.
(= 0.005 mm) are separated and removed. • Connection diameters from ¾” to DN 600
• Dirt can be discharged while the system is and above.
in operation. • A complete range, suitable for various SpiroPlus
• No shut-off valves or bypass required. pressures and temperatures. Protect and optimize the system and
SPIRO
• Minimal constant pressure drop. • Exceptional guarantee. its efficiency with SpiroPlus flushing
• Maintenance only takes a few seconds. EXCEPTIONAL
GUARANTEE agents and additives.

3
An extensive range of SpiroTrap dirt separators
Optimum system and process water quality is achieved when air and dirt is
kept to a minimum. If air and dirt is not removed, or is not removed sufficiently,
numerous complaints and problems can arise such as annoying noises, frequent
manual venting, deteriorating pump performance, an imbalance in the system,
unnecessary disturbance and excessive wear. All these things result in higher
energy consumption, complaints and failure and often require immediate
action.

Spirotech offers an extensive range of and in (stainless) steel. The brass separators,
SpiroTrap dirt separators specially for suitable for a flow velocity of up to 1 m/s, can
removing dirt. All products can be used for be installed in horizontal and vertical pipes.
both new build projects and for renovating The SpiroTrap MB2 can even be fitted in
heating, cooling and process systems. diagonal pipes. The steel models are available
SpiroTrap dirt separators are available in brass in standard and hi-flow designs.
p at max. flow [kPa]
Max. flow [m3/h]

Article number
Max. flow [l/s]
H [mm]

L [mm]

Connection
22 mm. comp. 118 106 1.3 0.35 1.3 AE022 Brass, horizontal: 22 mm up to 2”
22 mm. comp. V 182 104 1.3 0.35 1.5 AE022V
G¾ 116 85 1.3 0.35 1.3 AE075
G ¾V 172 84 1.3 0.35 1.5 AE075V
G1 143 88 2.0 0.55 1.3 AE100
G1V 172 84 2.0 0.55 2.4 AE100V
G1¼ 161 88 3.6 1.0 1.3 AE125
G1½ 197 88 5.0 1.4 1.3 AE150
G2 238 132 7.5 2.1 1.4 AE200

V= Vertical connection Flow velocity ≤ 1m/s


Operating pressure 0 - 10 bar Fluid temperature 0 - 110°C
Other sizes, materials, pressures and temperatures are available on request.
Brass, vertical: 22 mm up to 1”

4
The flexible SpiroTrap MB2 operates in any position
The SpiroTrap MB2 is a completely universal unit. Just like other SpiroTrap
models it removes simple and efficient both magnetic and non-magnetic dirt
particles from the system fluid. Thanks to the built in magnet, magnetic parts
will be removed quicker. The universal ‘twist-release’ ring is suitable for vertical,
horizontal or even diagonal installations.

How does the Extra SpiroTrap MB2 Suitable for vertical, horizontal and even
SpiroTrap MB2 work? benefits: diagonal piping work
The SpiroTrap MB2 has got a unique dual • Thanks to the built-in magnet, magnetic
action separation system which continuously parts will be removed quicker.
filters out all the dirt; the Spirotube and the • Suitable for vertical, horizontal and even
self-cleaning magnet. The Spirotube traps all diagonal piping work.
dirt particles (from 0,005 mm!) that are • Even easier and quicker to install.
heavier than water. The magnet instantly
boosts the separation of magnetic dirt
(mainly magnetite).
1. Twist-release ring to easily rotate fitting to
desired angle.
2. The unique Spirotube is the heart. This
1 component has been specially designed
for optimum dirt separation and has a
very low flow resistance.
3. Self-cleaning magnet which instantly Rotating fitting mechanism
boosts the separation of magnetic dirt
particles.
4. Drain valve for removing dirt collected.

2
Technical specifications SpiroTrap MB2
Connection [D] 22 mm comp. 28 mm comp.
3 Max. Flow rate [l/sec] 0.30 0.55
Volume [l] 0.18 0.25
Weight [kg] 1.44 1.63

4 Dimension (Hv) 167 mm 178 mm


Dimension (Hh) 149 mm 160 mm
Dimension (L) 100 mm 100 mm
Dimension (M) 102 mm 115 mm
Product code UE022WM UE028WM Universal model

5
Standard vs. Hi-flow
Standard steel SpiroTrap products are designed for a nominal flow velocity up to 1.5 m/s.
At higher velocities the increased turbulence will not always leave sufficient quiet zone in a
standard unit for optimal separation. Exceeding the nominal flow will also lead to a substanti-
ally increased pressure drop. For structural higher flow velocities (up to 3 m/s) a Hi-flow type
is recommended.
Standard; nom. 1.5 m/s Hi-flow; nom. 3 m/s
Nom. = 1,5 m/s Max. = 3 m/s

Article number demountable*

Article number demountable*


p bij max. Connection [kPa]
Max. Connection [m3/h]
Connection OD [mm]

p at max. flow [kPa]

p at max. flow [kPa]


Max. flow [m3/h]

Max. flow [m3/h]


Connection [DN]

Article number*

Article number*
Max. flow [l/s]

Max. flow [l/s]

Max. flow [l/s]


LF [mm]

H [mm]

H [mm]
L [mm]

050 60 260 350 470 3.5 12.5 3.0 7 25 11.8 BE050 BF050 630 7 25 11.8 HE050 HF050
Standard
065 76 260 350 470 5.5 20 2.7 11 40 11.6 BE065 BF065 630 11 40 11.6 HE065 HF065
080 89 370 470 590 7.5 27 2.9 15 54 12.4 BE080 BF080 785 15 54 12.4 HE080 HF080
100 114 370 475 590 13 47 3.7 26 94 14.6 BE100 BF100 785 26 94 14.6 HE100 HF100
125 140 525 635 765 20 72 4.2 40 144 16.8 BE125 BF125 1045 40 144 16.8 HE125 HF125
150 168 525 635 765 30 108 4.9 60 215 19.4 BE150 BF150 1045 60 215 19.4 HE150 HF150
200 219 650 775 975 50 180 5.8 100 360 23.1 BE200 BF200 1315 100 360 23.1 HE200 HF200
250 273 750 890 1215 80 288 6.9 160 575 27.7 BE250 BF250 1715 160 575 27.7 HE250 HF250
300 324 850 1005 1430 113 405 7.7 225 810 31.0 BE300 BF300 2025 225 810 31.0 HE300 HF300
350 356 n/a 1128 1910 140 500 7.8 280 1000 31.0 BE350 BF350 2400 280 1000 31.0 HE350 HF350
400 406 n/a 1226 2120 180 650 8.4 360 1300 34.0 BE400 BF400 2680 360 1300 34.0 HE400 HF400
450 457 n/a 1330 2320 235 850 10.0 470 1700 39.0 BE450 BF450 2960 470 1700 39.0 HE450 HF450
500 508 n/a 1430 2540 295 1060 11.0 590 2120 43.0 BE500 BF500 3250 590 2120 43.0 HE500 HF500
Hi-flow
600 610 n/a 1630 2980 425 1530 12.0 835 3000 47.0 BE600 BF600 3830 835 3000 47.0 HE600 HF600

Operating pressure 0 - 10 bar Fluid temperature 0 - 110°C * for weld ends add L (e.g. BE200L)
Other sizes, materials, pressures and temperatures are available on request. for flanges add F (e.g. BE200F)

Select the correct SpiroTrap


1. Determine the pipe diameter.
2. Determine the flow.
3. Determine the correct model using the table.

Applicable
Max. flow m3/h & l/s
SpiroTrap
1000
1060
1300
1530
1700
2120
3000
12.5

108
144
180
215
288
360
405
500
575
650
810
850

m3/h Standard: DN50 to DN600


20
25
27
40
47
54
72
94

Standard

Hi-flow

l/s
100
113
140
160
180
225
235
280
295
360
425
470
590
835
3.5
5.5

7.5
11
13
15
20
26
30
40
50
60
80
7

DN050 BE/BF050 HE/HF050


DN065 BE/BF065 HE/HF065
DN080 BE/BF080 HE/HF080
DN100 BE/BF100 HE/HF100
DN125 BE/BF125 HE/HF125
DN150 BE/BF150 HE/HF150
DN200 BE/BF200 HE/HF200
DN250 BE/BF250 HE/HF250
DN300 BE/BF300 HE/HF300
Hi-flow: DN50 to DN600
DN350 BE/BF350 HE/HF350
DN400 BE/BF400 HE/HF400
DN450 BE/BF450 HE/HF450
DN500 BE/BF500 HE/HF500
DN600 BE/BF600 HE/HF600

standard model a standard model at maximum flow,


= = = choose bigger ∅ or lower the flow
nominal flow hi-flow recommended

Other sizes, materials, pressures and temperatures are available on request.

Choosing a larger connection size allows achieving the same flow rate with a lower flow Demountable: DN50 to DN600
velocity, resulting in better separation efficiency and a lower pressure drop (less energy loss). Hi-flow demountable: DN50 to DN600

Demountable
If the level of contamination is such that it needs to be possible to replace or clean the A SpiroTrap dirt separator is preferably
separating element (Spirotube assembly), the demountable model can be chosen. to be installed in the main return pipe.

6
Flow resistance graph for SpiroTrap
Unlike filters, SpiroTrap dirt separators have a minimal constant pressure drop.

Brass Steel
10 100

DN 00
M

0
60
5
DN0
DN 00
W

45
DN 300
DN 0
35
Add-on sets

4
28

0
DN
G1 U V

25
0
20
V E0
¾

DN
0
DN
15
G¾ G

Spirotech provides complete add-on sets for

5
0

12

DN
&V&

10
mm m M

DN
DN
80
50

65
2222m2W

vertical oil and gas boilers with distributors

DN
DN

DN
02

10
Pressure drop [kPa]

Pressure drop [kPa]


¼

½
UE

and mixing groups which are ready for use.


G1
G1

G2
G1
These can be installed between the boiler
1
and the mixing group.

0.1 0.1
0.1 1 10 1 10 100 1000
Flow [l/s] Flow [l/s]
Insulation
Steel
100 Specially made insulation
DN 00

sets are available for most


0
60
5
DN0
DN 00
45
DN 300
DN 0
35
4
0
DN

dirt separators.
25
0
20

DN
0
DN
15
5
0

12

DN
10
DN
DN
80
50

65
DN
DN

DN

10 Custom-made solutions and OEM


Pressure drop [kPa]

applications
Spirotech offers not only standard products.
If necessary, we work with customers to
1 produce custom-made solutions. These are
based on users’ specific requirements. If
desired, these can also be supplied as OEM
products.
0.1
10 1 10 100 1000
Flow [l/s]

Measured values according to Spirotech standard. Values shown are maximum values.
Please contact us for further information.

SpiroTrap dirt separators are suitable for water and water/glycol mixtures (max. 50%). They
can be used in combination with locally approved chemical additives and inhibitors that are
compatible with the materials applied within the system. Not suitable for drinking water.

The standard SpiroTrap is suitable for a temperature range of 0 to 110 °C and for an operating Digital support
pressure of 0 to 10 bar. The SpiroTrap housing (from DN 050) is made of unalloyed steel. The Product data sheets, standard specification
flange connection is PN 16. The housing of the SpiroTrap 22 mm compression, ¾”, 1”, 1¼”, 1½” texts, line drawings, CAD symbols, project
and 2” is made of brass. Other sizes, materials, pressures and temperatures are available on descriptions, etc. are available via our
request. website.

Separate literature is available which


contains detailed product information.
You can also find this information on our
website.

7
SPIROLIFE
Guarantee of a lifetime!
Spirotech’s Exceptional Guarantee
Terms!
SPIRO Brass Products ≤ 110°C:
20 years
Steel Products and
Brass Products > 110°C:
5 years
Vacuum Degassers:
EXCEPTIONAL 2 years
GUARANTEE
Conditions:
Correct selection, installation, maintenance and use
of the products, in accordance with our regulations,
data sheets and user manuals. Our guarantee does
not cover normal wear and tear. Please also see our
general terms and conditions.

Spirotech: accessories, additives and advice


Spirotech designs and produces innovative total solutions for conditioning fluids in HVAC and
process systems. Our products and services reduce faults and wear, less maintenance is
required, performance is improved and energy consumption is reduced.

Spirotech is deservedly regarded as the only real specialist in the world. Leading manufactu-
rers of system components recommend Spirotech products on account of their high standard
of quality and the company’s vision on product development and process improvement.

Thanks to a very extensive international network of suppliers, users all over the world enjoy
the benefits of our products and services every day.

Spirotech is a Spiro Enterprises company

Spirotech bv Spirotech UK Ltd. The diagrams and situations presented in this brochure are only intended
to serve as examples. We would be pleased to advise you on any specific
14.382_03

PO Box 207 PO Box 818 Altrincham situation. Modifications and printing/typographic errors reserved.
5700 AE Helmond, NL Cheshire, WA15 5GZ ©Copyright Spirotech bv. no part of this publication may be used without
T +31 (0)492 578 989 T +44 (0)208 451 3344 prior written permission from Spirotech bv.

F +31 (0)492 541 245 F +44 (0)208 451 3366


info@spirotech.nl info@spirotech.co.uk
www.spirotech.com www.spirotech.co.uk
SPIROTECH SPECIFICATION SHEET
Version 16.2 / BDB
Product: SpiroTrap Hi-flow Type: HE200F
DN 200 Flanged end
Customer: M J Lonsdale

Project: 100, Bishopsgate Date: 28/11/2016

Reference: DS/-03/05

Design criteria Drawing:


Medium: Water / glycol (max 50%)
Max. flow velocity: 3 m/s
Max. flow rate: 100.0 l/s
Max. pressure: 10 bar-g
Max. temperature: 110 °C
Δp at max. flow: 23.18 kPa
Flow: 53.0 l/s
Δp at flow: 6.52 kPa
Design standard: EN 13445

Testing and quality assurance


Test pressure (bar): 7
Test medium: Air
Test certificate: no
Design and manufacturing acc. 97/23/EC: yes
Material certificates (structural parts): no
Drawing: no
Weld procedures: no
Nondestructive Testing (X-ray: 10%): no
Notified body inspection: no

Construction materials Dimensions:


Body: S235 JR G2 (St.37) DN 200 mm
Connections: S235 JR G2 (St.37) OD 219.1 mm
Fittings: S235 JR G2 (St.37) H 1240 mm
Flanges (DIN 2633 PN16): C22.8 h 955 mm
Heads: S235 JR G2 (St.37) D 406 mm
Spirotube Tube: S235 JR G2 (St.37) LF 775 mm
Wire: Copper e 1"
Solder: Tin(SnCu3)
Paint: Standard
Color: Yellow (RAL 1003)
Drain valve: Nickeled brass Volume: 150 ltr
Dry weight (approx): 136 kg

Subject to changes
SPIROTECH SPECIFICATION SHEET
Version 16.2 / BDB
Product: SpiroTrap Hi-flow Type: HE200F
DN 200 Flanged end
Customer: M J Lonsdale

Project: 100, Bishopsgate Date: 28/11/2016

Reference: DS/-03/06

Design criteria Drawing:


Medium: Water / glycol (max 50%)
Max. flow velocity: 3 m/s
Max. flow rate: 100.0 l/s
Max. pressure: 10 bar-g
Max. temperature: 110 °C
Δp at max. flow: 23.18 kPa
Flow: 60.5 l/s
Δp at flow: 8.49 kPa
Design standard: EN 13445

Testing and quality assurance


Test pressure (bar): 7
Test medium: Air
Test certificate: no
Design and manufacturing acc. 97/23/EC: yes
Material certificates (structural parts): no
Drawing: no
Weld procedures: no
Nondestructive Testing (X-ray: 10%): no
Notified body inspection: no

Construction materials Dimensions:


Body: S235 JR G2 (St.37) DN 200 mm
Connections: S235 JR G2 (St.37) OD 219.1 mm
Fittings: S235 JR G2 (St.37) H 1240 mm
Flanges (DIN 2633 PN16): C22.8 h 955 mm
Heads: S235 JR G2 (St.37) D 406 mm
Spirotube Tube: S235 JR G2 (St.37) LF 775 mm
Wire: Copper e 1"
Solder: Tin(SnCu3)
Paint: Standard
Color: Yellow (RAL 1003)
Drain valve: Nickeled brass Volume: 150 ltr
Dry weight (approx): 136 kg

Subject to changes
SPIROTECH SPECIFICATION SHEET
Version 16.2 / BDB
Product: SpiroTrap Hi-flow Type: HE150F
DN 150 Flanged end
Customer: M J Lonsdale

Project: 100, Bishopsgate Date: 28/11/2016

Reference: DS/-03/09

Design criteria Drawing:


Medium: Water / glycol (max 50%)
Max. flow velocity: 3 m/s
Max. flow rate: 60.0 l/s
Max. pressure: 10 bar-g
Max. temperature: 110 °C
Δp at max. flow: 19.50 kPa
Flow: 42.2 l/s
Δp at flow: 9.62 kPa
Design standard: EN 13445

Testing and quality assurance


Test pressure (bar): 7
Test medium: Air
Test certificate: no
Design and manufacturing acc. 97/23/EC: yes
Material certificates (structural parts): no
Drawing: no
Weld procedures: no
Nondestructive Testing (X-ray: 10%): no
Notified body inspection: no

Construction materials Dimensions:


Body: S235 JR G2 (St.37) DN 150 mm
Connections: S235 JR G2 (St.37) OD 168.3 mm
Fittings: S235 JR G2 (St.37) H 970 mm
Flanges (DIN 2633 PN16): C22.8 h 740 mm
Heads: S235 JR G2 (St.37) D 324 mm
Spirotube Tube: S235 JR G2 (St.37) LF 635 mm
Wire: Copper e 1"
Solder: Tin(SnCu3)
Paint: Standard
Color: Yellow (RAL 1003)
Drain valve: Nickeled brass Volume: 75 ltr
Dry weight (approx): 73 kg

Subject to changes
SPIROTECH SPECIFICATION SHEET
Version 16.2 / BDB
Product: SpiroTrap Type: BE200F
DN 200 Flanged end
Customer: M J Lonsdale

Project: 100, Bishopsgate Date: 28/11/2016

Reference: DS/-03/10

Design criteria Drawing:


Medium: Water / glycol (max 50%)
Nom. flow velocity: 1.5 m/s
Nom. flow rate: 50.0 l/s
Max. pressure: 10 bar-g
Max. temperature: 110 °C
Δp at nom. flow: 5.8 kPa
Flow: 50.0 l/s
Δp at flow: 5.8 kPa
Design standard: EN 13445

Testing and quality assurance


Test pressure (bar): 7
Test medium: Air
Test certificate: no
Design and manufacturing acc. 97/23/EC: yes
Material certificates (structural parts): no
Drawing: no
Weld procedures: no
Nondestructive Testing (X-ray: 10%): no
Notified body inspection: no

Construction materials Dimensions:


Body: S235 JR G2 (St.37) DN 200 mm
Connections: S235 JR G2 (St.37) OD 219.1 mm
Fittings: S235 JR G2 (St.37) H 900 mm
Flanges (DIN 2633 PN16): C22.8 h 615 mm
Heads: S235 JR G2 (St.37) D 406 mm
Spirotube Tube: S235 JR G2 (St.37) LF 775 mm
Wire: Copper e 1"
Solder: Tin(SnCu3)
Paint: Standard
Color: Yellow (RAL 1003)
Drain valve: Nickeled brass Volume: 105 ltr
Dry weight (approx): 105 kg

Subject to changes
SPIROTECH SPECIFICATION SHEET
Version 16.2 / BDB
Product: SpiroTrap Type: BE065F
DN 65 Flanged end
Customer: M J Lonsdale

Project: 100, Bishopsgate Date: 28/11/2016

Reference: DS/-03/11

Design criteria Drawing:


Medium: Water / glycol (max 50%)
Nom. flow velocity: 1.5 m/s
Nom. flow rate: 5.5 l/s
Max. pressure: 10 bar-g
Max. temperature: 110 °C
Δp at nom. flow: 2.9 kPa
Flow: 2.5 l/s
Δp at flow: 0.6 kPa
Design standard: EN 13445

Testing and quality assurance


Test pressure (bar): 7
Test medium: Air
Test certificate: no
Design and manufacturing acc. 97/23/EC: yes
Material certificates (structural parts): no
Drawing: no
Weld procedures: no
Nondestructive Testing (X-ray: 10%): no
Notified body inspection: no

Construction materials Dimensions:


Body: S235 JR G2 (St.37) DN 65 mm
Connections: S235 JR G2 (St.37) OD 76.1 mm
Fittings: S235 JR G2 (St.37) H 395 mm
Flanges (DIN 2633 PN16): C22.8 h 260 mm
Heads: S235 JR G2 (St.37) D 159 mm
Spirotube Tube: S235 JR G2 (St.37) LF 350 mm
Wire: Copper e 1"
Solder: Tin(SnCu3)
Paint: Standard
Color: Yellow (RAL 1003)
Drain valve: Nickeled brass Volume: 5 ltr
Dry weight (approx): 15 kg

Subject to changes
SPIROTECH SPECIFICATION SHEET
Version 16.2 / BDB
Product: SpiroTrap Type: BE100F
DN 100 Flanged end
Customer: M J Lonsdale

Project: 100, Bishopsgate Date: 28/11/2016

Reference: DS/06/03

Design criteria Drawing:


Medium: Water / glycol (max 50%)
Nom. flow velocity: 1.5 m/s
Nom. flow rate: 13.0 l/s
Max. pressure: 10 bar-g
Max. temperature: 110 °C
Δp at nom. flow: 3.7 kPa
Flow: 8.4 l/s
Δp at flow: 1.5 kPa
Design standard: EN 13445

Testing and quality assurance


Test pressure (bar): 7
Test medium: Air
Test certificate: no
Design and manufacturing acc. 97/23/EC: yes
Material certificates (structural parts): no
Drawing: no
Weld procedures: no
Nondestructive Testing (X-ray: 10%): no
Notified body inspection: no

Construction materials Dimensions:


Body: S235 JR G2 (St.37) DN 100 mm
Connections: S235 JR G2 (St.37) OD 114.3 mm
Fittings: S235 JR G2 (St.37) H 515 mm
Flanges (DIN 2633 PN16): C22.8 h 345 mm
Heads: S235 JR G2 (St.37) D 219 mm
Spirotube Tube: S235 JR G2 (St.37) LF 475 mm
Wire: Copper e 1"
Solder: Tin(SnCu3)
Paint: Standard
Color: Yellow (RAL 1003)
Drain valve: Nickeled brass Volume: 17 ltr
Dry weight (approx): 26 kg

Subject to changes
SPIROTECH SPECIFICATION SHEET
Version 16.2 / BDB
Product: SpiroTrap Type: BE100F
DN 100 Flanged end
Customer: M J Lonsdale

Project: 100, Bishopsgate Date: 28/11/2016

Reference: DS/06/04

Design criteria Drawing:


Medium: Water / glycol (max 50%)
Nom. flow velocity: 1.5 m/s
Nom. flow rate: 13.0 l/s
Max. pressure: 10 bar-g
Max. temperature: 110 °C
Δp at nom. flow: 3.7 kPa
Flow: 8.8 l/s
Δp at flow: 1.7 kPa
Design standard: EN 13445

Testing and quality assurance


Test pressure (bar): 7
Test medium: Air
Test certificate: no
Design and manufacturing acc. 97/23/EC: yes
Material certificates (structural parts): no
Drawing: no
Weld procedures: no
Nondestructive Testing (X-ray: 10%): no
Notified body inspection: no

Construction materials Dimensions:


Body: S235 JR G2 (St.37) DN 100 mm
Connections: S235 JR G2 (St.37) OD 114.3 mm
Fittings: S235 JR G2 (St.37) H 515 mm
Flanges (DIN 2633 PN16): C22.8 h 345 mm
Heads: S235 JR G2 (St.37) D 219 mm
Spirotube Tube: S235 JR G2 (St.37) LF 475 mm
Wire: Copper e 1"
Solder: Tin(SnCu3)
Paint: Standard
Color: Yellow (RAL 1003)
Drain valve: Nickeled brass Volume: 17 ltr
Dry weight (approx): 26 kg

Subject to changes
SPIROTECH SPECIFICATION SHEET
Version 16.2 / BDB
Product: SpiroTrap Type: BE150F
DN 150 Flanged end
Customer: M J Lonsdale

Project: 100, Bishopsgate Date: 28/11/2016

Reference: DS/06/05

Design criteria Drawing:


Medium: Water / glycol (max 50%)
Nom. flow velocity: 1.5 m/s
Nom. flow rate: 30.0 l/s
Max. pressure: 10 bar-g
Max. temperature: 110 °C
Δp at nom. flow: 4.9 kPa
Flow: 14.8 l/s
Δp at flow: 1.2 kPa
Design standard: EN 13445

Testing and quality assurance


Test pressure (bar): 7
Test medium: Air
Test certificate: no
Design and manufacturing acc. 97/23/EC: yes
Material certificates (structural parts): no
Drawing: no
Weld procedures: no
Nondestructive Testing (X-ray: 10%): no
Notified body inspection: no

Construction materials Dimensions:


Body: S235 JR G2 (St.37) DN 150 mm
Connections: S235 JR G2 (St.37) OD 168.3 mm
Fittings: S235 JR G2 (St.37) H 690 mm
Flanges (DIN 2633 PN16): C22.8 h 460 mm
Heads: S235 JR G2 (St.37) D 324 mm
Spirotube Tube: S235 JR G2 (St.37) LF 635 mm
Wire: Copper e 1"
Solder: Tin(SnCu3)
Paint: Standard
Color: Yellow (RAL 1003)
Drain valve: Nickeled brass Volume: 50 ltr
Dry weight (approx): 56 kg

Subject to changes
SPIROTECH SPECIFICATION SHEET
Version 16.2 / BDB
Product: SpiroTrap Type: BE150F
DN 150 Flanged end
Customer: M J Lonsdale

Project: 100, Bishopsgate Date: 28/11/2016

Reference: DS/39/03

Design criteria Drawing:


Medium: Water / glycol (max 50%)
Nom. flow velocity: 1.5 m/s
Nom. flow rate: 30.0 l/s
Max. pressure: 10 bar-g
Max. temperature: 110 °C
Δp at nom. flow: 4.9 kPa
Flow: 15.2 l/s
Δp at flow: 1.2 kPa
Design standard: EN 13445

Testing and quality assurance


Test pressure (bar): 7
Test medium: Air
Test certificate: no
Design and manufacturing acc. 97/23/EC: yes
Material certificates (structural parts): no
Drawing: no
Weld procedures: no
Nondestructive Testing (X-ray: 10%): no
Notified body inspection: no

Construction materials Dimensions:


Body: S235 JR G2 (St.37) DN 150 mm
Connections: S235 JR G2 (St.37) OD 168.3 mm
Fittings: S235 JR G2 (St.37) H 690 mm
Flanges (DIN 2633 PN16): C22.8 h 460 mm
Heads: S235 JR G2 (St.37) D 324 mm
Spirotube Tube: S235 JR G2 (St.37) LF 635 mm
Wire: Copper e 1"
Solder: Tin(SnCu3)
Paint: Standard
Color: Yellow (RAL 1003)
Drain valve: Nickeled brass Volume: 50 ltr
Dry weight (approx): 56 kg

Subject to changes
SPIROTECH SPECIFICATION SHEET
Version 16.2 / BDB
Product: SpiroTrap Type: BE150F
DN 150 Flanged end
Customer: M J Lonsdale

Project: 100, Bishopsgate Date: 28/11/2016

Reference: DS/39/04

Design criteria Drawing:


Medium: Water / glycol (max 50%)
Nom. flow velocity: 1.5 m/s
Nom. flow rate: 30.0 l/s
Max. pressure: 10 bar-g
Max. temperature: 110 °C
Δp at nom. flow: 4.9 kPa
Flow: 15.1 l/s
Δp at flow: 1.2 kPa
Design standard: EN 13445

Testing and quality assurance


Test pressure (bar): 7
Test medium: Air
Test certificate: no
Design and manufacturing acc. 97/23/EC: yes
Material certificates (structural parts): no
Drawing: no
Weld procedures: no
Nondestructive Testing (X-ray: 10%): no
Notified body inspection: no

Construction materials Dimensions:


Body: S235 JR G2 (St.37) DN 150 mm
Connections: S235 JR G2 (St.37) OD 168.3 mm
Fittings: S235 JR G2 (St.37) H 690 mm
Flanges (DIN 2633 PN16): C22.8 h 460 mm
Heads: S235 JR G2 (St.37) D 324 mm
Spirotube Tube: S235 JR G2 (St.37) LF 635 mm
Wire: Copper e 1"
Solder: Tin(SnCu3)
Paint: Standard
Color: Yellow (RAL 1003)
Drain valve: Nickeled brass Volume: 50 ltr
Dry weight (approx): 56 kg

Subject to changes
SPIROTECH SPECIFICATION SHEET
Version 16.2 / BDB
Product: SpiroTrap Type: BE150F
DN 150 Flanged end
Customer: M J Lonsdale

Project: 100, Bishopsgate Date: 28/11/2016

Reference: DS/06/06

Design criteria Drawing:


Medium: Water / glycol (max 50%)
Nom. flow velocity: 1.5 m/s
Nom. flow rate: 30.0 l/s
Max. pressure: 10 bar-g
Max. temperature: 110 °C
Δp at nom. flow: 4.9 kPa
Flow: 14.9 l/s
Δp at flow: 1.2 kPa
Design standard: EN 13445

Testing and quality assurance


Test pressure (bar): 7
Test medium: Air
Test certificate: no
Design and manufacturing acc. 97/23/EC: yes
Material certificates (structural parts): no
Drawing: no
Weld procedures: no
Nondestructive Testing (X-ray: 10%): no
Notified body inspection: no

Construction materials Dimensions:


Body: S235 JR G2 (St.37) DN 150 mm
Connections: S235 JR G2 (St.37) OD 168.3 mm
Fittings: S235 JR G2 (St.37) H 690 mm
Flanges (DIN 2633 PN16): C22.8 h 460 mm
Heads: S235 JR G2 (St.37) D 324 mm
Spirotube Tube: S235 JR G2 (St.37) LF 635 mm
Wire: Copper e 1"
Solder: Tin(SnCu3)
Paint: Standard
Color: Yellow (RAL 1003)
Drain valve: Nickeled brass Volume: 50 ltr
Dry weight (approx): 56 kg

Subject to changes
Technical submittal sheet

5. Certified drawings
Contract
TS-6000-042 ME2758 100 Bishopsgate
number:

N/A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

For continuation refer to Drawing


Number. 6000-109XX-504
COMPUTER AIDED DRAWING - AVOID MANUAL MODIFICATION

THIS DRAWING MUST NOT BE SCALED.


ALL DIMENSIONS TO BE CHECKED ON SITE.

A REFERENCE DRAWINGS. A
DRAWING No. TITLE. REV.
M-155XX-503 CONDENSER WATER SCHEMATIC SHEET 07
Refrigerant relief 1 OF 2
line discharge point M-X50XX-400 MECHANICAL SERVICES SYMBOLS 06
LEGEND

(414 Max) (2.63)


326.15 Normal 2.07
64
(102)

KEY PLAN

PN25

PN25

PN25

PN25
Level B1
2
1 B
B
N

15 SHP

NOTES:

C C
326.15 Normal 326.15 Normal

cs bfv

drv bfv bfv drv


water circulation purpose circulation purpose

D D
ABBREVIATIONS:-
bfv cs
drv drv CHW.F - CHILLED WATER FLOW
bfv bfv bfv bfv
CHW.R - CHILLED WATER RETURN
LTHW.F - LOW TEMPERATURE HOT WATER FLOW
LTHW.R - LOW TEMPERATURE HOT WATER RETURN
CW.F - CONDENSER WATER FLOW
CW.R - CONDENSER WATER RETURN
UF.HTG.F - UNDER FLOOR HEATING FLOW
UF.HTG.R - UNDER FLOOR HEATING RETURN
F&R - FLOW AND RETURN
bfv bfv bfv bfv F/A - FROM ABOVE
F/B - FROM BELOW 0
cs cs cs Less than 2.5 pipe diameters (typical)
FFL - FINISH FLOOR LEVEL
Less than 2.5 pipe 1
E diameters (typical) H/L - HIGH LEVEL
bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv
L/L - LOW LEVEL
2
bfv drv bfv drv bfv drv bfv drv bfv drv bfv drv bfv drv bfv drv bfv drv bfv drv bfv drv bfv drv T/A - TO ABOVE
PN16

PN16

PN16

PN16
tp tp tp tp tp tp T/B - TO BELOW
Removable bypass 3
str str str pipe (typical) str str str Removable bypass pipe (typical) AP - ACCESS PANEL
tp tp tp tp tp tp tp tp tp tp tp tp
tp tp tp
SU - SET UP 4
str cv tp tp str cv tp tp str cv tp tp str cv tp tp str cv tp tp str cv tp tp
SD - SET DOWN
tp tp tp tp tp tp cv 163.075 tp tp tp tp cv tp tp 5
drv cv drv cv drv 163.075 drv cv drv drv cv

tg tg tg tg tg tg tg tg tg tg tg tg ITS - IMMERSION TEMPERATURE SENSOR


DPS - DIFFERENTIAL PRESSURE SWITCH 6

BFV - BUTERFLY VALVE


163.075 Normal 163.075 Normal 7
DRV - DOUBLE REGULATING VALVE
tp tp tp tp tp tp
CS - COMMISSIONING SET 8
fc fc fc fc fc fc fc fc fc fc fc fc STR - STRAINER
cv cv cv cv cv cv
F NRV - NON RETURN VALVE. 9
S4 S1 S4 S1 S4 S1 S4 S1 S4 S1 S4 S1
tp tp tp tp tp tp CV - CONTROL VALVE
- 10
fmd fmd fmd fmd fmd fmd fmd fmd fmd fmd fmd fmd
PICV PRESSURE INDEPENDANT CONTROL VALVE
Heat Heat Heat Heat Heat Heat FMD - FLOW MEASURING DEVICE
tg Ex. tg tg Ex. tg tg Ex. tg tg Ex. tg tg Ex. tg tg Ex. tg
SV - SAFETY VALVE
326.15
AV - AIR VENT
tp tp tp tp tp tp tp tp tp tp tp tp PU
fc S3 S2 fc fc S3 S2 fc fc S3 S2 fc fc S3 S2 fc fc S3 S2 fc fc S3 S2 fc
-03/20 DC - DRAIN COCK
hudc hudc hudc hudc hudc hudc hudc hudc hudc hudc hudc hudc
TP - TEST POINT
HEX HEX HEX HEX HEX HEX HUBT - HOSE UNION BIB TAP
Buffer
-03/01 -03/02 -03/03 -03/04 -03/05 -03/06 Spill type Vessel
sv Vessel FC - FLEXIBLE COUPLING
PN25 PN16 PN25 PN16 PN25 PN16 PN25 PN16 PN25 PN16 PN25 PN16
dcv sc
hudc

Duty + Duty + Standby Duty + Duty + Standby flex lsv l/s m/s
326.15 (n/o)
nrv lsv
(n/o) Press. Pa/m size
G DP Unit Pressurisation G
iv
-03/01 System
iv drv Trapped
Drain
iv bfv Capped refrigerant vent pipe
Less than 2.5 pipe diameters
connections for future chiller
Dosing lsv
163.075 hudc
Pot
DP bfv bfv
VSD
tp tp
bfv nrv fc fc str bfv
bfv bfv
02 23-01-17 23-01-17 ISSUED FOR CONSTRUCTION SJN JG
DP 652.3
VSD
bfv bfv bfv bfv bfv bfv
tp tp 01 14-04-16 14-04-16 ISSUED FOR APPROVAL SJN JG
bfv nrv fc fc str bfv Less than 2.5
cs cs cs cs cs pipe diameters REV: DATE: CDM-CHK: REVISION: DRN: CHK:
Dirt bfv
bfv DP
Seperator
VSD
tp tp CLIENT:
bfv nrv fc fc str bfv fm fm fm fm fm
DS Removable bypass pipe
H -03/12 cv cv cv cv cv
DP
VSD
tp tp Active
bfv nrv fc fc str bfv tp tp tp tp tp
De-aerator

DP
DA
bfv bfv VSD
bfv nrv fc fc
tp
str
tp
bfv -03/02 PROJECT:

bfv CH Chillers
Pumps -03/01 (N + 1 future) H
(4 Duty/1 Standby) Future 100 BISHOPSGATE
PP
-03/20
PP
-03/21
PP
-03/22
PP
-03/23
PP
-03/24
CH CH CH hudc CH CH LONDON EC3
-03/02 -03/03 -03/04 tp -03/05 -03/06
str

tp drv
150.2 hudc hudc hudc hudc
water circulation purpose
tp tp tp tp
bfv
I str str str bfv str

Removable bypass pipe tp tp tp tp


cs
51.5
bfv bfv bfv bfv bfv
bfv bfv bfv bfv bfv

cs
STATUS: I
352.3
CONSTRUCTION
DRAWING TITLE:

MECHANICAL SERVICES
CONDENSER WATER SCHEMATIC
SHEET 1 OF 2
Discipline Project Phase
J Level B2 MECHANICAL 1 J
Drawing Originator Originator's Job No.
MICHAEL J LONSDALE ME2758
Checked By Checked Date Drawn By Drawn Date
JN 14/04/2016 SJN 16/02/2015
Approved By Approval Date Scale Bldg Grid Reference
JG 14/04/2016 1:1 @ A0 -

Drawing No. Revision

6000-109XX-503 02
1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
10 MW Heat Rejection Total 10 MW Heat Rejection Total

CT Approx 3333kW CT Approx 3333kW CT Approx 3333kW CT Approx 3333kW CT Approx 3333kW CT Approx 3333kW
39/01 Heat Rejection 39/02 Heat Rejection 39/03 Heat Rejection 39/04 Heat Rejection 39/05 Heat Rejection 39/06 Heat Rejection
COMPUTER AIDED DRAWING - AVOID MANUAL MODIFICATION

THIS DRAWING MUST NOT BE SCALED.


ALL DIMENSIONS TO BE CHECKED ON SITE.

VSD VSD VSD 69 Max VSD VSD VSD REFERENCE DRAWINGS.


A A
54.35 Normal DRAWING No. TITLE. REV.
M-155XX-504 CONDENSER WATER SCHEMATIC SHEET 07
2 0F 2
tp tp tp tp tp tp tp tp tp tp tp tp M-X50XX-400 MECHANICAL SERVICES SYMBOLS LEGEND 06
cv cv cv cv cv cv cv cv cv cv cv cv

tp tp tp tp tp tp tp tp tp tp tp tp
bfv iv bfv iv bfv iv bfv iv bfv iv bfv iv
(nc) (nc) (nc) (nc) (nc) (nc)
69 Max 69 Max 69 Max 69 Max
54.35 Normal 54.35 Normal 54.35 Normal 54.35 Normal
bfv 69 Max bfv bfv 69 Max bfv bfv bfv
(no) 54.35 Normal (no) (no) 54.35 Normal (no) (no) (no)
Immersion Immersion
Temperature Temperature
Sensor Sensor
Overflow
& Drain
Overflow
& Drain
Overflow
& Drain
Overflow
& Drain
Overflow
& Drain
Overflow
& Drain
KEY PLAN
CS CS CS CS
69 Max
CS CS CS CS
69 Max
CS CS
69 Max
CS CS 2
69 Max 69 Max B
B 54.35 Normal 54.35 Normal 54.35 Normal
54.35 Normal
1
54.35 Normal
N
tp tp 138 Max tp tp 276 Max tp tp tp tp 276 Max tp tp 138 Max tp tp

cv cv 108.7 Normal cv cv 217.4 Normal cv cv cv cv 217.4 Normal cv cv 108.7 Normal cv cv 15 SHP


tp tp bfv tp tp tp tp tp tp tp tp tp tp

bfv bfv drv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv drv

NOTES:
Balance Pipe fmd fmd
Balance Pipe

iv iv iv iv iv iv

bfv bfv bfv bfv

Level 39 Plant

C C
414 Max fm fm 414 Max
326.15 Normal 326.15 Normal

Pumps Pumps
(3 Duty/1 Standby) (3 Duty/1 Standby)
DP DP

Control Psa Oxygen Ozone Ozone Psa Oxygen Control tp tp


VSD VSD
tp tp Control Psa Oxygen Ozone Ozone Psa Oxygen Control
Panel Concentrator Generator Generator Concentrator Panel bfv str fc fc nrv bfv bfv nrv fc fc str bfv Panel Concentrator Generator Generator Concentrator Panel
& Dryer Unit & Dryer Unit & Dryer Unit & Dryer Unit

DP DP
VSD VSD
tp tp tp tp
bfv str fc fc nrv bfv bfv nrv fc fc str bfv
Electrical Electrical Electrical Electrical
Supply Vacuum Vacuum Supply Supply Vacuum Vacuum Supply
Sensor Sensor DP DP Sensor Sensor
D tp tp
VSD VSD
tp tp
D
bfv str fc fc nrv bfv bfv nrv fc fc str bfv
Ozone Ozone Ozone Ozone
Eductor Eductor Eductor Eductor
Redox Redox DP DP Redox Redox
Probe Cyclone Cyclone Probe tp tp
VSD VSD
tp tp Probe Cyclone Cyclone Probe
Filter Filter bfv str fc fc nrv bfv bfv nrv fc fc str bfv Filter Filter ABBREVIATIONS:-
Conductivity Conductivity Conductivity Conductivity CHW.F - CHILLED WATER FLOW
Cell Cell Cell Cell CHW.R - CHILLED WATER RETURN
138 Max SP SP SP SP SP SP SP SP 138 Max
108.7 Normal 38/24 38/25 38/26 38/27 108.7 Normal LTHW.F - LOW TEMPERATURE HOT WATER FLOW
38/20 38/21 38/22 38/23
LTHW.R - LOW TEMPERATURE HOT WATER RETURN
Sidestream Sidestream Sidestream Sidestream
Pump Pump Pump Pump CW.F - CONDENSER WATER FLOW

bfv
bfv
CW.R - CONDENSER WATER RETURN
Basket Basket Basket Basket
Strainer Strainer Strainer Strainer UF.HTG.F - UNDER FLOOR HEATING FLOW
DS Dirt Dirt DS UF.HTG.R - UNDER FLOOR HEATING RETURN
-03/03 Seperator 0
Blow-down & Blow-down & Seperator -03/04 Blow-down & Blow-down & F&R - FLOW AND RETURN
Filter Purge To
Ozone Systems With Integral Sidestream Filtration System Filter Purge To Filter Purge To
Ozone Systems With Integral Sidestream Filtration System Filter Purge To
Drain Drain Drain Drain F/A - FROM ABOVE 1
E

drv

drv
bfv

bfv
F/B - FROM BELOW

bfv

bfv
FFL - FINISH FLOOR LEVEL 2

H/L - HIGH LEVEL


3
To Cooling Tower Water Connection for Connection for To Cooling Tower Water L/L - LOW LEVEL
Recycling Plant Heat Pump cs cs Heat Pump Recycling Plant T/A - TO ABOVE
bfv bfv
(see drawing no. (see drawing no. 4
(See Detail below) (See Detail below) T/B - TO BELOW
6000-109XX-512) bfv bfv
6000-109XX-512)
AP - ACCESS PANEL
5
bfv bfv SU - SET UP
SD - SET DOWN 6
13.045 bfv bfv bfv bfv 13.045

ITS - IMMERSION TEMPERATURE SENSOR 7

PN16

PN16

PN16

PN16
DPS - DIFFERENTIAL PRESSURE SWITCH
8
BFV - BUTERFLY VALVE
F DRV - DOUBLE REGULATING VALVE
9
CS - COMMISSIONING SET
414 Max STR - STRAINER 10
326.15 Normal NRV - NON RETURN VALVE.
CV - CONTROL VALVE
PICV - PRESSURE INDEPENDANT CONTROL VALVE
FMD - FLOW MEASURING DEVICE
SV - SAFETY VALVE
AV - AIR VENT
DC - DRAIN COCK
TP - TEST POINT
HUBT - HOSE UNION BIB TAP
FC - FLEXIBLE COUPLING

G G

COOLING WATER BLEED-OFF RECYCLING UNIT To Water Meter Connection On Water Softener
Controller 24V ac Two Wire Signal
BMS Alarm
02 23-01-17 23-01-17 ISSUED FOR CONSTRUCTION SJN JG
415 Volt 3ph 16A 230V 3A 230V 3A 230V 3A 230V 15A
01 14-04-16 14-04-16 ISSUED FOR APPROVAL SJN JG
Treated Water To Soft 230 230 REV: DATE: CDM-CHK: REVISION: DRN: CHK:
Make-up Tank /24V /24V
WM
CLIENT:
Water Meter
By-pass Double
V/V Check Valve
H
For continuation
refer to drawing no. Outlet Inlet
6000-190XX-530 V/V V/V

Sample PROJECT:
V/V

H
Ro Concentrate Brine/salt
Tank
100 BISHOPSGATE
To Drain
1/2"

Drain
LONDON EC3
Cooling Tower Bleed-off
Collection Tank
Drain

Reverse Osmosis Water Softener Activated Carbon

Cooling Tower Water Recycling Detail

Level 38 Plant

STATUS: I
414 Max
CONSTRUCTION
326.15 Normal
DRAWING TITLE:

MECHANICAL SERVICES
CONDENSER WATER SCHEMATIC
SHEET 2 OF 2
Discipline Project Phase
J MECHANICAL 1 J
Level 6 Plant Drawing Originator Originator's Job No.
MICHAEL J LONSDALE ME2424
Checked By Checked Date Drawn By Drawn Date
JN 14/04/2016 SJN 16-02-2016
Approved By Approval Date Scale Bldg Grid Reference
For continuation refer to Drawing JG 14/04/2016 1:50 @ A0 -
Number. 6000-109XX-503 Drawing No. Revision

6000-109XX-504 02
1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
North Riser South Riser
drv
Core 1 For continuation refer to Drawing Core 1 drv
(7-21) Number. 6000-109xx-507 (7-21)
COMPUTER AIDED DRAWING - AVOID MANUAL MODIFICATION

THIS DRAWING MUST NOT BE SCALED.


ALL DIMENSIONS TO BE CHECKED ON SITE.

A REFERENCE DRAWINGS. A
DRAWING No. TITLE. REV.

KEY PLAN
2
1 B
B
N

15 SHP

NOTES:

C C

For continuation refer to Drawing


West

Number. 6000-109XX-xxx
D D

East

For continuation refer to Drawing


Number. 6000-109XX-XXX
0

1
E

F 9

10

G G

02 13.01.17 ISSUED FOR CONSTRUCTION PS JD

01 14-04-16 14/04/16 ISSUED FOR APPROVAL SJN JG

REV: DATE: CDM-CHK: REVISION: DRN: CHK:

CLIENT:

PROJECT:

H
100 BISHOPSGATE
LONDON EC3

I FS

STATUS: I
CONSTRUCTION
DRAWING TITLE:

MECHANICAL SERVICES
CHW Schematic
sheet 1 of 4
Discipline Project Phase
J MECHANICAL 1 J
Drawing Originator Originator's Job No.
MICHAEL J LONSDALE ME2758
Checked By Checked Date Drawn By Drawn Date
JN --/--/2016 SJN 15/02/2016
Approved By Approval Date Scale Bldg Grid Reference
-- --/--/2016 NTS @ A0 -

Drawing No. Revision

6000-109XX-505 02
1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

COMPUTER AIDED DRAWING - AVOID MANUAL MODIFICATION

THIS DRAWING MUST NOT BE SCALED.


ALL DIMENSIONS TO BE CHECKED ON SITE.

A REFERENCE DRAWINGS. A
DRAWING No. TITLE. REV.
M-155XX-511 CHW SCHEMATIC -SHEET 2 0F 4 06
M-X50XX-400 MECHANICAL SERVICES SYMBOLS 06
LEGEND
For continuation refer to Drawing
Number. 6000-109XX-507

KEY PLAN
2
1 B
B
N

15 SHP

19.8 9.9
NOTES:
fmd tp
PN16 bfv bfv
Future Tenant

drv
tp
PN16 bfv bfv Connections

9.9
9.9
av av
C C
fmd tp fmd tp
bfv bfv
Chilled Water flow & return
from Tower Plantroom (North) AHU AHU

bfv

bfv
to serve Podium AHUs & tp tp tp 06/05 tp tp tp 06/06
bfv str bfv str
future Tenant connections.
picv picv
hudc hudc

drv drv
Level 6 Plant
3.29 2.23

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail

Level 5
3.31 2.21
6.60 4.44
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail

Level 4
D 3.35 iv iv 2.20 D
iv iv
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail
9.95 6.64 ABBREVIATIONS:-
Level 3
6.50 4.26
CHW.F - CHILLED WATER FLOW
Refer to Riser Branch Refer to Riser Branch
CHW.R - CHILLED WATER RETURN
Connection Detail Connection Detail LTHW.F - LOW TEMPERATURE HOT WATER FLOW
16.45 10.90
Level 2 LTHW.R - LOW TEMPERATURE HOT WATER RETURN
6.59 4.30
CW.F - CONDENSER WATER FLOW
Refer to Riser Branch Refer to Riser Branch CW.R - CONDENSER WATER RETURN
Connection Detail Connection Detail
UF.HTG.F - UNDER FLOOR HEATING FLOW
Level 1
UF.HTG.R - UNDER FLOOR HEATING RETURN
F&R - FLOW AND RETURN 0
Level G
F/A - FROM ABOVE
av 1
E F/B - FROM BELOW
tp
bfv
FFL - FINISH FLOOR LEVEL
2
tp
H/L - HIGH LEVEL
CC fmd
picv L/L - LOW LEVEL
-01/01 tp 3
bfv T/A - TO ABOVE
picv
tp
hudc tp tp T/B - TO BELOW
str bfv 4
23.04 15.20 AP - ACCESS PANEL
tp

Level -01 SU - SET UP 5


SD - SET DOWN
6

ITS - IMMERSION TEMPERATURE SENSOR


7
DPS - DIFFERENTIAL PRESSURE SWITCH

BFV - BUTERFLY VALVE 8


0.46
DRV - DOUBLE REGULATING VALVE
F CS - COMMISSIONING SET
For continuation refer to Drawing

STR - STRAINER
Number. 6000-109XX-505

NRV - NON RETURN VALVE. 10

CV - CONTROL VALVE
PICV - PRESSURE INDEPENDANT CONTROL VALVE
Level -02 FMD - FLOW MEASURING DEVICE
SV - SAFETY VALVE
av
13 C 8 C - AIR VENT
AV
tp
bfv DC - DRAIN COCK
PN16 PN16
CC tp fmd TP - TEST POINT
-03/01 tp HUBT - HOSE UNION BIB TAP
bfv
picv picv -
17.28 tp FC FLEXIBLE COUPLING
bfv tp tp
hudc str bfv 1.62 2.08
PN16 bfv tp

G bfv
G

PN16 bfv

drv drv

iv iv iv iv
Refer to the detail for Refer to the detail for
the riser dirt pockets the riser dirt pockets
02 23-01-17 23-01-17 ISSUED FOR CONSTRUCTION SJN JG
West Riser East Riser
01 14-04-16 14-04-16 ISSUED FOR APPROVAL SJN JG
Core 2 Core 2
REV: DATE: CDM-CHK: REVISION: DRN: CHK:

CLIENT:

PROJECT:

H
100 BISHOPSGATE
LONDON EC3

Level -03

STATUS: I
CONSTRUCTION
DRAWING TITLE:

MECHANICAL SERVICES
CHW SCHEMATIC SHEET 2 OF 4

Discipline Project Phase


J MECHANICAL 1 J
Drawing Originator Originator's Job No.
MICHAEL J LONSDALE ME2424
Checked By Checked Date Drawn By Drawn Date
JN 14/04/2016 SJN 06/04/16
Approved By Approval Date Scale Bldg Grid Reference
JG 14/04/2016 1:50 @ A0 -

Drawing No. Revision

6000-109XX-506 02
1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

COMPUTER AIDED DRAWING - AVOID MANUAL MODIFICATION

THIS DRAWING MUST NOT BE SCALED.


ALL DIMENSIONS TO BE CHECKED ON SITE.

A REFERENCE DRAWINGS. A
DRAWING No. TITLE. REV.
M-155XX-512 CHW SCHEMATIC SHEET 3 OF 4 06
M-X50XX-400 MECHANICAL SERVICES SYMBOLS 06
LEGEND

For continuation refer to Drawing


Number. 6000-109XX-508

KEY PLAN
CU av Lift Motor Room Cooling Units av CU
21/01
fmd fmd
21/02 2
tp tp
iv iv
1 B
B
tp
picv N

SHP

iv

iv
92.63 3.29 tp tp
iv iv
tp tp tp 3.70 97.90
drv
picv picv
15
iv
Refer to Riser Branch Refer to Riser Branch
iv str
Connection Detail 0.93 tp tp
iv
Connection Detail
6000-109XX-XXX 6000-109XX-XXX
Level 21 fmd
3.29 3.67
NOTES:
Refer to Riser Branch iv 1.86 Refer to Riser Branch
Connection Detail 5.56 Connection Detail
6000-109XX-XXX 6000-109XX-XXX
iv
Level 20 DPT
3.36 iv 3.73
DPT
Refer to Riser Branch Refer to Riser Branch
iv
Connection Detail 6.58 Connection Detail
6000-109XX-XXX 6000-109XX-XXX
Level 19
C 3.43 3.79 C
Refer to Riser Branch
12.96 Refer to Riser Branch
Connection Detail Connection Detail
6000-109XX-XXX 6000-109XX-XXX
13.36
Level 18
3.50 3.86

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail
6000-109XX-XXX 6000-109XX-XXX
Level 17
3.57 3.92

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail
6000-109XX-XXX 6000-109XX-XXX
Level 16
3.64 3.98

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail
6000-109XX-XXX 6000-109XX-XXX
D Level 15 D
3.71 4.04

Refer to Riser Branch Refer to Riser Branch ABBREVIATIONS:-


Connection Detail Connection Detail
6000-109XX-XXX 6000-109XX-XXX CHW.F - CHILLED WATER FLOW
iv iv
Level 14 CHW.R - CHILLED WATER RETURN
3.78 4.10
DPT DPT LTHW.F - LOW TEMPERATURE HOT WATER FLOW
Refer to Riser Branch Refer to Riser Branch
iv iv LTHW.R - LOW TEMPERATURE HOT WATER RETURN
Connection Detail Connection Detail
6000-109XX-XXX 6000-109XX-XXX
CW.F - CONDENSER WATER FLOW
Level 13
3.83 4.14 CW.R - CONDENSER WATER RETURN
Refer to Riser Branch Refer to Riser Branch UF.HTG.F - UNDER FLOOR HEATING FLOW
Connection Detail Connection Detail
6000-109XX-XXX 6000-109XX-XXX
UF.HTG.R - UNDER FLOOR HEATING RETURN
Level 12 F&R - FLOW AND RETURN
3.87 4.18
F/A - FROM ABOVE 0
Refer to Riser Branch Refer to Riser Branch F/B - FROM BELOW
Connection Detail Connection Detail

E Level 11 6000-109XX-XXX
39.25 44.97
6000-109XX-XXX FFL - FINISH FLOOR LEVEL 1

3.92 4.22 H/L - HIGH LEVEL


L/L - LOW LEVEL 2
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail T/A - TO ABOVE
6000-109XX-XXX 6000-109XX-XXX 3
Level 10 T/B - TO BELOW
3.97 4.26
AP - ACCESS PANEL
4
Refer to Riser Branch Refer to Riser Branch SU - SET UP
Connection Detail Connection Detail
6000-109XX-XXX 6000-109XX-XXX SD - SET DOWN 5
Level 9
4.02 4.29
ITS - IMMERSION TEMPERATURE SENSOR 6
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail DPS - DIFFERENTIAL PRESSURE SWITCH
6000-109XX-XXX 6000-109XX-XXX 7
Level 8 BFV - BUTERFLY VALVE
4.07 4.33
DRV - DOUBLE REGULATING VALVE
8
Refer to Riser Branch Refer to Riser Branch 54.66 CS - COMMISSIONING SET
Connection Detail Differential Pressure Connection Detail -
F 6000-109XX-XXX 6000-109XX-XXX drv STR STRAINER 9
Sensor -
Level 7 NRV NON RETURN VALVE.
54.66 97.90 CV - CONTROL VALVE 10
iv bfv
PN25 PN25 bfv PICV - PRESSURE INDEPENDANT CONTROL VALVE
bfv FMD - FLOW MEASURING DEVICE
DPT bfv fmd
iv iv
bfv bfv SV - SAFETY VALVE
bfv
bfv AV - AIR VENT
bfv
92.63 drv
fmd DPT Dirt DC - DRAIN COCK
iv Seperator
TP - TEST POINT
bfv HUBT - HOSE UNION BIB TAP
iv drv iv
FC - FLEXIBLE COUPLING
PN25 PN25 DS
fmd
bfv bfv bfv
06/02
77.19
Buffer PU bfv 55.23 62.07 bfv bfv Buffer PU
sv Spill type Vessel Dirt bfv sv Spill type Vessel
Vessel 06/10 Vessel 06/11
G Seperator bfv bfv
G

bfv

bfv
bfv bfv
dcv sc dcv sc

bfv

bfv

bfv

bfv
bfv bfv hudc hudc
bfv

bfv

tp

tp
fmd

fmd
drv

drv
flex

flex
lsv lsv
DS
bfv

bfv

bfv

bfv

(n/o) tp tp (n/o)

str

str
tp

tp
lsv 06/01 lsv
tp

tp
fmd

fmd
drv

drv

(n/o) Press. (n/o) Press.

picv

picv
Pressurisation Pressurisation

str

str
tp

tp
Unit drv Unit
tp iv iv
str

str
tp

tp

tp
System System
nrv

tp

tp
tp

tp
tp
picv

Trapped Trapped
str

str
tp

tp

picv

81.58

fc

fc

fc

fc
iv Drain tp tp Drain iv
DP

picv

picv
nrv
tp

tp
tp

tp
tp

PN25 PN25 PN25 PN25


iv 06/02
fc

fc

fc

fc

tp iv S4 S1 S4 S1
DPT tp DP 02 23-01-17 23-01-17 SJN JG
picv

ISSUED FOR CONSTRUCTION

tp

tp
tp tp iv
picv

iv bfv str fc fc nrv bfv


06/01

fmd

fmd
iv
S4 S1 S4 S1 01 14-04-16 14-04-16 ISSUED FOR APPROVAL SJN JG
Heat Heat
Dosing
tp

tp tp iv Ex. Ex.
tp

bfv str fc fc nrv bfv iv hudc REV: DATE: CDM-CHK: REVISION: DRN: CHK:
HEX HEX
fmd

fmd

Pot
Heat Heat 06/03 06/04 tp tp
Dosing bfv str fc fc nrv bfv
CLIENT:
HEX Ex. HEX Ex. hudc tp tp tp tp
Pot DPT fc S3 S2 fc fc S3 S2 fc
06/01 06/02 tp tp iv hudc
bfv str fc fc nrv bfv
H tp
S3 S2
tp tp
S3 S2
tp hudc hudc hudc hudc
TP TP
fc fc fc fc High Rise Heat Exchangers HX/6/2 06/12 06/13
hudc hudc hudc hudc
hudc (2@67%)
TP TP PN16 PN25 PN16 PN25
High Rise Heat Exchangers HX/6/1 06/10 06/11 bfv
(2@67%) av
PN16 PN25 PN16 PN25

bfv
PROJECT:
fmd tp bfv
32.2 bfv
tp
AHU bfv fmd H
100 BISHOPSGATE
bfv

bfv bfv
tp
str
tp tp 06/01 To Podium AHU av Typical Tenant tp
Connections bfv

bfv
16.1
picv
hudc
tp fmd
bfv LONDON EC3
av AHU

bfv
tp tp 06/03 tp tp tp
bfv bfv fmd For continuation refer to Drawing str bfv
fmd
bfv
tp bfv
bfv
tp picv AHU Number. 6000-109XX-506 picv
bfv

hudc
Typical Tenant tp tp tp 06/02 av
16.09 tp tp
bfv str tp str
bfv bfv
Connections
I picv 19.80 tp fmd
fmd hudc bfv
bfv 32.2
32.2
AHU

bfv
bfv tp tp
bfv str bfv 06/04 tp tp
str
tp
bfv
113.78
Level 6 16.1 16.09 Level 6
bfv bfv 52.0 picv bfv bfv
Plant hudc Plant

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail STATUS: I

Level 5
12 C 6 C 3.98 6000-109XX-XXX 6000-109XX-XXX
4.32
Level 5
CONSTRUCTION
129.19 Refer to Riser Branch Refer to Riser Branch DRAWING TITLE:
Connection Detail Connection Detail
6000-109XX-XXX 6000-109XX-XXX MECHANICAL SERVICES
CHW SCHEMATIC SHEET 3 OF 4
North Riser South Riser
Core 1 Core 1 Discipline Project Phase
J MECHANICAL 1 J
Drawing Originator Originator's Job No.
MICHAEL J LONSDALE ME2758
Checked By Checked Date Drawn By Drawn Date
For continuation refer to Drawing JN 14/04/2016 SJN 06/04/2016
Approved By Approval Date Scale Bldg Grid Reference
Number. 6000-109XX-505 JG 14/04/2016 1:XX @ A0 -

Drawing No. Revision

6000-109XX-507 02
1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

COMPUTER AIDED DRAWING - AVOID MANUAL MODIFICATION

THIS DRAWING MUST NOT BE SCALED.


0.51 ALL DIMENSIONS TO BE CHECKED ON SITE.
UPS Transformer av
tp 2.43
Cooling Unit bfv
av
Landlords
A tp fmd
Future Tenant Transformer Cooling REFERENCE DRAWINGS. A
iv tp
Connections bfv fmd tp Unit DRAWING No. TITLE. REV.
tp bfv
CU M-155XX-513 CHW SCHEMATIC -SHEET 4 0F 4 06
picv tp M-X50XX-400 MECHANICAL SERVICES SYMBOLS 06
38/05

iv
tp tp tp picv LEGEND

bfv
str iv
tp tp tp tp tp
picv tp tp bfv str
hudc
picv
Duty / CU
Standby 38/04
35.73 0.51 Duty /
av UPS Transformer Standby
av
Cooling Unit
tp fmd
bfv tp fmd 2.43 Landlords
iv
tp av Transformer Cooling
picv bfv
CU Unit KEY PLAN

iv
38/06 tp tp tp fmd tp
str iv bfv
tp tp tp
str
tp
bfv 2
picv
picv
1 B

bfv
B hudc
bfv
tp
str
tp tp
AHU 2.43
38/01 picv N
Tenant Transformer
0.51
SHP
av hudc
Cooling Unit
37.30
tp fmd
CU 15
bfv 38/03
CU 2.43

bfv
tp
bfv 38/01 tp tp
str
tp
bfv
Future Tenant picv
Connections tp hudc NOTES:
bfv

Duty /
av 1.57 Standby
LMR Cooling Unit tp fmd 2.43
iv
Tenant Transformer
tp av
Cooling Unit
bfv

picv
tp fmd
tp tp tp tp bfv
str iv
C CU C
picv

bfv
38/02 tp tp
str
tp
bfv
CU Typical Tenant
38/07 picv Connections
hudc

fmd

2.94 2.94
bfv bfv
tp tp
35.73
tp
bfv av

bfv

bfv
bfv fmd
Typical Tenant tp fmd fmd fmd
Connections bfv bfv bfv
tp
bfv
av tp
Goods LMR 0.43
drv

bfv
bfv picv
Cooling Unit tp fmd
iv tp tp tp tp tp
str bfv bfv bfv
tp fmd bfv picv
picv iv bfv
tp tp tp tp bfv bfv
AHU
str iv 1.57
D 38/02 D
picv str av
tp tp bfv
CU LMR Cooling Unit tp fmd Active DA
39/01 iv ABBREVIATIONS:-
bfv
De-aerator 06/02
tp CHW.F - CHILLED WATER FLOW
DA Active bfv
picv CHW.R - CHILLED WATER RETURN

iv
06/01 De-aerator
tp tp tp tp tp
bfv str iv LTHW.F - LOW TEMPERATURE HOT WATER FLOW
picv LTHW.R - LOW TEMPERATURE HOT WATER RETURN
drv 39.73
CU CW.F - CONDENSER WATER FLOW
38/08 fmd
PN16 PN16 bfv CW.R - CONDENSER WATER RETURN
UF.HTG.F - UNDER FLOOR HEATING FLOW

bfv
tp tp
bfv str bfv
UF.HTG.R - UNDER FLOOR HEATING RETURN
40.67 F&R - FLOW AND RETURN
Level 38/39 0
Plant F/A - FROM ABOVE
3.16 3.50
F/B - FROM BELOW
E PN16 PN16 1
Refer to Riser Branch iv Refer to Riser Branch FFL - FINISH FLOOR LEVEL
Connection Detail Connection Detail
iv H/L - HIGH LEVEL
M-157XX-603/05 M-157XX-603/05 2
Level 37 DPT L/L - LOW LEVEL
3.17 3.52
DPT iv T/A - TO ABOVE 3
Refer to Riser Branch iv Refer to Riser Branch
Connection Detail
43.23 Connection Detail T/B - TO BELOW
M-157XX-603/05 M-157XX-603/05
47.0 4
AP - ACCESS PANEL
Level 36
3.18 3.54 SU - SET UP
46.75
5
Refer to Riser Branch Refer to Riser Branch SD - SET DOWN
Connection Detail Connection Detail
M-157XX-603/05 50.18 M-157XX-603/05 6
50.29
Level 35 ITS - IMMERSION TEMPERATURE SENSOR
3.19 3.56
DPS - DIFFERENTIAL PRESSURE SWITCH 7
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail BFV - BUTERFLY VALVE
M-157XX-603/05 M-157XX-603/05 8
DRV - DOUBLE REGULATING VALVE
Level 34
3.20 3.57 CS - COMMISSIONING SET
F - 9
Refer to Riser Branch Refer to Riser Branch STR STRAINER
Connection Detail Connection Detail
NRV - NON RETURN VALVE.
M-157XX-603/05 M-157XX-603/05 10
Level 33 CV - CONTROL VALVE
3.22 3.59
PICV - PRESSURE INDEPENDANT CONTROL VALVE
Refer to Riser Branch Refer to Riser Branch - FLOW MEASURING DEVICE
Connection Detail Connection Detail
FMD
M-157XX-603/05 M-157XX-603/05 SV - SAFETY VALVE
Level 32 -
3.23 3.61 AV AIR VENT
DC - DRAIN COCK
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail TP - TEST POINT
M-157XX-603/05 M-157XX-603/05
Level 31 HUBT - HOSE UNION BIB TAP
3.24 3.63
FC - FLEXIBLE COUPLING
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail
M-157XX-603/05 M-157XX-603/05
Level 30
G 3.25 3.64 G
iv
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail
iv M-157XX-603/05
M-157XX-603/05
Level 29 DPT
3.27 iv
3.66
DPT
Refer to Riser Branch iv Refer to Riser Branch
Connection Detail Connection Detail
M-157XX-603/05 M-157XX-603/05
Level 28
3.28 3.68

Refer to Riser Branch Refer to Riser Branch 02 23-01-17 23-01-17 SJN JG


ISSUED FOR CONSTRUCTION
Connection Detail Connection Detail
M-157XX-603/05 M-157XX-603/05
01 14-04-16 14-04-16 ISSUED FOR APPROVAL SJN JG
Level 27
3.29 3.70 REV: DATE: CDM-CHK: REVISION: DRN: CHK:

Refer to Riser Branch Refer to Riser Branch


CLIENT:
Connection Detail Connection Detail
M-157XX-603/05 M-157XX-603/05

H Level 26
3.30 3.72

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail
M-157XX-603/05 M-157XX-603/05
Level 25
3.32 3.73 PROJECT:

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail H
Level 24
M-157XX-603/05 M-157XX-603/05

3.75
100 BISHOPSGATE
3.33

Refer to Riser Branch Refer to Riser Branch


LONDON EC3
Connection Detail Connection Detail
M-157XX-603/05 M-157XX-603/05
Level 23
3.34 3.77

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail
M-157XX-603/05 92.63 97.90 M-157XX-603/05
I Level 22 iv iv

DPT DPT
iv iv

STATUS: I
North Riser South Riser CONSTRUCTION
Core 1 Core 1
DRAWING TITLE:

MECHANICAL SERVICES
For continuation refer to Drawing CHW SCHEMATIC -SHEET 4 OF 4
Number. 6000-109XX-507
Discipline Project Phase
J MECHANICAL 1 J
Drawing Originator Originator's Job No.
MICHAEL J LONSDALE ME2758
Checked By Checked Date Drawn By Drawn Date
JN 14/04/2016 SJN 06/04/2016
Approved By Approval Date Scale Bldg Grid Reference
JG 14/04/2016 1:XX @ A0 -

Drawing No. Revision

6000-109XX-508 02
1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

bfv

COMPUTER AIDED DRAWING - AVOID MANUAL MODIFICATION


bfv
bfv
For continuation refer to Drawing bfv
iv iv
14.77 Number. 6000-109XX-511 iv
THIS DRAWING MUST NOT BE SCALED.
72.76 14.87 ALL DIMENSIONS TO BE CHECKED ON SITE.
102.73
fmd fmd DPT
bfv bfv bfv bfv bfv bfv
25.00 REFERENCE DRAWINGS.
A bfv bfv iv A
Dirt drv iv
Dirt bfv
DRAWING No. TITLE. REV.
iv
Seperator DS Seperator DA M-156XX-500 LTHW SCHEMATIC SHEET 1 OF 4 08
iv PN25

bfv
DPT iv 06/05
iv drv 06/06 bfv M-X50XX-400 MECHANICAL SERVICES SYMBOLS 06
iv
LEGEND
iv PN25
iv 14.18
bfv bfv
bfv bfv DS bfv 72.71
bfv bfv
06/06
Active DA 39.18 bfv
5.26 bfv PN25 PN25
06/03 bfv
DA Active De-aerator iv Active
fmd
06/05 De-aerator De-aerator
PN25 PN25 bfv bfv fmd bfv
tp tp bfv
bfv bfv bfv str
bfv iv
bfv
Dirt

47.47 13.91 5.02


Seperator DS bfv bfv
fmd 5.98 KEY PLAN
06/03
fmd
iv
2
Dirt DS 5.98 1 B
B bfv
bfv
tp tp Seperator
str bfv 06/04 PU Buffer
iv Spill type
Vessel N
bfv tp tp 06/33 sv
SHP
Vessel

bfv bfv bfv bfv sc dcv 15


bfv
drv
12.0 hudc 9.96 9.96

flex
lsv
DA (n/o)
bfv bfv bfv bfv
bfv lsv
Typical Tenant 06/04 Press. (n/o)
PU Buffer Pressurisation
Connections 5.94 9.9 Vessel Spill type 5.02 Unit
06/30 Vessel sv 8.36 5.26 8.77 System drv bfv bfv bfv drv bfv bfv bfv
Active
Trapped tp tp tp tp
NOTES:
sc dcv De-aerator Drain
PU Buffer 9.9 5.94 8.36 str sv str str sv str
Vessel Spill type hudc 5.02 8.77 5.26
06/31 Vessel sv
tp fmd tp tp fmd tp

flex
lsv
bfv bfv bfv bfv bfv bfv bfv bfv picv picv
(n/o)
sc dcv bfv bfv bfv bfv lsv
Press. tp tp
(n/o)
hudc Pressurisation Unit
PU Buffer
Spill type drv bfv bfv bfv drv bfv bfv bfv fc fc fc fc
drv bfv bfv bfv drv bfv bfv bfv Vessel
drv bfv bfv bfv drv bfv bfv bfv System 06/32 Vessel sv
flex

lsv
tp tp tp tp tp tp tp tp tp tp
(n/o) bfv nrv fc fc str bfv
lsv tp tp tp tp Trapped
Drain sc dcv str str
Immersion str str
S4 S1 S4 S1
Press. (n/o) str str str str
C Pressurisation Unit str str str str sv hudc Temperature C
sv sv sv tp tp
System fmd tp sv sv
tp tp
fmd tp tp Sensor tp fmd fmd

flex
tp fmd tp fmd tp tp lsv tp tp Heat Heat
Trapped fmd picv fmd bfv nrv fc fc str bfv
picv picv picv picv (n/o)
Drain lsv picv Ex. Ex.
tp tp tp tp tp Press. (n/o) tp
nrv picv Pressurisation tp picv tp
fc fc Unit sv sv hudc
fc fc fc fc fc fc
System fc fc fc fc TP TP tp tp tp tp
iv tp tp tp tp fc S3 S2 fc fc S3 S2 fc
bfv nrv fc fc str bfv Trapped 06/36 06/37
iv S4 S1 S4 S1 S4 S1 S4 S1 nrv Drain nrv
S4 S1 S4 S1 hudc hudc hudc hudc
Mid Rise Heat Exchangers

For continuation refer to Drawing


iv

fmd
iv fmd fmd fmd fmd iv
bfv nrv
tp
fc fc
tp
str bfv Heat Heat tp tp Heat Heat DP fmd fmd (2@67%)
bfv nrv fc fc str bfv
06/05 Heat Heat iv

Number. 6000-109XX-510
Dosing Ex. Ex. Ex. Ex. iv PN16 PN25 PN16 PN25
hudc Ex. Immersion Ex.
Pot hudc iv iv
Temperature HEX HEX
tp tp tp tp tp tp TP TP tp tp tp tp tp tp tp tp tp tp
DP
bfv nrv fc fc str bfv fc S3 S2 fc fc S3 S2 fc fc S3 S2 fc fc S3 S2 fc
bfv nrv fc fc str bfv fc S3 S2 fc Sensor fc S3 S2 fc
06/11 06/12
nrv 06/30 06/31 Dosing Dosing
06/03 hudc hudc
hudc hudc hudc hudc hudc hudc hudc hudc Pot hudc hudc hudc hudc Pot 33.53
hudc iv
TP TP Mid Rise Heat Exchangers Low Rise Heat Exchangers Low Rise Heat Exchangers
tp tp DP
06/32 06/33 (2@67%) iv (2@100%) bfv nrv fc fc str bfv (2@100%)
06/06
PN16 PN25 PN16 PN25 PN16 PN25 PN16 PN25 PN16 PN25 PN16 PN25
iv
hudc
0.41 DP
D HEX HEX HEX HEX TP TP HEX HEX D
Dosing 06/04 21.12
06/05 06/06 hudc 06/07 06/08 06/34 06/35 06/09 06/10 21.53
Pot
av
fmd tp
iv

AHU ABBREVIATIONS:-
8.36 8.77
iv

iv
tp
str
tp tp 06/07
tp tp
CHW.F - CHILLED WATER FLOW
picv av av av
hudc tp fmd fmd tp tp fmd bfv bfv CHW.R - CHILLED WATER RETURN
bfv bfv iv
drv LTHW.F - LOW TEMPERATURE HOT WATER FLOW
tp
picv
25.90

bfv

bfv
LTHW.R - LOW TEMPERATURE HOT WATER RETURN

iv
tp tp tp tp tp tp tp tp tp
tp str bfv bfv str str iv
Typical Tenant CW.F - CONDENSER WATER FLOW
picv picv picv
hudc hudc hudc Connections CW.R - CONDENSER WATER RETURN
21.12 av av
AHU AHU AHU 0.41 12
tp fmd fmd tp Differential Differential UF.HTG.F - UNDER FLOOR HEATING FLOW
bfv bfv
Pressure Pressure 06/03 10.56 10.56 06/04 06/08 0
tp
picv Sensor Sensor 3.24 3.85 UF.HTG.R - UNDER FLOOR HEATING RETURN
bfv

bfv

tp tp
str
tp tp
str
tp tp F&R - FLOW AND RETURN
bfv bfv tp 1
E F/A - FROM ABOVE
picv picv PN16 bfv
hudc hudc 4.51 F/B - FROM BELOW 2
AHU AHU PN16 cs
10.56 10.56 FFL - FINISH FLOOR LEVEL
06/01 06/02 bfv
bfv PN16 bfv
H/L - HIGH LEVEL 3
bfv bfv
bfv bfv L/L - LOW LEVEL
0.611 5.53 0.749 PN16 cs
4
Level 6 bfv bfv T/A - TO ABOVE
Plant bfv bfv bfv bfv
T/B - TO BELOW
PN16 PN16 PN16 PN16 5
AP - ACCESS PANEL
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail SU - SET UP
3.55 4.38 6
Level 5 SD - SET DOWN

0.611 0.749 7
ITS - IMMERSION TEMPERATURE SENSOR
Refer to Riser Branch 2.60 3.24 Refer to Riser Branch
Connection Detail Connection Detail DPS - DIFFERENTIAL PRESSURE SWITCH 8
Level 4
BFV - BUTERFLY VALVE
F Refer to Riser Branch 9
Connection Detail Refer to Riser Branch DRV - DOUBLE REGULATING VALVE
Connection Detail
0.611 iv iv 0.749 CS - COMMISSIONING SET
10
Level 3 STR - STRAINER
DPS DPS
0.028 0.04 NRV - NON RETURN VALVE.
Refer to Riser Branch Refer to Riser Branch
iv iv
Connection Detail Connection Detail CV - CONTROL VALVE
0.601 2.23 0.762
Level 2 1.78 PICV - PRESSURE INDEPENDANT CONTROL VALVE
FMD - FLOW MEASURING DEVICE
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail SV - SAFETY VALVE
0.91 bfv
flushing by-pass bfv 1.15 -
0.068 iv iv iv iv AV AIR VENT
Level 1
DC - DRAIN COCK
0.02 TP - TEST POINT
FCU FCU North Riser Core 1 South Riser
0M/02 0M/01 0.02 HUBT - HOSE UNION BIB TAP
0.212
Level M FC - FLEXIBLE COUPLING

G PICV on bypass 0.232 FCU G


iv 00/01 0.084 0.056 0.128 0.108 0.08

Level 00
DPT

iv PICV on bypass
30.02

iv
0.04
DPS

iv 02 23-01-17 23-01-17 ISSUED FOR CONSTRUCTION SJN JG


FCU
-01/06 0.02 0.04 0.06 01 14-04-16 14-04-16 ISSUED FOR APPROVAL SJN JG

Level -01 REV: DATE: CDM-CHK: REVISION: DRN: CHK:

10.418 PICV on bypass CLIENT:


0.088 FCU PICV on bypass
-02/03 FCU FCU FCU FCU FCU FCU FCU
H -01/07 -01/06 -01/05 -01/04 -01/03 -01/02 -01/01

43.17 1.915
Differential Pressure 0.292
Sensor
Level -02
drv
To serve Entrance Lobby underfloor and fmd PROJECT:
DA Active door heating systems FCU FCU Active DA
bfv PICV on bypass iv iv drv bfv iv
-03/07 De-aerator For continuation refer to -02/04 -02/02 De-aerator -03/08
bfv
fmd
Drawing Number. 6000-109XX-513 bfv H
iv 25.90
DPT
bfv
iv iv
34.6
iv
DPT
50.03
iv
DPS
bfv DPT
100 BISHOPSGATE
iv iv
DPT
PN16
iv iv iv
bfv To serve Changing Area underfloor bfv
iv iv

PN16 bfv bfv


fmd
iv iv
LONDON EC3
iv heating systems PN25 PN25
fmd bfv bfv fmd
bfv bfv bfv For continuation refer to bfv bfv
PN16 Dirt
PN25 PN25 17.35 Drawing Number. 6000-109XX-513
fmd tp tp PN16 Seperator DS bfv
Dirt tp tp 15.55 tp tp
12 -03/10 bfv str bfv
Seperator iv
bfv bfv bfv
bfv tp tp av av
drv str bfv drv fmd fmd drv
iv tp tp bfv bfv
DS bfv bfv iv iv
bfv 17.35
I -03/09 drv
iv iv AHU 20.11 20.11
bfv

bfv
28.92 Typical Tenant tp tp tp -03/02 tp tp tp
PU Buffer 28.92 bfv str str bfv PU Buffer
Vessel Spill type Connections Tenant Vessel Spill type 33.52 33.52
-03/30 Vessel sv 12 picv picv -03/31 Vessel sv
hudc hudc 19.05 Connections
Refer to detail for sc dcv bfv bfv bfv bfv
15.55 3.136 sc dcv bfv bfv bfv bfv
AHU Refer to
Riser dirt pockets hudc hudc
drv bfv bfv bfv drv bfv bfv bfv -03/01 av drv bfv bfv bfv drv bfv bfv bfv detail for
AHU
flex

flex
lsv lsv Riser dirt
tp fmd
(n/o)
lsv
tp tp tp tp
av bfv
-03/06
(n/o)
lsv
tp tp tp tp
pockets
STATUS: I
Pressurisation
Press.
Unit
(n/o) str sv str str sv
fmd
str bfv
fmd tp
AHU bfv
av
tp fmd
bfv
Pressurisation
Press.
Unit
(n/o) str sv str str sv str CONSTRUCTION
fmd fmd tp fmd tp
System tp tp tp
tp
-03/04 tp tp
str
tp
bfv
System
tp tp
bfv

Trapped picv tp tp tp Trapped picv picv DRAWING TITLE:


picv tp bfv str picv bfv tp
Drain tp tp tp Drain
nrv tp
tp picv
picv
hudc str bfv nrv
tp picv tp
MECHANICAL SERVICES
8.79
fc

fc

fc

fc
fc

fc

fc

fc
picv
iv
tp hudc
hudc iv
tp LTHW SCHEMATIC
3.2 AHU iv
iv S4 S1 S4 S1
-03/05
av
tp fmd
iv S4 S1 S4 S1 SHEET 1 OF 4
bfv DPS
iv fmd fmd iv fmd fmd
tp tp drv tp tp Discipline Project Phase
bfv nrv fc fc str bfv Heat Heat AHU bfv nrv fc fc str bfv Heat Heat
J Ex. Ex. tp
iv
Dosing Ex. Ex.
MECHANICAL 1 J
Dosing -03/03 picv bfv
Pot hudc HEX HEX Pot hudc HEX HEX Drawing Originator Originator's Job No.
-03/15 -03/16 tp tp tp tp -03/17 -03/18
tp tp tp tp tp tp tp str bfv
tp tp tp tp tp tp
MICHAEL J LONSDALE ME2758
bfv nrv fc fc str bfv fc S3 S2 fc fc S3 S2 fc bfv nrv fc fc str bfv fc S3 S2 fc fc S3 S2 fc
DP picv
DP Checked By Checked Date Drawn By Drawn Date
-03/07 hudc hudc hudc hudc
hudc -03/08 hudc hudc hudc hudc JN 14/04/2016 SJN 06/02/2016
hudc Heat Exchangers
TP TP hudc Heat Exchangers 10.26 TP TP Approved By Approval Date Scale Bldg Grid Reference
-03/30 -03/31 (2@67%) -03/32 -03/33 (2@67%) JG 14/04/2016 1:XX @ A0 -
Level -03 PN16 PN25 PN16 PN25 PN16 PN25 PN16 PN25
Drawing No. Revision

6000-109XX-509 02
1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

COMPUTER AIDED DRAWING - AVOID MANUAL MODIFICATION

THIS DRAWING MUST NOT BE SCALED.


PN25 ALL DIMENSIONS TO BE CHECKED ON SITE.
PN25
A REFERENCE DRAWINGS. A
DRAWING No. TITLE. REV.
M-156XX-501 LTHW SCHEMATIC SHEET 2 OF 4 08
M-X50XX-400 MECHANICAL SERVICES SYMBOLS 06
LEGEND
25.00

KEY PLAN
2
1 B
B
N

12.00 15 SHP

tp
bfv

Refer to typical Tenant


tp
bfv Connection detail NOTES:

bfv

bfv

C C
13.00 6.5 6.5

av AHU av AHU
fmd tp fmd tp
bfv bfv

bfv tp
tp tp tp
bfv str bfv picv
picv tp
tp tp tp
For continuation refer to Drawing

hudc bfv str


AHU AHU
picv
Number. 6000-109XX-509

06/05 hudc 06/06

D D

ABBREVIATIONS:-
CHW.F - CHILLED WATER FLOW
CHW.R - CHILLED WATER RETURN
LTHW.F - LOW TEMPERATURE HOT WATER FLOW
LTHW.R - LOW TEMPERATURE HOT WATER RETURN
CW.F - CONDENSER WATER FLOW
CW.R - CONDENSER WATER RETURN
UF.HTG.F - UNDER FLOOR HEATING FLOW
3.24 UF.HTG.R - UNDER FLOOR HEATING RETURN
F&R - FLOW AND RETURN
0
F/A - FROM ABOVE
PN16 bfv F/B - FROM BELOW 1
E
bfv FFL - FINISH FLOOR LEVEL
PN16 bfv
H/L - HIGH LEVEL 2
PN16 bfv L/L - LOW LEVEL
cs iv 2.94
bfv T/A - TO ABOVE 3
PN16 bfv
dpcv
T/B - TO BELOW
RAD 4
05/01 iv
AP - ACCESS PANEL
0.78 0.59 Level 6 Plant
SU - SET UP
5
Refer to Riser Branch Refer to Riser Branch SD - SET DOWN
3.85 Connection Detail trv LSV 0.1 0.3 Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
2.35 6
0.79 3.07 0.59 Level 5 ITS - IMMERSION TEMPERATURE SENSOR
DPS - DIFFERENTIAL PRESSURE SWITCH 7
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail -
See dwg. No. 6000-109XX-XXX
BFV BUTERFLY VALVE
See dwg. No. 6000-109XX-XXX RAD 1.76 8
03/01 DRV - DOUBLE REGULATING VALVE
0.66 2.28 0.50 Level 4
CS - COMMISSIONING SET
F 9
Refer to Riser Branch Refer to Riser Branch STR - STRAINER
0.1 0.2 iv
Connection Detail 1.62 trv LSV Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX NRV - NON RETURN VALVE. 10
iv
DPS 0.55 Level 3 CV - CONTROL VALVE
0.71
DPS PICV - PRESSURE INDEPENDANT CONTROL VALVE
Refer to Riser Branch iv Refer to Riser Branch
Connection Detail iv Connection Detail FMD - FLOW MEASURING DEVICE
1.25
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
RAD SV - SAFETY VALVE
01/01 0.7 Level 2 -
AV AIR VENT
Refer to Riser Branch Refer to Riser Branch DC - DRAIN COCK
Connection Detail drv Temperature trv LSV 0.1 Temperature drv Connection Detail
See dwg. No. 6000-109XX-XXX 15mm dia. DRV See dwg. No. 6000-109XX-XXX TP - TEST POINT
Maintenance By-Pass Maintenance By-Pass
0.91 Level 1 HUBT - HOSE UNION BIB TAP
bfv bfv
iv iv iv iv FC - FLEXIBLE COUPLING
hudc drv
hudc
Refer to detail for Refer to detail for
Riser dirt pockets Riser dirt pockets Level M
G G
Core 2 Core 2
West Riser East Riser
Level G

02 23-01-17 23-01-17 ISSUED FOR CONSTRUCTION SJN JG

01 14-04-16 14-04-16 ISSUED FOR APPROVAL SJN JG

REV: DATE: CDM-CHK: REVISION: DRN: CHK:

CLIENT:
Level B1M

PROJECT:

Level B1
H
100 BISHOPSGATE
LONDON EC3

STATUS: I
CONSTRUCTION
DRAWING TITLE:

MECHANICAL SERVICES
LTHW SCHEMATIC
SHEET 2 0F 4
Discipline Project Phase
J MECHANICAL 1 J
Drawing Originator Originator's Job No.
MICHAEL J LONSDALE ME2758
Checked By Checked Date Drawn By Drawn Date
JN 14/04/2016 SJN 06/02/2016
Approved By Approval Date Scale Bldg Grid Reference
JG 14/04/2016 1:XX @ A0 -

Drawing No. Revision

6000-109XX-510 02
1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

For continuation refer to Drawing


Number. 6000-109XX-512 COMPUTER AIDED DRAWING - AVOID MANUAL MODIFICATION

THIS DRAWING MUST NOT BE SCALED.


ALL DIMENSIONS TO BE CHECKED ON SITE.

iv iv
A REFERENCE DRAWINGS. A
DRAWING No. TITLE. REV.
DPT DPT M-156XX-502 LTHW SCHEMATIC SHEET 3 OF 4 08
0.98 iv iv 0.96
M-X50XX-400 MECHANICAL SERVICES SYMBOLS 06
15.18 15.09 LEGEND
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 37 PN16 PN16 PN16 PN16
14.20 14.12
0.97 0.96
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 36 0.97 0.96
13.23 13.16

Refer to Riser Branch


Connection Detail
Refer to Riser Branch
Connection Detail KEY PLAN
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 35 0.97 0.96 2
12.26 12.20 B
B 1
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail
N

SHP
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 34 0.96 0.95
11.29 11.24 15
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 33 0.96 0.95
10.33 10.29

Refer to Riser Branch Refer to Riser Branch


NOTES:
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 32 0.95 0.95
9.37 9.34
iv iv
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 31 0.95 DPT DPT 0.94
iv iv
C C
Refer to Riser Branch 8.42 8.39 Refer to Riser Branch
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 30 0.95 0.94
7.47 7.45

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 29 0.94 0.94
6.52 6.51

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 28 0.94 0.94
5.58 5.57

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 27 0.94 0.93
D 4.64 4.63 D
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 26 0.93 0.93
3.70 3.70
ABBREVIATIONS:-
Refer to Riser Branch Refer to Riser Branch CHW.F - CHILLED WATER FLOW
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX CHW.R - CHILLED WATER RETURN
Level 25 0.93 0.93
2.77 2.77 LTHW.F - LOW TEMPERATURE HOT WATER FLOW
iv iv LTHW.R - LOW TEMPERATURE HOT WATER RETURN
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail CW.F - CONDENSER WATER FLOW
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 24 0.92 DPT DPT 0.92 CW.R - CONDENSER WATER RETURN
iv iv
UF.HTG.F - UNDER FLOOR HEATING FLOW
UF.HTG.R - UNDER FLOOR HEATING RETURN 0
Refer to Riser Branch 1.84 1.84 Refer to Riser Branch
Connection Detail Connection Detail
0.92 See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX 0.92 F&R - FLOW AND RETURN
1
E Level 23 F/A - FROM ABOVE
iv iv
drv
F/B - FROM BELOW
2
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail FFL - FINISH FLOOR LEVEL
DPT See dwg. No. 6000-109XX-XXX drv See dwg. No. 6000-109XX-XXX DPT
iv iv iv iv iv
0.93 H/L - HIGH LEVEL 3
Level 22 0.92 iv
L/L - LOW LEVEL
Refer to detail for Refer to detail for T/A - TO ABOVE 4
Refer to Riser Branch Refer to Riser Branch
Connection Detail
Riser dirt pockets Riser dirt pockets Connection Detail
drv T/B - TO BELOW
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 21 0.92 drv 0.94 AP - ACCESS PANEL 5

SU - SET UP
6
PN25 PN25
Refer to Riser Branch 1.86 1.87 Refer to Riser Branch
PN25 PN25 SD - SET DOWN
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
iv iv 7
Level 20 0.94 0.95
ITS - IMMERSION TEMPERATURE SENSOR
DPT DPT DPS - DIFFERENTIAL PRESSURE SWITCH 8
Refer to Riser Branch Refer to Riser Branch
iv iv
Connection Detail Connection Detail -
BFV BUTERFLY VALVE
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
F Level 19 0.95 0.95 DRV - DOUBLE REGULATING VALVE 9
2.80 2.82
CS - COMMISSIONING SET
- 10
Refer to Riser Branch Refer to Riser Branch STR STRAINER
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX NRV - NON RETURN VALVE.
Level 18 0.95 0.96
3.75 3.77 CV - CONTROL VALVE
PICV - PRESSURE INDEPENDANT CONTROL VALVE
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail FMD - FLOW MEASURING DEVICE
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 17 0.95 0.96 SV - SAFETY VALVE
4.70 4.73 AV - AIR VENT
Refer to Riser Branch Refer to Riser Branch DC - DRAIN COCK
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX TP - TEST POINT
Level 16 0.96 0.96 HUBT - HOSE UNION BIB TAP
5.65 5.69
FC - FLEXIBLE COUPLING
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail
G See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX G
Level 15 0.96 0.97
6.61 6.65

Refer to Riser Branch Refer to Riser Branch


Connection Detail 7.57 7.62 Connection Detail
See dwg. No. 6000-109XX-XXX iv iv See dwg. No. 6000-109XX-XXX
Level 14 0.96 0.97

DPT DPT
Refer to Riser Branch Refer to Riser Branch
iv iv
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 13 0.98 0.99
8.53 8.59 02 23-01-17 23-01-17 ISSUED FOR CONSTRUCTION SJN JG

Refer to Riser Branch Refer to Riser Branch 01 14-04-16 14-04-16 ISSUED FOR APPROVAL SJN JG
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX REV: DATE: CDM-CHK: REVISION: DRN: CHK:
Level 12 1.01 1.01
9.52 9.58 CLIENT:

Refer to Riser Branch Refer to Riser Branch


H Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 11 1.03 1.04
10.52 10.59

Refer to Riser Branch Refer to Riser Branch


Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX PROJECT:
Level 10 1.05 1.06
11.55 11.63
H
Refer to Riser Branch
Connection Detail
Refer to Riser Branch
Connection Detail
100 BISHOPSGATE
Level 9 1.07
See dwg. No. 6000-109XX-XXX

12.60 12.69
See dwg. No. 6000-109XX-XXX
1.08 LONDON EC3
Refer to Riser Branch Refer to Riser Branch
Connection Detail Connection Detail
See dwg. No. 6000-109XX-XXX See dwg. No. 6000-109XX-XXX
Level 8 1.10 1.10
13.68 13.77
Refer to Riser Branch
Connection Detail Refer to Riser Branch
I See dwg. No. 6000-109XX-XXX Connection Detail
See dwg. No. 6000-109XX-XXX
Level 7 PN16 PN16 PN16 PN16
iv iv

DPT DPT
72.76 iv iv
102.72
STATUS: I
14.77 14.87
CONSTRUCTION
DRAWING TITLE:

MECHANICAL SERVICES
Core 1 Core 1 LTHW SCHEMATIC
North Riser South Riser SHEET 3 OF 4
Discipline Project Phase
J MECHANICAL 1 J
Drawing Originator Originator's Job No.
MICHAEL J LONSDALE ME2758
Checked By Checked Date Drawn By Drawn Date
JN 14/04/2016 SJN 06/02/2016
Approved By Approval Date Scale Bldg Grid Reference

For continuation refer to Drawing JG 14/04/2016 1:XX @ A0 -

Number. 6000-109XX-509 Drawing No. Revision

6000-109XX-511 02
1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

COMPUTER AIDED DRAWING - AVOID MANUAL MODIFICATION

Boiler THIS DRAWING MUST NOT BE SCALED.


ALL DIMENSIONS TO BE CHECKED ON SITE.

A REFERENCE DRAWINGS. A
av DRAWING No. TITLE. REV.
tp tp M-156XX-504 LTHW SCHEMATIC SHEET 4 OF 4 08
sv
M-X50XX-400 MECHANICAL SERVICES SYMBOLS 06
hudc LEGEND
doc

9.56 14.34 19.12 23.9 38.26 59.78

tp

str
tp
PP PP
22.12 39/30 39/34
cs fc
bfv bfv bfv bfv bfv bfv
SP SP (Used for flow
bfv bfv KEY PLAN

DP
fmd
fc fc
tp fmd
bfv 39/34 39/35 fm
monitoring)
bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv bfv tp tp Continued on
4.78 4.78 4.78 4.78 4.78
bfv
cs tp hudc 460kW 2

bfv
Condenser Water fc
tp tp tp tp tp tp tp tp tp tp tp
fmd fmd fmd fmd fmd fmd Schematic
bfv str fc fc Heat Pump fc str bfv
bfv nrv fc fc
tp
str
tp
bfv 1 B
B nrv
Flue str Flue str Flue str Flue str Flue str Flue str drv cv mv
picv picv picv picv picv
hudc
tp tp tp tp tp tp tp tp tp tp
Future Boiler N
tp tp tp tp tp tp TP HP 10.76
SHP
13.045 tp
tp
cs 38/20 38/01 tp tp
tp
picv
tp
picv
tp
picv
tp
picv
tp
picv picv
bfv nrv fc fc str bfv
cv 15
av av av av av cs
fmd tp fmd
7.18 fc fc bfv tp
sv Continued on cs
bfv
tp hudc 460kW cs bfv

bfv
tp tp tp tp tp Condenser Water tp tp tp tp tp
bfv str fc fc Heat Pump fc str bfv bfv
Schematic bfv
tp
hudc cv mv
tp tp
hudc hudc hudc hudc hudc hudc drv Connections for Future HWS NOTES:
13.045 TP HP 10.76 fmd
bfv
tp
38/21 38/02

Boiler
B B B B B
39/01
Boiler
39/02
Boiler
39/03
Boiler
39/04
Boiler
39/05
Boiler Typical Boiler Valve/Pipe Connection Detail

B
C 39/06 C

PP PP PP PP PP
39/30 39/31 39/32 39/33 39/34

Boiler Pump ref's

47.85 47.85 47.85 47.85 47.85

Spill type
Buffer PU
sv Vessel
Vessel 39/30

D dcv sc D
hudc
239.23

flex
lsv
(n/o)
lsv
(n/o) Press. ABBREVIATIONS:-
Unit Pressurisation
fmd
System CHW.F - CHILLED WATER FLOW
lsv
Trapped
Drain
CHW.R - CHILLED WATER RETURN
LTHW.F - LOW TEMPERATURE HOT WATER FLOW
bfv
LTHW.R - LOW TEMPERATURE HOT WATER RETURN
CW.F - CONDENSER WATER FLOW
CW.R - CONDENSER WATER RETURN
nrv
tp UF.HTG.F - UNDER FLOOR HEATING FLOW
iv UF.HTG.R - UNDER FLOOR HEATING RETURN
str
239.23 F&R - FLOW AND RETURN 0
iv
tp
fmd F/A - FROM ABOVE
1
E iv
F/B - FROM BELOW
DP
Dosing 39/01 FFL - FINISH FLOOR LEVEL 2
hudc
Pot H/L - HIGH LEVEL
bfv Temporary Pump L/L - LOW LEVEL 3
bfv bfv connection for T/A - TO ABOVE
flushing
T/B - TO BELOW 4

iv AP - ACCESS PANEL
cv 5
bfv SU - SET UP
tp tp
bfv bfv
SD - SET DOWN
tp cv tp 6
bfv bfv

Active ITS - IMMERSION TEMPERATURE SENSOR


7
De-aerator -
tp tp DPS DIFFERENTIAL PRESSURE SWITCH
drv
bfv
DA cs cs cs cs
BFV - BUTERFLY VALVE 8

39/01 DRV - DOUBLE REGULATING VALVE


F iv
Temporary Pump 9
tp tp fmd CS - COMMISSIONING SET
str bfv connection for
STR - STRAINER
bfv bfv
flushing
bfv - 10
bfv bfv NRV NON RETURN VALVE.
fmd cs iv CV - CONTROL VALVE
tp tp
str bfv bfv
258.97 DS PICV - PRESSURE INDEPENDANT CONTROL VALVE
bfv fmd
39/01 FMD - FLOW MEASURING DEVICE
iv
SV - SAFETY VALVE
Dirt -
AV AIR VENT
Seperator
DC - DRAIN COCK
TP - TEST POINT
HUBT - HOSE UNION BIB TAP
FC - FLEXIBLE COUPLING
drv 112.19
bfv 10.11 9.054

12.0
G iv G
SP SP
39/30 39/31 tp
bfv bfv bfv
6.07
103.14
9.11 82.28
drv tp
bfv bfv bfv
114.53
tp tp
bfv nrv fc fc str bfv Typical iv
Tenant
Connections Dirt
PU Buffer 6.07 03 23-01-17 23-01-17 ISSUED FOR CONSTRUCTION SJN JG
tp tp Seperator Vessel Spill type
bfv nrv fc fc str bfv 39/33 Vessel sv
bfv
AHU AHU 02 11-07-16 04-07-16 REVISED AS CLOUDED JPD JG
38/01 DS sc dcv
38/04
144.44 10.11 01 14-04-16 14-04-16 ISSUED FOR APPROVAL SJN JG
iv 39/04 Active hudc
15.18 bfv nrv fc fc
tp
str
tp
bfv De-aerator REV: DATE: CDM-CHK: REVISION: DRN: CHK:
AHU

flex
lsv
(n/o)
38/03 DA lsv CLIENT:
bfv bfv Press. (n/o)
hudc 39/04 Pressurisation Unit hudc
av tp tp 12.0 bfv nrv fc
tp
str
tp
bfv
av tp tp
H System
picv picv
bfv bfv fc Trapped
Drain
av tp tp hudc
tp
bfv
picv
6.1 10.17 iv nrv
Buffer PU Typical
Spill type
sv Vessel
Vessel
39/31 Tenant drv tp bfv
tp iv DP tp PROJECT:
Dirt Connections SP SP 124.19
10.17 6.1 Seperator 39/33 39/32 39/03
dcv sc fmd str iv fmd str
hudc H
tp Active DS tp
Dosing iv tp
100 BISHOPSGATE
flex

lsv
bfv bfv bfv bfv De-aerator 39/03
73.17 fmd str (n/o) Pot

tp drv bfv bfv bfv drv bfv bfv bfv


lsv
(n/o) Press.
Unit Pressurisation DA
iv iv
hudc bfv nrv
tp
fc fc
tp
str bfv drv bfv bfv bfv drv bfv bfv bfv
iv iv
LONDON EC3
System 39/03 av
tp tp tp tp iv fmd tp tp tp tp iv
20.25 tp
iv iv fmd fmd Trapped iv 0.411
str str str str str fmd str str fmd str
Drain tp tp
tp tp
nrv
AHU iv
bfv nrv fc fc str bfv tp tp
tp tp tp bfv tp bfv
iv 38/02 tp tp tp
0.411
picv picv DP str iv picv picv
sv tp sv tp 39/02 hudc sv tp sv tp
iv picv
fc fc fc fc hudc
TP TP fc fc fc fc
I Dosing 20.25
iv 39/32 39/33
Pot
102.53
S4 S1 S4 S1 iv S4 S1 S4 S1
bfv bfv
144.44
iv iv iv iv
fmd fmd tp tp fmd fmd
Heat Heat hudc Heat Heat
bfv str fc fc nrv bfv 102.72
Ex. Ex. Ex. Ex.
72.76
tp tp tp tp tp tp tp tp tp tp STATUS: I
fmd
fc S3 S2 fc fc S3 S2 fc bfv str fc fc nrv bfv
fmd
bfv bfv
fc S3 S2 fc fc S3 S2 fc fmd
CONSTRUCTION
bfv hudc hudc hudc hudc hudc hudc hudc hudc bfv
hudc fmd
bfv bfv bfv
High Rise Heat Exchangers TP TP bfv High Rise Heat Exchangers DRAWING TITLE:
PN16 (2@67%) 39/30 39/31 (2@67%) PN16
bfv bfv PN16 PN16 PN16 PN16 PN16 PN16 PN16 PN16 PN16 PN16 PN16 PN16 bfv bfv
MECHANICAL SERVICES
15.09 LTHW SCHEMATIC
15.18
PN25 HEX HEX HEX HEX PN25 SHEET 4 OF 4
Level 38/39 39/01 39/02 39/03 39/04
Plant Discipline Project Phase
J MECHANICAL 1 J
Drawing Originator Originator's Job No.
MICHAEL J LONSDALE ME2758
Checked By Checked Date Drawn By Drawn Date
JN 14/04/2016 SJN 16-02-2016
For continuation refer to Drawing Approved By Approval Date Scale Bldg Grid Reference

Number. 6000-109XX-511 JG 14/04/2016 1:XX @ A0 -

Drawing No. Revision

6000-109XX-512 03
1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

2.484
PU Manifold 1 Manifold 2 Manifold 3 Manifold 4
-03/32
1.125 tp tp tp tp

iv iv iv iv COMPUTER AIDED DRAWING - AVOID MANUAL MODIFICATION


Refer To CHW Schematic Buffer
Diverting Spill type THIS DRAWING MUST NOT BE SCALED.
Drg. No. 6000-109XX-500 Chilled Water sv Vessel
ALL DIMENSIONS TO BE CHECKED ON SITE.
Valve Vessel dc dc dc dc
For Continuation To Main F&R
tp tp
A System dcv sc REFERENCE DRAWINGS. A
bfv bfv hudc Fill Point DRAWING No. TITLE. REV.
tp M-156XX-503 MECHANICAL SERVICES ENTRANCE LOBBY 04
Number of underfloor UNDERFLOOR LTHW/CHW SCHEMATIC

flex
lsv
bfv (n/o) M-X50XX-400 MECHANICAL SERVICES SYMBOLS 06
Connections for Connections for Connections Connections for lsv nrv heating circuits for each LEGEND
(n/o) Press. manifold to be confirmed
future West future South for future East future North Unit Pressurisation DP
door heaters door heaters door heaters door heaters System iv -03/09 by the underfloor heating
iv dc dc dc dc
Contractor/Manufacturer tp
Trapped iv tp tp tp
bfv Drain

mv

mv

mv
iv iv cs
drv drv drv drv iv Dosing
Level 00

drv

bfv
fmd tp tp tp
Pot KEY PLAN

mv
tp tp tp tp cs cs cs drv
hudc High / Low limit iv iv iv 2
picv picv picv tp tp TP TP tp (n/c) (n/c) (n/c)
picv picv shut off valve

tp
bypass bypass bypass 1 B
B -03/34 -03/35
valve valve valve str 0.471 0.417 tp tp
tp tp tp tp 0.391 iv

str
fmd ITS N
tp tp tp tp tp tp
tp tp
bfv
tp
str
tp
fc fc nrv bfv drv mv
15 SHP

tp
str

fc

fc
tp ITS iv
cs
tp (n/c)
str fmd str fmd str fmd
iv iv
tp tp
tp tp tp picv S4 S1 bfv str fc fc nrv bfv bfv iv iv
Heat
bfv 1.268 0.797 0.38 NOTES:
iv iv iv iv iv iv tp

fmd
tp DPT
1.24 ITS
Ex. ITS
tp tp 2.484
fc S3 S2 fc PN16
PN16 drv
bfv tp tp bfv
hudc hudc
iv iv iv iv
Cooling Heat Diverting 2.484 2.093 Manifold 5 Manifold 6
HEX Valve iv
C Exchanger -03/19
bfv bfv tp tp C

iv iv iv iv

dc dc
2.48 2.48 1.24 Dirt
1.24 DS
DA Seperator
-03/12 -03/11
4.96
Active
De-aerator

6.2

dc dc
Entrance Lobby Schematic tp tp

mv

mv
D D
tp tp drv
cs cs ABBREVIATIONS:-
iv CHW.F - CHILLED WATER FLOW
(n/c) tp tp CHW.R - CHILLED WATER RETURN
bfv
bfv

10.418 0.428
4.218 LTHW.F - LOW TEMPERATURE HOT WATER FLOW
bfv drv mv
LTHW.R - LOW TEMPERATURE HOT WATER RETURN
iv CW.F - CONDENSER WATER FLOW
PN16
Refer To LTHW Schematic (n/c) CW.R - CONDENSER WATER RETURN
Drg. No. For Continuation UF.HTG.F - UNDER FLOOR HEATING FLOW
To Main System PN16 UF.HTG.R - UNDER FLOOR HEATING RETURN
fmd F&R - FLOW AND RETURN
2.484 0.825 0.397
LTHW iv F/A - FROM ABOVE 0

F&R F/B - FROM BELOW


1
E iv iv bfv FFL - FINISH FLOOR LEVEL
Differential H/L - HIGH LEVEL
Pressure Sensor 2
L/L - LOW LEVEL
drv

bfv

fmd
T/A - TO ABOVE
3
T/B - TO BELOW
tp tp AP - ACCESS PANEL
tp

4
0.074 0.074 SU - SET UP
picv str
str

SD - SET DOWN 5

tp tp
West Male Lockers East Male Lockers North Female Lockers
tp

iv iv iv ITS - IMMERSION TEMPERATURE SENSOR 6


fc

fc -
DPS DIFFERENTIAL PRESSURE SWITCH
7
tp BFV - BUTERFLY VALVE
S4 S1 cs cs cs DRV - DOUBLE REGULATING VALVE 8
picv CS - COMMISSIONING SET
Heat
fmd

F STR - STRAINER 9
tp Ex. -
PU tp tp 0.074 NRV NON RETURN VALVE.
PN16 fc S3 S2 fc PN16 0.074 10
-03/33 CV - CONTROL VALVE
PICV - PRESSURE INDEPENDANT CONTROL VALVE
hudc hudc iv
Heating Heat Central Female Lockers FMD - FLOW MEASURING DEVICE
Buffer iv SV - SAFETY VALVE
Spill type Exchanger -
Vessel sv AV AIR VENT
Vessel HEX nrv cs DC - DRAIN COCK
-03/20
sc dcv
iv
DP
-03/10
Central Female Lockers cs
TP - TEST POINT
Fill Point hudc HUBT - HOSE UNION BIB TAP
iv FC - FLEXIBLE COUPLING
iv
flex

lsv
(n/o)
lsv
Press. (n/o)
iv Dosing 0.074
Pressurisation cs
G Unit Pot G
System
hudc
Trapped TP TP iv
Drain -03/38 -03/39

1.149 tp tp cs
bfv str fc fc nrv bfv 0.148 0.148

0.148
South Female Lockers 02 23-01-17 23-01-17 ISSUED FOR CONSTRUCTION SJN JG
tp tp
bfv str fc fc nrv bfv 01 14-04-16 14-04-16 ISSUED FOR APPROVAL SJN JG

REV: DATE: CDM-CHK: REVISION: DRN: CHK:

CLIENT:

drv
H
Number of underfloor heating circuits 0.296 0.147
1.915 iv for each manifold to be confirmed by
the underfloor heating PROJECT:
Refer To LTHW Schematic PN16 iv iv Contractor/Manufacturer 0.304
Drg. No. H
Dirt
For Continuation To Main PN16
Seperator
DS tp tp tp tp tp tp tp tp tp
100 BISHOPSGATE
cs iv iv cs cs iv
System fmd -03/12
LONDON EC3
bfv bfv
LTHW mv dc dc dc dc mv mv dc dc
iv iv iv
iv
F&R (n/c) (n/c)
tp tp (n/c)
iv
iv iv Changing Area Schematic
drv mv 0.254 0.451
drv

DA
iv

fmd
I -03/11

Active
tp tp tp De-aerator Differential
picv ITS
Pressure Sensor
str str

tp tp tp
STATUS: I
fc fc CONSTRUCTION
tp
cs DRAWING TITLE:

picv S4 S1 MECHANICAL SERVICES


Heat 0.444 tp High limit shut off valve
tp fmd ENTRANCE LOBBBY
Ex. 0.705 UNDERFLOOR LTHW/CHW SCHEMATIC
ITS tp tp
fc S3 S2 fc cs
PN16 PN16 Discipline Project Phase
J MECHANICAL 1 J
hudc hudc
tp Drawing Originator Originator's Job No.
Heating Heat MICHAEL J LONSDALE ME2758
Exchanger Checked By Checked Date Drawn By Drawn Date
JN 14/04/2016 SJN 16/02/2016
HEX bfv Approved By Approval Date Scale Bldg Grid Reference
-03/21 JG 14/04/2016 1:XX @ A0 -

1.149 Drawing No. Revision

6000-109XX-513 02
1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16
Technical submittal sheet

6. Design Calculations Check


TS-6000-042 Contract
ME2758 100 Bishopsgate
number:

N/A
Technical submittal sheet

7. BMS Interface
TS-6000-042 Contract
ME2758 100 Bishopsgate
number:

Please see MJL BMS Tech Sub.


Technical submittal sheet

8. List of recommended spares


TS-6000-042 Contract
ME2758 100 Bishopsgate
number:

N/A
Technical submittal sheet

9 - Samples
TS-6000-042 Contract
ME2758 100 Bishopsgate
number:

N/A