Location of Intended
1D
Use:
Use in DEWA Transmission Asset: ☒ Yes ☐ No
Reference
1E
Document(s):
Specify Other
1F
Submittal Details:
2G ☒ Country of Origin 2P ☐
3. Contractor Details:
Prepared by: Reviewed by: Approved by:
Name: Noor Mohammed Name: Mohamed Nasar Name: Mohd Duraidy
Index
Dear Sir,
Reference to your inquiry we are at United Electronics very pleased to offer you the best price of our Mitsubishi
units as follows.
Notes:
** ALL UNITS HAVE ESMA CERTIFICATE
** ALL THE DECO / DUCTED UNITS ARE SIDE DISCHARGE. WITH R32 GAS
** ALL THE DUCTED UNITS WITH INVERTOR COMPRESSOR TECHNOLOGY.
**DUCTED UNITS ARE COMPATIBLE TO CONNECTED TO BMS & (SMART SYSTEM ) WITH ADITIONAL PARTS
**WORK UNTIL 52C
Summary:
Decorative Split A/C Unit 03 TR, Top Discharge (EER as per DM Regulation)
Company Profile
Technical Data Sheet
Reference for ongoing Projects
Reference for previous Projects
ISO Certificates
Test Certificates
Trade License
Product Catalogue
Copy of Previous Approvals
18.08.2021
Submit thermostat with advanced model (more digital) and compact size including better look aesthetically
wise for Consultant / Client's approval.
Client Project Management Architect/Engineer of Main Contractor
record
1. Contractor has proposed DX units ducted and decorative type from the M/s Mitsubishi-Thailand, is
acceptable in principle as manufacturer, subject to comply with following comments,
2. Contractor to ensure the air flow rates are shown on selection shall be validated based on floor plan.
3. The DX unit for dual purpose in case of Chilled water units fails whereas shown in design drawings if any,
the units switching interfaces and operational shall be addressed.
4. Confirm the condensing unit fans with variable speed to maintain the compressor head pressure, as
specified, highlight the features on manufacturer technical literature attached in submittal.
5. The condensing unit shall be selected with horizontal or vertical discharge based on allocated with specified
locations with allowances of installation and maintenance access as recommended by the manufacturer.
The unit arrangements, indoor and outdoor, refrigerant pipework shall be verified by the supplier and
stamped on drawings submitted in due course.
6. Outdoor unit casing material and coil coatings shall be suitable for hot, humid and saline environment,
submit test certificates to substantiate.
7. Contractor to verify that the proposed ESPs are calculated based on the routing / size of ducts as per
approved coordinated shop drawings. Submit ESP calculation part of technical submittal for review.
8. Contractor shall validate the energy performance compliance to issued Sustainability report as per local
Authority approval, establish the sustainability check list along with submittal.
9. Country of origin, bill of lading, packing list and factory performance test reports shall be submitted for
Equipment’s along with material delivery at site. Demonstrate the shipment tracking upon delivery.
Chandar
Comments:
Signed Signed
31-08-2020
WSP/Parsons Brinckerhoff Ltd. AADC
Note: The above comments and/or approval does not relieve the Contractor from the obligation in the Contract to ensure conformance to
the Specifications. Any Specification deviations found subsequent to approval are to be corrected by the Contractor to the satisfaction of
the AADC/Engineer.
TYPE OF SUBMITTAL
Shop Drawings & Schedules Method Statement Preliminary As Built Drawings
Samples Programme As Built Drawings
Materials & Product Data Mock-up & QC panel O & M Manuals
Certification & Verification of Inspection & Test Reports Other - Please specify
Performance
DESCRIPTION
SUB CONTRACTOR / MANUFACTURER
VRV Units
M/s Mitsubhisi Electric
1. CONTRACTOR TO ENSURE MANUFACTURER LICENSED ARE UP TO DATE AND APPROVED BY THE LOCAL
AUTHORITY.
2. CONTRACTOR TO ENSURE THAT NOISE LEVEL OF INDOOR UNIT NOT EXCEED THE MINIMUM NOISE dB
LEVEL.
MICHAEL ARABIANA
15 May 2019
For and on behalf of Consultant Date:
RVT
PROJECT MANAGER'S APPROVAL
QR.C-06/R-02/Jan2015