MATERIAL / EQUIPMENT APPROVAL REQUEST (MEAR)

HATTA PUMPED STORAGE HYDRO Project / PO3091900054


Project / Location Name:
POWER PLANT (PSHPP) Location No.:

Reference No.: PO3091900054-W-31-ME-AC-004 Rev.: A


1.Submittal Details

Material Name / Decorative Split A/C Units


1A
Description:
DEWA Transmission MSCMS ID: N/A
Manufacturer / MITSUBISHI ELECTRIC
1B
Supplier: UNITED ELECTRONICS CO.(L.L.C.)
1C Country of Origin: THAILAND

Location of Intended
1D
Use:
Use in DEWA Transmission Asset: ☒ Yes ☐ No

Reference
1E
Document(s):

Specify Other
1F
Submittal Details:

2.Attachments (* = Mandatory Requirement)


2A ☒ Technical / Material Data Sheet 2J ☐ Safety Data Sheet

2B ☒ Related Contract Specification 2K ☒ Reference Drawing

2C ☒ Company Profile 2L ☒ *Questionnaire for Manufacturer / Supplier’s Qualification


(Employer Issued)

2D ☒ Valid Licences & Certificates 2M ☐ *Manufacturer’s / Supplier Qualification (Employer Issued)

2E ☒ Valid ISO Certificates 2N ☒ Typical inspection and Test plan (ITP)

2F ☒ Related Test Reports 2O ☐

2G ☒ Country of Origin 2P ☐

2H ☒ Related Previous Approvals 2Q ☐

2I ☒ Related Previous Projects 2R ☐

3. Contractor Details:
Prepared by: Reviewed by: Approved by:
Name: Noor Mohammed Name: Mohamed Nasar Name: Mohd Duraidy

Signature: Signature: Signature:

Date: 29-06-2022 Date: 29-06-2022 Date: 29-06-2022

IMS # 30-F016-7966002E RevC 22.11.2021 PAGE 1 OF 1


TECHNICAL MATERIAL SUBMITTAL

Decorative Split A/C Unit


PROJECT: HATTA PUMPED
STORAGE HYDRO POVVER PLANT
{PSHPP), DUBAI, UAE

EMPLOYER: Dubai Electricity & Water Authority (DEWA)

ENGINEER: Electricite de France (edf)

MAIN CONTRACTOR: Strabag-Ozkar JV

SUB CONTRACTOR: Al Hijaz Mechanical Equipment


Co.LLC. (AHME)

MANUFACTURE: Mitsubishi Electric

SUPPLIER: United Electronics Co. (L.L.C.)


Project: HATTA PUMPED STORAGE HYDRO POWER PLANT (PSHPP), DUBAI – UAE
Employer – Dubai Electricity & Water Authority (DEWA)
Engineer – Électricité de France (edf)
Main Contractor – Strabag-Ozkar JV
Subcontractor: Al Hijaz Mechanical Equipment Co.LLC. (AHME)

Index

(1) DEWA Questionnaire for Supplier-Manufacturer qualification


(2) List of Material
(3) Company Profile
(4) Technical Data Sheet
(5) Reference for recent Projects
(6) Reference for previous Projects
(7) ISO Certificates
(8) Test Certificates
(9) Trade License
(10) Product Catalogue
(11) Copy of previous Approval
Questionnaire for Manufacturer / Supplier’s Qualification
Bill of Material
UNITED ELECTRONICS CO. (L.L.C)
ABU DHABI DUBAI AL AIN SHARJAH
P.O.BOX 25751 13751 20029 31367
TEL. + 971 2 6777701 4 2277401 3 7556404 6 5591119
FAX: + 971 2 6728940 4 2230529 3 7556414 6 5591212
E-mail: unitco@emirates.net.ae .
TRN NO. 100011562400003
WEBSITE: www.unitco.ae

TO AL HIJAZ MECHANICAL EQUIPMENT FROM ENG.AMAL ABDALLAH


ATTN ENG. RAEAD OUR REF 21/22/AA
TEL/FAX/E-MAIL (+971) 4 2672269 PAGES 02
YOUR REF EMAIL DATE 21/JUN/22
SUBJECT : LIST OF MATERIALS
PROJECT: HATTA PUMPED STORAGE HYDRO POWER PLANT (PSHPP),

Dear Sir,
Reference to your inquiry we are at United Electronics very pleased to offer you the best price of our Mitsubishi
units as follows.

Notes:
** ALL UNITS HAVE ESMA CERTIFICATE
** ALL THE DECO / DUCTED UNITS ARE SIDE DISCHARGE. WITH R32 GAS
** ALL THE DUCTED UNITS WITH INVERTOR COMPRESSOR TECHNOLOGY.
**DUCTED UNITS ARE COMPATIBLE TO CONNECTED TO BMS & (SMART SYSTEM ) WITH ADITIONAL PARTS
**WORK UNTIL 52C

Summary:

MODEL TYPE QTY NOM.TR


MS-GS36/MU-GS36 VF Wall Mounted 4 3

Decorative Split A/C Unit 03 TR, Top Discharge (EER as per DM Regulation)
Company Profile
Technical Data Sheet
Reference for ongoing Projects
Reference for previous Projects
ISO Certificates
Test Certificates
Trade License
Product Catalogue
Copy of Previous Approvals
18.08.2021

Submit thermostat with advanced model (more digital) and compact size including better look aesthetically
wise for Consultant / Client's approval.
Client Project Management Architect/Engineer of Main Contractor
record

Project: 5190750, Marsa Al Arab, JBH Phase 5, Dubai

Submittal Type: Material Submittal Date: August 31, 2020

Document Reference: (WF-012148) MAA-ASGC-HVAC-CCD-000289 Rev.: 00

Subject : Material Submittal for DX Units

Status Code: Code B - Approved as Noted Discipline: Mechanical

Manufacturer: Mitsubishi-Thailand Local Supplier: Al Mazroui -UAE

1. Contractor has proposed DX units ducted and decorative type from the M/s Mitsubishi-Thailand, is
acceptable in principle as manufacturer, subject to comply with following comments,
2. Contractor to ensure the air flow rates are shown on selection shall be validated based on floor plan.
3. The DX unit for dual purpose in case of Chilled water units fails whereas shown in design drawings if any,
the units switching interfaces and operational shall be addressed.
4. Confirm the condensing unit fans with variable speed to maintain the compressor head pressure, as
specified, highlight the features on manufacturer technical literature attached in submittal.
5. The condensing unit shall be selected with horizontal or vertical discharge based on allocated with specified
locations with allowances of installation and maintenance access as recommended by the manufacturer.
The unit arrangements, indoor and outdoor, refrigerant pipework shall be verified by the supplier and
stamped on drawings submitted in due course.
6. Outdoor unit casing material and coil coatings shall be suitable for hot, humid and saline environment,
submit test certificates to substantiate.
7. Contractor to verify that the proposed ESPs are calculated based on the routing / size of ducts as per
approved coordinated shop drawings. Submit ESP calculation part of technical submittal for review.
8. Contractor shall validate the energy performance compliance to issued Sustainability report as per local
Authority approval, establish the sustainability check list along with submittal.
9. Country of origin, bill of lading, packing list and factory performance test reports shall be submitted for
Equipment’s along with material delivery at site. Demonstrate the shipment tracking upon delivery.

Chandar

Page 1 of 1 Document Ref. : (WF-012148) MAA-ASGC-HVAC-CCD-000289 Rev. 00


37464240 / P249-2016-60020/19/197
DESIGN REVIEW AND SUPERVISION FOR DESIGN AND
P O Box 47445 BUILD OF TWO PACKAGE UNITS 33-11 KV AT AL AIN ZOO
Abu Dhabi
United Arab Emirates

The Drawing/Document Comment Sheet – Review of Contractor’s Document No. 109

To : Engineering Solutions Electromechanical Fax No: 02-6718803


Attn : Project Manager
cc : Project Manager – Abu Dhabi General services PJSC, Fax No: 02-4042221
trading as Musanada
Project Engineer - AADC Fax No:
03-7632025

: DTS No. 109 Comment Sheet Ref. : CS-109

Submission Date : 19-Aug-2020 Date : 25-Aug-2020

Receipt Date : 20-Aug-2020 Page : 1 of 1

Previous reference : 109 rev-2

No. of working days 1


with Consultant

Titles / Details CSD No. Rev. Status Comment


P249-2016-
60020/19/197

1.0 HVAC Heat Load Calculation DTS-ELE-109 3 AP See below

Status AP = Approved AEN = Approved Except as Noted NA = Not Approved


RET = Returned

Comments:

1.0 HVAC Heat Load Calculation, Rev.3


1.1 Clarification noted and contractor shall demonstrate indoor temperature and humidity for each zone during
summer and winter reliability test (submit SAT procedure for HVAC system)

Signed Signed
31-08-2020
WSP/Parsons Brinckerhoff Ltd. AADC

Note: The above comments and/or approval does not relieve the Contractor from the obligation in the Contract to ensure conformance to
the Specifications. Any Specification deviations found subsequent to approval are to be corrected by the Contractor to the satisfaction of
the AADC/Engineer.

200819-P249-EGE-109-HVAC Heat Load Calculation Page 1 of 1 25/08/2020


-R3
SUBMITTAL COVER SHEET
NAME OF PROJECT: Robotics Lab Design & Build
Submittal No: ATS-RL-50804-MA-ML-016
Project
Project No. 50804 Revision No: 00
Client: M/s Dubai Future Foundation Submittal Date: 13-May-2019
Consultant: RVT Title: Mechanical
Contractor: M/s. Al Tayer Stocks LLC Drawing No:

FIRST SUBMITTAL OF THIS ITEM OR RESUBMITTAL

TYPE OF SUBMITTAL
Shop Drawings & Schedules Method Statement Preliminary As Built Drawings
Samples Programme As Built Drawings
Materials & Product Data Mock-up & QC panel O & M Manuals

Certification & Verification of Inspection & Test Reports Other - Please specify
Performance

DESCRIPTION
SUB CONTRACTOR / MANUFACTURER

VRV Units
M/s Mitsubhisi Electric

Specification & BOQ Ref: Location / Use:

DESIGN CONSULTANT'S COMMENTS

1. CONTRACTOR TO ENSURE MANUFACTURER LICENSED ARE UP TO DATE AND APPROVED BY THE LOCAL
AUTHORITY.

2. CONTRACTOR TO ENSURE THAT NOISE LEVEL OF INDOOR UNIT NOT EXCEED THE MINIMUM NOISE dB
LEVEL.

CONTRACTOR'S REVIEW SUBMITTAL REVIEW STATUS

The contractor has reviewed this submission prior to A Approved


submission to the Consultant B Approved with Comments
C Rejected
Signature D Not Reviewed

DATE RECEIVED DATE RETURNED

DESIGN CONSULTANT'S SIGNATURE

MICHAEL ARABIANA
15 May 2019
For and on behalf of Consultant Date:
RVT
PROJECT MANAGER'S APPROVAL

For and on behalf of Project Manager Date:

Distribution: Original to Al Tayer Stocks