LIWA

GRID STATION
PROJECT: TENDER NO: 61/2021 CIRCUIT:
UPGRADING AND RECONSTRUCTION OF SIET-2 PSS TO 3X20MVA WITH 33KV OUTGOING FEEDER [H_LN02]
ONE 33KV FRESH FEEDER FROM LIWA-2 GRID STATION (NORTH BATINAH GOVERNORATE) – TO FIZAH PSS [H_LN02]

PRE-COMMISSIONING TEST REPORT

PROTECTION RELAY @ 33KV OUTGOING FEEDER [H_LN02]


TO FIZAH PRIMARY STATION – INCOMER # 2

Tested By Reviewed By
OMAN NATIONAL ENGINEERING & INVESTMENT CO. MAJAN ELECTRICITY COMPANY SAOC
Name FEROZ HAKKIM
Signature

Date:
PROJECT: TENDER NO: 60/2021
UPGRADING FIZAH PSS FROM 3X6MVA TO 2X20MVA
WITH 33KV FEEDER INTERLINKS FROM SHINAS GRID (NORTH BATINAH GOVERNORATE)

Station SHINAS OLD GRID STATION VT Ratio 33KV LINE VT 33KV/√3/110V/√3


Circuit Reference 33kV OUTGOING FEEDER [H_LN02] CT Ratio 33KV FEEDER PANEL CT 400/1 A

1. PROTECTION RELAY TESTING – F87L


DATE OF TEST: 31/10/2022
1.1. Line Differential Relay Details
Relay Function Line Differential Protection
Relay Code 87L
Relay Make/Model SIEMENS 7SD86
Relay Order Code P1B88239
Serial BM2009006936
Phase CT Ratio 400 / 1 A

1.2. Relay Setting


Function Pickup Setting
I DIFF> 0.2 A
I DIFF>> 1.20 A
BACKUP OC HS 12 A

1.3. Relay Characteristic Test Results


Function Pickup Trip Time
Function
Required Actual Required Actual
I DIFF> Rɸ 0.2 A 0.22 A 0S 30.10 mS
I DIFF> Yɸ 0.2 A 0.22 A 0S 30.20 mS
I DIFF> Bɸ 0.2 A 0.22 A 0S 32.60 mS
I DIFF>> 3ɸ 1.2 A 1.37 A 0S 16.90 mS
BACKUP OC HS 3ɸ 12 A 12.06 A 0S 7.60 mS

2. PROTECTION RELAY TESTING – F51/51N


DATE OF TEST: 31/10/2022
2.1. OC & EF IDMT Relay Details
Relay Function Overcurrent & Earth Fault Protection
Relay Code 51/51N
Relay Make/Model SIEMENS 7SJ802
Relay Order Code 7SJ80215EB261FA0----------------
Serial 1308504517
Phase CT Ratio 400 / 1 A

2.2. Relay Setting


Function Pickup Setting Trip Delay Setting Trip Delay Curve
51 – OC IDMT 1.5 A 0.18 IEC SI
51N – EF IDMT 0.20 A 0.15 IEC SI
51 – OC DMT 1.0 A 16.0 S DT
46 – BROKEN CONDUCTOR I2/I1 = 40% 5.5 S DT
51NS – SEF 0.05 A 5.0 S DT

2.3. Relay Characteristic Test Results


Function Pickup X2 Trip Time X5 Trip Time (mS)
Function
Required Required Actual Required Actual
51 OC Rɸ IDMT 1.5 A 1.805 S 1.806 S 770.4 mS 765.5 mS
51 OC Yɸ IDMT 1.5 A 1.805 S 1.806 S 770.4 mS 765.1 mS
51 OC Bɸ IDMT 1.5 A 1.805 S 1.806 S 770.4 mS 765.2 mS
51N EF IDMT 0.20 A 1.504 S 1.510 S 642.0 mS 636.1 mS
51 OC 3ɸ DMT 1.0 A 16.0 S 16.03 S -- --
46 BC DT 40 % 5.50 S 5.543 S -- --
51NS SEF DT 0.05 A 5.0 S 5.039 S -- --