Reference: 3271005941

Project: Saidpur 20MW GT Power Station, BPDB, Saidpur, Nilphamari,


Bangladesh
Contractor: SPARTANS
End-Customer: Bangladesh Power Development Board
PO ref.: Procurement of 145 KV SF6 Circuit Breaker Including Installation,
Testing & Commissioning for Saidpur 20MW GT Power Station
27.11.0000.304.19.466.19.09, Dated: 24.10.2019

LIVE TANK CIRCUIT BREAKER 145 KV (AIS), 3150 A, Mechanically GANG


OPERATED, RATED SHORT CIRCUIT BREAKING CURRENT: 40KA

Minimum Requirement of BPDB Guaranteed


S. No. Description
Unit Data

1. Circuit Breaker – General

1.1. Manufacturer Alstom T&D GE T&D India Limited


(Formerly ALSTOM)
outdoor, 3Phase , Live tank, outdoor, 3Phase , Live tank,
1.2 Type
three pole operated three pole operated
(Mechanically gang
operated)

1.3 Model designation GL312PF1 GL312PF1


1.4 Country of origin to be mentioned India
IEC 62271-100, 60273, IEC 62271-100
1.5 Standards
60694, 60815
1.6 Isolating and quenching medium SF6 SF6
1.7 Type of circuit breaker Outdoor Outdoor

1.8 Design Gang breaking Gang breaking

1.9 Operating mechanism Motor-wound spring Motor-wound spring


1.10 Number of poles pcs. 3 3

2. Circuit Breaker – Characteristics

2.1 Nominal system voltage kV rms 132 132


2.2 Highest voltage for equipment Un kV rms 145 145
2.3 Rated lightning impulse withstand voltage kV peak 650 650
Rated short duration power frequency
2.4 kV 275 275
voltage
2.5 Rated frequency f r Hz 50 50

2.6 Rated current Ir A 3150A 3150A

2.7 Rated short-circuit breaking current Isc kA rms 40kA 40kA

Page 1|4
Minimum Requirement of BPDB Guaranteed
S. No. Description
Unit Data
Rated peak withstand current Ip (equal
2.8 kA 100kA 100kA
short-circuit making current)
D.C. component of the rated short-circuit
2.9 % > 30 > 30
breaking current
2.10 Rated operating sequence O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO

2.11 Duration of short-circuit s 3 3


2.12 Rated out-of-phase breaking current kA To be mentioned 10kAp

2.13 Auto reclosing Yes yes

Maximum total break time (trip initiation to


2.14 final arc extinction) pos.3.7.135 acc. to IEC ms ≤ 60 ≤ 60
62271-100)

Time of final arc extinction (3.7.134 acc. IEC


2.15 ms 20 ± 5 20 ± 5
62271-100)

2.16 Opening time ms ≤45 ≤45


Number of operations without maintenance
CO at no-load ≥ 10000 ≥ 10000
2.17
CO at rated current ≥ 2500 ≥ 2500
CO at rated breaking current Isc ≥5 ≥5
2.18 The frequency of mechanical operations Class M2 M2
2.19 Rated electrical endurance Class Min E1 E1
2.20 Rated pressure of a circuit breaker Mpa To be mentioned 0.64
2.21 Limits of gas pressure at 20°C
Maximum Mpa To be mentioned 0.74 (Absolute)
Minimum Mpa To be mentioned 0.61 (Absolute)
2.22 Guaranteed maximum gas leakage % per year <1% <1%
2. 23 Total mass of SF6 gas in a circuit breaker kg To be mentioned Refer OGA

3. Circuit Breaker - Design and Construction

3.1 Circuit Breaker


3.2 Insulator material Porcelain Porcelain
3.3 Minimum creepage distance mm/kV Min. ≥ 25 Min. ≥ 25
3.4 HV terminal Pcs/ckt 2 2 per pole

3.5 Shape Flat Flat


Weight and dimensions
3.6 Support insulator height mm To be mentioned

Page 2|4
Minimum Requirement of BPDB Guaranteed
S. No. Description
Unit Data
3.7 Total height mm To be mentioned
3.8 Pole weight kg To be mentioned
3.9 Weight of operating mechanism kg To be mentioned
3.10 Total weight (with metal structure) of CB kg To be mentioned Please refer attached OGA
3.11 Minimum clearance
3.12 Between poles mm To be mentioned
3.13 To ground mm To be mentioned
Operating mechanism
3.14 Operating mechanism Manufacturer To be mentioned Spring - Spring
3.15 Is lockout facility fitted? Yes/No Yes Yes
3.16 Motor - auxiliary supply voltage V, Hz 230, 50 230, 50

3.17 Rated power of motor W To be mentioned 380W


3.18 Control voltage V. DC 110 110
3.19 Number of closing coils pcs. 1 1
3.20 Number of tripping coils pcs. 2 2
3.21 Heater Yes Yes
3.22 Heater supply voltage V, Hz 230,50 230,50
Minimum number of available contacts
3.23 8NO+8NC+1V 8NO+8NC+1V
(NO/NC/V)
3.24 Water-tight corrosion-resistant housing IP55 IP55
3.25 A crank for manual spring loading Yes Yes
4 Accessories in central control panel
4.1 Anti-pumping relay Yes Yes Shall be done through
by contactor
4.2 Local/remote control selector switch Yes Yes
4.3 Local operation push buttons Yes Yes
4.4 Minimum pressure lock-out and alarm relays Yes Yes
4.5 Service outlet (socket) - 230 V, 50 Hz,13A Yes Yes
4.6 Lighting switch Yes Yes
4.7 Lighting - 230 V, 50 Hz Yes Yes
4.8 Heater - 230 V, 50 HZ Yes Yes
4.9 Operation counter Yes Yes
Motor MCB (miniature circuit breakers) (for
4.10 Yes Yes
all operating mechanisms)
4.11 Time phase discrepancy relay Yes NA

Page 3|4
Minimum Requirement of BPDB Guaranteed
S. No. Description
Unit Data
Weather proof, corrosion resistance
4.12 IP55 IP55, Material: Al
enclosure, Al or stainless steel
Cu earthing rails inside central control Al. Earth pad provided
4.13 Yes
cabinet externally
Detachable plates, the bottom of central
4.14 Yes Yes
control cabinet
Set of cables for connection of operating
4.15 mechanism and central control panel of Yes NA
circuit breaker
Galvanized horizontal and vertical metal
4.16 Yes Yes
structure with minimum 85 μm zinc layer
4.17 Supporting structure Shall be provided Shall be provided
4.18 Gas filling equipment shall be provided shall be provided
4.19 SF6 Gas Cylinder , 20 Kg Shall be provided 10kg Shall be provided
4.20 Name plate rating Shall be provided Shall be provided