Circuit Breaker

Sr. No Parameters/Standards Guaranteed Particulars


1 Manufacturer’s Name and Country: CG Power and Industrial Solutions Ltd. India
2 Manufacturer’s type designation 70-SFM-40AA
3 Applicable Technical Standards IEC-62271-100
4 Rated Voltage (kV rms) 66
5 Rated frequency (Hz) 50
6 Type of arc quenching medium SF6
7 Number of poles 3
8 Rated normal current (A) 1250A
9 First pole to clear factor 1.5
10 Rated short circuit current breaking capacity at rated voltage (kA rms) 31.5kA
11 Rated short circuit making current (kA rms) 78.75kA
12 Rated short circuit current duration (seconds) 3
a) Total break time for any current upto the rated breaking current with limiting
13 </=60
conditions of operating & quenching media pressure (ms) b) Rated break time(ms)
14 Closing time (ms) </=80
15 Standard value of rated transient recovery voltage for terminal fault As per IEC-62271-100
16 Rated operating duty cycle O-0.3s-CO-3min-CO
17 Auto reclosing Yes
18 Rated insulation level
a) 1.2/50 micro second lightning impulse withstand voltage between line terminals We confirmed 375kVp
and ground between terminals with contact open However as per IEC 325kVp

b) One minute power frequency withstand voltage between line terminals and We confirmed 160kVp
ground and ground between terminals with contact open (kV rms) However as per IEC 140kVp

19 Minimum corona extinction voltage in open and close position (kV rms) Not Applicable
Maximum radio interference voltage for frequency between 0.5 to 2 MHz in open
20 Not Applicable
and close position (micro volt)
21 Maximum line charging current (rms) 110A
22 Rated cable charging breaking current capacity (rms) 125A
a) Not Applicable
Difference in instants of closing/opening of contacts a) Within a pole(ms) b) Between b) </=3.3
23
poles for opening(ms) c) Between poles for closing(ms) c) </=5

24 Maximum noise level upto 50 m distance from the base of CB (dB) < 140
25 Temperature rise above ambient temperature (Deg.C) AS per IEC
26 No. of trip coils 2
Operating mechanism
a) Type Motorised Spring charged mechanism
27 b) Charging Spring - Spring
c) Max. actuating force required for manual charging of spring 40 kg
d) Supply voltage 110V DC
e) Permissible supply voltage variation in case of motor charging 85-110%
a) Auxiliary Contacts Yes
28
b) No. of Auxiliary contacts 10 NO 10 NC
29 Minimum Creepage distance (mm) 1815 mm
30 Control circuit voltage 110V DC
31 Circuit breaker Class —
32 CLEARANCES
a) Phase to Phase spacing for breaker (mm) 1100
b) Phase to earth clearance (mm) 850
33 Quantity of SF6 (gas) required for 1 st filling of all 3 poles of CB at rated pressure 4.5
34 Rated pressure of SF6 (gas) in CB 6 kg/cm2
35 Quantity of SF6 gas & its pressure supplied in SF6 (gas) cylinder + 20% extra 11kg
36 Make and type of vacuum interrupter —
37 Short circuit rating of vacuum interrupter —
38 Whether vacuum interrupter are Type Tested (Yes/ No) —
39 No. of operation with full short circuit —