Report No: JTR-20006

TEST REPORT Date


Page No.
27/06/2020
3.1 of 3.3

Current Transformer Details

Current Transformer Nameplate Data Current Transformer Rating


Serial number 20203 Standard IEC 60044
Rated frequency 50.0 Hz Cores 2
Phase C Taps 1
Manufacturer Sunzle

Current Transformer Core 1 Configuration Current Transformer Core 2 Configuration


Application Metering Application Protection
Ratio 150 : 5 Ratio 150 : 5
Class 0.5 Class 10p
FS ALF 10

Detailed ratings for each taps


Core Name of Tap Ipn: Isn Rated Burden
1 1S1 - 1S2 150 : 5 10VA – 0.8

2 2S1 - 2S2 150 : 5 15VA – 0.8


Report No: JTR-20006
TEST REPORT Date
Page No.
27/06/2020
3.2 of 3.3

Measurement of Turns Ratio

Current Transformer Turns Ratio: The CT ratio is the ratio of primary current input to secondary current output at full
load.

Connection Diagram:

Procedure:
1. All the Busbar Connection were removed from the terminals of CT.
2. All the Burdens were disconnected from the CT.
3. Measurement Settings were verified according to the test requirements.
4. The Measurement to be performed was selected and the output and input of the CPC to the CT were
connected as indicated by the wiring diagram.
5. No secondary windings were open.
6. Assessment was conducted & the result was recorded automatically in the CPC 100.
Report No: JTR-20006
TEST REPORT Date
Page No.
27/06/2020
3.3 of 3.3

Measurement of CT Ratio

Max. Test Current 400A Used Equipment CPC 100


Test Frequency 50 Hz Serial No. VF027D
Testing Time 23/06/2020

Ratio
Core Tap Ipn:Isn I prim I sec Ratio Phase Polarity
Dev.
(A) (A)
1 1S1-1S2 150:5 149.99 5.0173 150 : 5.0176 0.35 % 13.90 ° OK

2 2S1-2S2 150:5 99.97 3.9372 150 : 5.9075 -1.95 % 19.94 ° OK

Comments:
No significant deviations are recorded as per values.

Tested By: Witnessed By: Approved By: