33kV CT Phase C– Report (20203)

Client RRP Agro 33kV CT C


Execution date 6/23/2020 Reason of the job Commission
Tested by JRCTESTING-PC\JRC TESTING Location 33kv CT C
Approved by JRC Powertech Asset Current transformer
Report ID 2 Asset type Inductive
Report issue date 6/26/2020 11:29:07 AM Asset serial number 20203
Work order RRP Manufacturer sunzle

Summary

Performed tests Assessment


CT Ratio Not assessed

Overall Assessment Not assessed

Tested by: Approved by:

1
Location & company information
Location Company
Name 33kv CT C Company
Region NARSHINDI Department
Division DHaka Address
Area City
Plant State/Province
Address Postal code
City Country
State/Province Phone No.
Postal code Fax No.
Country E-mail

Geo coordinates

Contact person Comment


Name
Phone No. 1
Phone No. 2
Fax No.
E-mail

Current transformer nameplate data


Serial number 20203 Apparatus ID
Manufacturer sunzle Rated frequency 50.0 Hz
Manufacturing year Feeder
Manufacturer type Phase
Asset system code

Comment

Ratings
Standard IEC 60044
Primary windings 1x
Um (r.m.s.) V
U withstand (r.m.s.) V
U lightning (peak) V
Icth 120 %
I dyn (peak) A
I th (r.m.s.) A Duration 1s

CT configuration
Cores 2

Core 1

Full Tap Class Details

Application Metering
Class 0,5

2
Detailed ratings for 1S1 - 1S2:
FS

Name Ipn : Isn Rated burden Operating burden In Use


1S1 - 1S2 150 A : 5 A 10 VA - 0.8

Core 2

Full Tap Class Details

Application Protection
Class 10P
Detailed ratings for 2S1 - 2S2:
ALF 10.00

Name Ipn : Isn Rated burden Operating burden In Use


2S1 - 2S2 150 A : 5 A 15 VA - 0.8

Test set information


Model Serial number Calibration date
CPC100 VF027D 07/19/2019 11:05:57

Global test conditions


Weather Clear Humidity 60 %
Unit location Outside Ambient temperature 32 °C

Oil temperature 38 °C

3
CT Ratio
CPC output AC 800A
Rated frequency 50.0 Hz

Comments

Core 1

Tap Ipn : Isn f I prim I sec Ratio Ratio dev Phase Polarity In Use Assessment
1S1 - 1S2 150 A : 5 A 50.0 Hz 149.99 A 5.0173 A 150 : 5.0176 0.35 % 13.90 ° OK Pass

Core 2

Tap Ipn : Isn f I prim I sec Ratio Ratio dev Phase Polarity In Use Assessment
2S1 - 2S2 150 A : 5 A 50.0 Hz 99.97 A 3.9372 A 150 : 5.9075 -1.95 % 19.94 ° OK Pass