ELECTRICAL PROTECTION, TESTING & MAINTENANCE ENGINEERS GLOBAL PARTNER

TEST CERTIFICATE OF CURRENT TRANSFORMER


Client RELIANCE SILVASA Tested On 12/6/18
Plant Tested By NEEL
Feeder

1.
Metering Core :
0

Acc. Primary Secondary CT resi.


Sr. No. Ratio VA Polarity
Class Injected Current Current Ω
18/T-576369 4000/5 15 1.0 1000/2000 1.21/2.5 1.2
18/T-576370 4000/5 15 1.0 1000/2000 1.21/2.5 1.2
18/T-576371 4000/5 15 1.0 1000/2000 1.21/2.5 1.2

2.
Protection Core :
0

Acc. Primary Secondary CT resi.


Sr. No. Ratio VA Polarity
Class Injected Current Current Ω
18/T-576376 4000/5 15 5P10 1000/2000 1.21/2.5 1.6
18/T-576377 4000/5 15 5P10 1000/2000 1.21/2.5 1.6
18/T-576378 4000/5 15 5P10 1000/2000 1.21/2.5 1.6

3.
Differential Core :
0

Acc. Primary Secondary CT resi.


Sr. No. Ratio VA Polarity
Class Injected Current Current In Ω
18/T-575237 4000/1 15 P.S 500/1000 0.12/0.24 8.5
18/T-575238 4000/1 15 P.S 500/1000 0.12/0.24 8.5
18/T-575239 4000/1 15 P.S 500/1000 0.12/0.24 8.6

4.
General Checks :
0

Checks Remarks
1 Inspection For Physical Damage
2 Wiring Check
3 Cleaning And Tightness Of Connections

5.
Remarks :
0
ELECTRICAL PROTECTION, TESTING & MAINTENANCE ENGINEERS GLOBAL PARTNER

TEST REPORT FOR POTENTIAL TRANSFORMER


Client Tested On
Plant Tested By
Feeder

1.0 Metering Core :

Volts Volts
Meter
Ph PT Ratio VA Acc. Class Polarity Applied at Measured at
Reading
Primary Secondary
R
Y
B

2.0 Protection Core :

Acc. Primary Secondary Voltage On


Ph PT Ratio VA Polarity
Class Injected Volts Volts Relay
R
Y
B

3.0 General Checks :

CHECKS REMARKS
1 Inspection For Physical Damage
2 Wiring Check
3 Cleaning And Tightness Of Connections

4.0 Remarks :