You are on page 1of 20

KKS

Kraftwerk
Kennzeichen
System

Power Station Identification System


3 Types of KKS Code
process-related identification of system and items
of equipment in power plant process
mounting location for encoding installation
locations and places in electrical equipment
systems
room identification for encoding topographic
locations (compartments, floors) of plant and
equipment units buildings
Code & Breakdown Level

Breakdown Level 0 1 2 3

Process related Total Plant Station Code


Equipment Component
Identification Unit Code Code

Point of Installation Total Plant


Installation Installation
Identification Unit Code Space Code

Location Total Plant


Structure Room
Identification Code Code
Examples illustrating process-related identification :
Breakdown
levels 0 1 2 3
Equipment unit Component
Total plant System Code
code code
Spray deluge
Example Unit A Pump system Pump
system
0 0SGA10 AP001 KP01

0SGA10
KP01
Transformer
M

AP001
Process - Related Identification M
Identification of a Pump
Structure of Breakdown Levels
Breakdown Level 0 1 2 3

Process related Total Plant Station Code


Equipment Component
Identification Unit Code Code

Designation of G F0 F1 F2 F3 FN A1 A2 AN A3 B1 B2 BN
Character

Character A or N N A A A N N A A N N N A A A N N

Example for CCGT 2 1 M B P 1 3 A A 0 0 1 A - S 0 1


at Killingholme
Serial Number
Electrical Component = Switch
Suffix, identifying adjacent or x-fold items
Serial Number
Equipment = Valve
Serial Number
Function Group = Fuel Gas Supply for Gas Turbine
Section = 1 (of more GT within one module)
Module = 2 (of possible more modules, each consisting of 2 GT, 2 HRSG, 1 ST etc)

Thus. 2 1MBP13 AA001A -S01


mean = Module 2, Unit 1 GT - Fuel Gas Emergency Stop Valve Pilot Valve’s Limit Switch (open position)
Structure of Breakdown Levels Private Paiton 2 Case

Breakdown Level 0 1 2 3

Process related Total Plant Station Code


Equipment Component
Identification Unit Code Code

Designation of G F0 F1 F2 F3 FN A1 A2 AN A3 B1 B2 BN
Character

Character A or N N A A A N N A A N N N A A A N N

Example for Paiton 6 0 H H E 6 1 A A 0 0 1 - S 0 1


Unit 6
Serial Number
Electrical Component = Switch
No suffix identifying
Serial Number
Equipment = Valve
Pulverizer Number “6” distribution line corner “1”
Function Group = Pulverized coal bin, forwarding and distribution system
Section = 0 (no more further detail)
Unit = 6 (of possible Unit 5 or Unit 6)

Thus. 6 0HHE61 AA001 -S01


mean = Unit 6, Pulverized coal distribution line shut-off valve (Burner shut-off slide gate) Limit Switch (open position)
Structure of Breakdown Levels
Breakdown Level 0 1 2 3

Process related Total Plant Station Code


Equipment Component
Identification Unit Code Code

Designation of G F0 F1 F2 F3 FN A1 A2 AN A3 B1 B2 BN
Character

Character A or N N A A A N N A A N N N A A A N N

Example for Paiton 5 0 L B A 3 0 C T 0 0 1 - B 0 1


Unit 5
Serial Number
Electrical Component = Transducer
No suffix identifying
Serial Number
Equipment = Temperature Monitor
Serial Number
Function Group = Main Steam Piping System
Section = 0 (no more further detail)
Module = 2 (number 5 Unit)

Thus. 5 0LBA30 CT001 -B01


mean = Unit 5, Main Steam Temperature Monitor (Transducer)
Examples illustrating process-related identification :
Breakdown
levels 0 1 2 3
Equipment unit Component
Total plant System Code
code code
Unit Station Cooling Fan
Example Unit 1 Transformer MV
Motor
system
1 2BBT01 AN010 - M01

2BBT01

- M01
Transformer
M

AN010
Process - Related Identification
M
Identification of a Fan Motor of
Transformer
Examples illustrating mounting location identification :
Breakdown 0 1 2
levels Mounting Mounting
Total plant
unit code space code
Example Low voltage
Unit 1 Tier/space
switchgear
1 0BFA04 CA022

0BFA04
A 01 02 03 04
B
C
D
E

Mounting Location Identification


Plug - Unit a Low Voltage CA022
Switchgear cabinet
Examples illustrating mounting location identification :
Breakdown 0 1 2
levels Mounting Mounting
Total plant
unit code space code
Example Console,
Common Coordinate
Section
0 0CWA02 AB22

CWA02

AA

AB

AC

AD
21 22 23 24 25 26 27
Mounting Location Identification
Instrumentation & Control Example
Examples illustrating topographic location identification :
Breakdown 0 1 2
levels Structure Room
Total plant
code code
Example Structure/Build-
Common Room Number
ing & Floor
0 0UCA04 04

UHN UCA
Control Room
UHA Building

UHT

UCA
UMA
UCA06 UCA0404 Room no. 4
UCA05
UCA04
UCA03
UCA02
UCA01

Topographic Location Identification


for Building or Structure UCA04
Function Key, Main Group
A Grid and distribution systems
B Power transmission and auxiliary power supply
C Instrumentation and control equipment
E Fuel supply and residues disposal
G Water supply and disposal
H Heat generation
L Steam, water cycles
M Main machine sets
P Cooling water systems
Q Auxiliary systems
S Ancillary systems
U Structures
X Heavy machinery (not main machine sets)
Function Key B

BA Power Transmission
BB Medium voltage distribution boards and transformers, unit
BC Medium voltage distribution boards and transformers, station service
BF Low voltage main distribution boards and transformer, unit
BH Low voltage main distribution boards and transformer, station service
BM Low voltage distribution boards and transformer, (diesel) emergency power
. system
BR Low voltage distribution boards (converter) emergency power system
BT Battery systems
BU DC distribution boards
Function Key BA

BAA Generator leads


BAB Foundation cabinets
BAC Generator circuit breaker, also commutating pole circuit breaker, incl.
cooling system
BAT Generator Transformer, including cooling system
BAW Earthing and lightning protection system
BAX Control air supply system
BAY Control and protection equipment
Equipment unit Key, Main Group
A Mechanical equipment
B Mechanical equipment
C Direct measuring circuits
D Closed loop control circuits
E Analog and binary signal conditioning
F Indirect measuring circuits (gated, corrected, suppressed, calculated
G Electrical equipment
M Subassemblies of main and heavy machinery
Equipment unit Key A, Mechanical Equipment
AA Valves, dampers, etc., incl. actuators, also manual, rupture disk equipment
AB Isolating elements, air locks
AC Heat exchanger, heat transfer surface
AE Turning, driving, lifting and slewing gear (also manipulators)
AF Continues conveyors, feeders (escalators)
AG Generator units
AH Heating, cooling and air conditioning units
AJ Size reduction equipment, only as part of process
AK Compacting and packaging equipment, only as part of process
AM Mixers, agitators
AN Compressors units, fans
AP Pump units
AS Adjusting and tensioning equipment for non-electrical variables
AT Cleaning, drying, filtering and separating equipment, excl. *BT*
AU Braking, gearbox, coupling equipment, non-electrical converters
AV Combustion equipment
AW Stationery tooling, treatment equipment
AX Test and monitoring equipment for plant maintenance
Component Key, Main Group

K Mechanical components
M Mechanical components
Q Instrumentation and control components (non-electrical)
- Electrical components
X Signal origins
Y Signal applications
Component Key -, Electrical Component
-A Assemblies and subassemblies
-B Transducers for non-electrical to electrical variables and vice-versa
-C Capacitors
-D Binary elements, delay devices, memory devices
-E Special components
-F Protective devices
-G Generators, power supplies
-H Signalling devices
-K Relays, contactors
-L Inductors
-M Motors
-N Amplifiers, controllers
-P Measuring instruments, testing instruments
-Q Power switchgear
-R Resistors
-S Switches, selectors
-T Transformers
-U Modulators, convertors from electrical to other electrical variables
-V Tubes, semiconductors
-W Transmission paths, waveguides, aerials
-X Terminals. plugs, socket
-Y Electrical positioners, e.g. solenoids (non-motors)
-W Terminations, balancing equipment, filters, limiters, cable terminations, equalizers, hybrid transformers
Serial Numbering
Demineralized Water Pumps

0 0GHC10 AT001
0 0GHC01 AT001

0 0GHC10 AP001
Demineralized Water 0 0GHC01 AP001 Closed Cycle
Storage Tank 0 0GHC20 AT001 Cooling Water
0 0GHC02 AT001 Head Tank

0 0GHC20 AP001
0 0GHC02 AP001
0 0GHC30 AT001
0 0GHC03 AT001

0 0GHC30 AP001
0 0GHC03 AP001
Decading system
Closed Cooling Water Pump
Suction Header
Ascending system
Coal Handling Plant KKS Sample
KKS Description

0 0EAA01 Ship Unloader Scraper to unload the coal from


Ship to Unloading Belt Conveyor
0 0EAC11 Belt Conveyor from Ship Unloader to Junction
House 0 0UEF01
0 0UEF01 Junction House to switch Coal Loading from BC
0 0EAC01 to BC 00EAC12
0 0EBE11 Junction House 0 0UEF01 Magnetic Separator

0 0EAD11 Stacker/Reclaimer

You might also like