ACCU at 8300 Rotor Health Monitor DS 0178
ACCU at 8300 Rotor Health Monitor DS 0178
■ Continuous monitoring for ground faults Ground resistance measurement technology: By using 16-bit
digital rotor telemetry technology, Accumetrics allows users
to monitor fault resistance trends over time and track the
TYPICAL APPLICATIONS progression of ground faults from their onset. This provides
the possibility of early warning of impending failure and allows
■ Rotor protection through condition based maintenance
for predictive maintenance. Two adjustable- threshold alarm
■ Predictive maintenance for large motors and generators relay contacts, 4-20 mA, and digital data output of all measured
parameters are provided, allowing warning, shutdown, and
■ Increasing production throughput control by improved
overtemperature monitoring predictive maintenance tracking for ground faults.
Average Field Winding Calculated from directly measured field voltage Control of User Settings (see above)
Temperature divided by directly measured field current Fault resistance trend graph; numeric display of
RHM Console Software fault resistance & location, field voltage, currents,
Field Voltage Features resistance & average winding temperature; RTD
0 to 500 VDC temperatures; system status. Archival data storage in
Measurement range
(Contact factory for other ranges) .csv files for importing into MS Excel.
Maximum Transient
1000 V for 5 seconds Physical
without Damage
Measured by a low level differential voltage from a Field positive and negative terminals, rotor ground,
customer supplied 0-100 mV current shunt installed Rotor Connections RTD inputs, and connections to current shunts
Field Current (located at the field negative terminal)
at the negative terminal so that common mode volt-
Measurement Range
age is within ± 0.75 Volts of Vf Negative connection.
End of shaft mounted transmitter, approximately
Two redundant channels are provided. Transmitter Mounting
150 mm diameter, contact Accumetrics for special
Information
Ground Fault Resistance Measurement adapters or other mounting requirements.
Measurement Range 0 to 80 MegOhms Environment
± 250 Ohms ± 2% of reading 0 to 500 kOhms 32 to 185 ºF / 0 to 85 ºC at rotor transmitter,
Accuracy (exclusive of AC content and noise effects from the Ambient Temperature
32 to 122 ºF / 0 to 50 ºC maximum at receiver
excitation system)
4320 RPM max (3600 RPM with up to 20%
Ground Fault Location Factor Rotor Speed
overspeed)
0 to 100% representing the ratio of the potential at
Receiver Power 85 to 250 VAC 50 / 60 Hz, <20 W
the ground fault to that of the total field voltage (0
Range
if the fault is at negative terminal; 100% at positive Receiver Ambient Tem- 32 to 122 ºF / 0 to 50 ºC; thermoelectric cooling is
terminal) perature available as an option
± 1% for a 10 kOhm fault and field
Accuracy
excitation ≥ 25 V
Receiver Alarm Outputs
© 2021 PCB Piezotronics - all rights reserved. PCB Piezotronics is a wholly-owned subsidiary of Amphenol Corporation. Endevco is an assumed name of PCB Piezotronics of North Carolina, Inc., which is a wholly-owned subsidiary of PCB Piezotronics,
Inc. Accumetrics, Inc. and The Modal Shop, Inc. are wholly-owned subsidiaries of PCB Piezotronics, Inc. IMI Sensors and Larson Davis are Divisions of PCB Piezotronics, Inc. Except for any third party marks for which attribution is provided herein, the
company names and product names used in this document may be the registered trademarks or unregistered trademarks of PCB Piezotronics, Inc., PCB Piezotronics of North Carolina, Inc. (d/b/a Endevco), The Modal Shop, Inc. or Accumetrics, Inc.
Detailed trademark ownership information is available at www.pcb.com/trademarkownership.
DS-0178 revA 1219