Professional Documents
Culture Documents
The General Specification for Lift, Escalator and Passenger Conveyor Installation
in Government Buildings of the Hong Kong Special Administrative Region 2017 Edition
(hereinafter referred to as “General Specification for Lift, Escalator and Passenger
Conveyor Installation 2017 edition”) is reviewed from time to time to ensure that
requirements stipulated in the document are clear, concise and in pace with technological
advancements.
Electronic version of the General Specification for Lift, Escalator and Passenger
Conveyor Installation 2017 edition incorporating Corrigendum No. GSLE01-2017 can be
viewed on the ArchSD Internet website.
(12/2019)
MAJOR CHANGES IN THE CORRIGENDUM (NO. GSLE01-2017) OF THE
GENERAL SPECIFICATION FOR LIFT, ESCALATOR AND PASSENGER CONVEYOR INSTALLATION
IN GOVERNMENT BUILDINGS OF THE HONG KONG SPECIAL ADMINISTRATIVE REGION
2017 EDITION
C10.15(a) C10.15(a) To replace “ have minimum dimension …… with an FRR of not less than one hour for door used as
emergency door, and …… with an FRR of not less than one hour for door used as inspection door;”
by “ have minimum dimension …… with an FRR of not less than that of the fire barriers therein
with regard to integrity, or not less than -/120/- for door used as emergency door, and …… with an
FRR of not less than that of the fire barriers therein with regard to integrity, or not less than -/120/-
for door used as inspection door;”
C25.5 C25.5 To replace “emergency electrical switch and push button with ……” by “emergency electrical
switch and push button installed outside the lift well with ……”
The following clauses are amended in the above edition of General Specification for Lift,
Escalator and Passenger Conveyor Installation.
Clauses
CAR ENCLOSURES
The fan shall be of quiet running type having a noise level not greater than 55
dBA when measured at a distance of 1 m from the fan and it shall be capable of
handling at least 20 air changes per hour of lift car volume, with car doors closed.
The effective area of ventilation apertures situated in the upper part of the car
shall be at least 1% of the available car area, and the same applies for any
apertures in the lower part of the car.
SECTION C10
Each car entrance shall be provided with an imperforated car door which shall
extend the full height and width of the car opening. The top track of the door shall
not obstruct the car entrance.
The LE Contractor shall provide lift doors that are constructed to satisfy the
criterion for integrity in accordance with BS 476 Part 20:1987 & Part 22:1987 (or
EN 81-58:2003 or EN 1634-1:2014 as appropriate) unless otherwise specified.
Any projections on or recesses in the exposed parts of the car doors or landing
doors shall be kept to a minimum in order to avoid finger trapping between sliding
parts of the door and any fixed part of the car or landing entrance.
For all automatic power operated horizontally sliding car doors, means shall be
provided to minimise the risk of dragging the children’s hands into the gaps
between the car door panels and uprights.
The clearance between panels or between panels and any fixed part of the car or
landing entrance shall not exceed 6 mm.
Sliding car and landing doors shall be guided on door tracks and sills for the full
Page 2 of 8 LE_GS 2017 Edition
Corrigendum GSLE01-2017
travel of the doors. The distance between the car and landing sills shall not exceed
35 mm.
The clear height of all entrances on car and landings shall not be less than 2 m.
SECTION C10
Where there is a long stretch of lift well without a landing door, an emergency
door shall be provided at a distance apart not exceeding 11000 mm for evacuating
the passengers. The inspection and emergency doors shall, unless otherwise
specified, be provided by others, except item (e), and the LE Contractor shall
coordinate with the party responsible for the work, to check and ensure that the
doors provided comply with the following:-
(a) have minimum dimension 1800 mm x 500 mm with an FRR of not less
than that of the fire barriers therein with regard to integrity, or not less
than -/120/- for door used as emergency door, and minimum dimension
1400 mm x 600 mm with an FRR of not less than that of the fire barriers
therein with regard to integrity, or not less than -/120/- for door used as
inspection door;
SECTION C12
The available car area, rated load and number of passengers shall be determined
from EN 81-1:1998 and EN 81-2:1998 (or EN 81-20:2014 and EN 81-50:2014.).
SECTION C17
CONTROLLER
The controller shall comply with the general requirements as stated in EN 81-
1:1998 or EN 81-20:2014 and EN 81-50:2014, and in particular, the following
features shall be included:-
SECTION C25
To cater for power failure and breakdown of the lift car, in addition to the
provision of emergency electrical switch in Clause C16.4 and the controls for
releasing the brake as described in Clause C16.5, the following facilities shall be
provided by the LE Contractor and be readily available for use by the rescue
personnel:
(a) Car lifting tool for moving the car in case it is stuck; and
A suitable lockable container for storage of the above facilities, together with
clear instructions on the method for releasing the brake and moving the lift car in
an emergency, shall be provided by the LE Contractor and placed inside the lift
equipment room/cabinet. The container shall bear on the outside face a notice
‘Emergency release operation shall only be undertaken by authorised person’.
SECTION D10
DRIVING MACHINERY
D10.4 SPEED
The rated speed of the escalator shall not be more than 0.75 m/s and 0.5 m/s for
an escalator with an angle of inclination not exceeding 30, and 35° with rise not
more than 6m from the horizontal respectively.
The rated speed of passenger conveyor shall not exceed 0.75 m/s. However, this
rated speed may be increased to 0.9 m/s maximum provided that:-
(a) the width of the pallets or the belt does not exceed 1100 mm; and
(b) at the landings, the pallets or the belt move horizontally for a length of at
least 1600 mm before entering the combs.
SECTION E1
(c) The clear platform floor area shall be at least 1100 mm x 1500 mm and
not exceed 2 m2;
SECTION F1
Ramps shall be fitted to the platform access edges, when folded up, to prevent
accidental wheelchair roll off. The ramps shall be raised and lowered electrically;
operated in sequence only when the platform is unfolded and at rest at a landing.
Drive system shall be electrically and mechanically interlocked with the ramps to
prevent the stairlift from moving unless the ramps are raised and to prevent the
ramps from lowering during the stairlift travelling.
The power system shall not, by injection of undesirable waveforms into the
electrical installation, adversely affect the connected electricity supply system
and/or the electricity supply to other users or consumers.
In addition to the requirements stipulated in Section B2, the electrical works shall
comply with the following requirements.
The control circuit voltage shall not exceed 50 V. All wiring and electrical parts
which are accessible without using any tools shall be at a potential of not
exceeding 24 V.
All secondary wiring shall be completed with numbered ferrules for identification
which shall be carried out in a neat and systematic manner and terminated at a
terminal board at the junction of small wiring and the incoming cables.
Electrical motors shall comply with IEC 60034-1:2017 and shall be of such size
and type to adequately drive the equipment under all normal conditions of service
without overloading. Insulation shall be of minimum Class F to IEC 60085:2007
for tropical conditions.
Motor starters shall be rated to intermittent class 0.1, 60% on-load factor and
utilisation category AC-3 in accordance with EN 60947-4-1:2010+A1:2012, or
equivalent. Suitably rated thermal overload relays shall be incorporated into each
starter circuit with inherent single-phase protection. Each starter shall incorporate
fuse protection.
SECTION G3
ANNEX IC
MAINTENANCE SCHEDULE
FOR ESCALATORS AND PASSENGER CONVEYORS
NOTES TO ANNEX IC
The lubricants used shall be of the brands and grades recommended by the
component manufacturer or their approved equivalents. Ensure adequate lubrication, but
avoid excess. Spillage shall be wiped off. Oily rags or waste shall be removed.
The following items are general guidance for the proper maintenance of the
escalator/passenger conveyor installation. These items are by no means exhaustive. The
maintenance personnel shall follow all instructions and guidelines as recommended by
their relevant manufacturer.
2. In long escalator with vertical rise greater than 15m, all drive chains shall
be replaced at intervals not exceeding 6 years of their services unless
otherwise stated by the chain manufacturer or escalator manufacturer.