TRANSFORMER SPECIFICATIONS

Compartmentalized, Pad-Mounted Transformer, Three Phase, Self-Cooled, Dead


Front or Live Front type, 60 Hz, 65 °C Temp Rise, Sealed-Tank type, Indoor/Outdoor
type, Built and Tested in accordance to applicable ANSI/IEEE/NEMA standards.

Capacity : As Required
Primary Voltage : 13,800 Volts, Delta
Taps 14,490, 14,145, 13,800, 13,155, 13,110 Volts
Primary BIL Rating : 95kV
Secondary Voltage : As Required
Multi-tap secondary side not allowed

Standard Accessories:

– (3) High Voltage Side Bushing, 15 kV, 200 Amps (Live Front/Dead Front)
– Low Voltage Bushings (Including Neutral) with spade terminals
– Bay-O-Net-Fuse for Overload Protection
– Externally Operated Tap changer for De-Energized operation
– Drain Valve, with oil sampling device in low voltage compartment
– Liquid Level Guage
– Upper fill plug
– Pressure Relief Device
– Non-PCB Fire Resistant Dielectric Coolant (Transformer Oil)
– (2) sets Ground Pads and Clamp with eye-bolt connector
– (4) Lifting and jacking pad provisions
– Diagrammatic Nameplate
– Divider provisions between high voltage & low voltage compartments
– External grounding for low voltage neutral
– Door stops
– Padlock provisions
– Hand hole (bolted cover for tank access)