Manufacturers Test Report

Date :- 27/12/2021

Raw Material Used Material Grade 012DB54 COLOR :-


OUTSIDE-
INSIDE -Black
HDPE DWC DUCT PIPE 63 mm Outer dia 51 mm Inner Dia in Coil 300mtr length
Product Description:- As per specification no. latest IS 16205 (Part-24) : 2017

Rudrax Polymers PVT LTD HDPE DWC PIPE OD/ID 63/51 MM AS PER IS
Marking Description:- 16205 Tm MASTODON

Client Name

1. Dimensions (Clause No. 8)

Requirements

Nominal Size 63MM


Outside Diameter 63 + 1.2mm
Inside Diameter Min. 47 Min.

Observation:

Sample No. Outside Diameter (MM) Inside Diameter (MM) Result


1 63.20 51.45 Passed
2 63.10 51.52 Passed
3 63.50 51.46 Passed
4 63.20 51.38 Passed
5 63.30 51.45 Passed
6 63.40 51.56 Passed
7 63.20 51.48 Passed
8 63.20 51.43 Passed
9 63.40 51.48 Passed
10 63.20 51.53 Passed
11 63.30 51.45 Passed
12 63.20 51.39 Passed
13 63.40 51.55 Passed
CONSTRUCTION ( Clause No. 9)

Requirement Pipe should be free from Sharp Edges Burrs or


surface projection etc.

S. No. Observation Result


1 No sharp edges, burrs or surface projections etc. Pass
2 No sharp edges, burrs or surface projections etc. Pass

2. MECHANICAL PROPERTIES ( Clause No. 10)


2.1 COMPRESSION TEST Clause No.10.2
Requirement
Specimen Length 200 ±5 mm
Applied Deflection (6.7 mm) 5 % of ID
Load Required (min.) 450 N
OBSERVATION

Specimen LOAD Result


(N)
1 580 Pass
2 590 Pass

2.2 IMPACT TEST ( Clause No. 10.3)

Requirement After the test there shall be no crack allowing ingress of light & water inside
and outside wall

Specimen Length 200 ±5 mm


Weight of Striker 5 Kg
Fall Height 800 mm
S. No. Observation Result
1 No crack allowing ingress of Pass
light & water in inside &
outside wall
2 No crack allowing ingress of Pass
light & water in inside &
outside wall

3.3 BENDING TEST ( Clause No. 10.4) at room temperature

Pipe shall not flatten when bent 90° at minimum bending radius 2000 mm. A
Requirement
sphere of diameter 95% declared of id of pipe should pass through at smoothly.
S. No. Observation N/A
1 Shall not be flatten N/A
2 Shall not be flatten N/A

3.4 BENDING TEST ( Clause No. 10.4) after conditions at -5° C

Pipe shall not flatten when bent 90° at minimum bending radius 2000 mm. A
Requirement
sphere of diameter 95% declared of id of pipe should pass through at smoothly.
S. No. Observation N/A
1 Shall not be flatten N/A
2 Shall not be flatten N/A

3.5 FIRE HAZARDS( Clause No. 13.1.2) as per IS 16205 Part-1

a) Flaming of the sample shall extinguished within 30s after removal of the flame.
Requirement b) The tissue paper should not ignite.
c)After extinction of the flaming of the sample, there shall no evidence of burning or
charring within 50mm of the lower
Extremity of the upper clamp.
Specimen length 675 ± 10 mm
S. Observation Result
No.
a) Flaming of the sample is extinguished within 30s after
removal of the flame. Pass
1
b) The tissue paper does not ignite.
c)The sample is not ignited by the flame

a) Flaming of the sample is extinguished within 30 s after Pass


removal of the flame.
2
b) The tissue paper does not ignite.
c)The sample is not ignited by the flame

Lab In-charge

For Rudrax Polymers Pvt Ltd