LOAD AND MOMENT COMPUTATIONS ON SLABS (Version 6)

PROJECT: PROPOSED THREE STOREY RESIDENTIAL BUILDING


LOCATION:
ARCHITECT:
STRUCTURAL:

DESIGN SPECIFICATIONS:
fc' = 20.7 MPa fy = 276 MPa

SLAB DESIGNATION : S-1A SLAB TYPE: TWO-WAY SLAB DESIGNATION : S-1B SLAB TYPE: ONE-WAY
Occupancy: RESIDENTIAL CASE NO.: 8 Occupancy: RESIDENTIAL SPAN TYPE: 4
Short Span, La = 4.210 m MOMENT COEFFICIENTS: Short Span, La = 2.260 m MOMENT COEFFICIENTS:
Long Span, Lb = 4.210 m Ca, neg = 0.033 Long Span, Lb = 5.030 m C, dis = N/A
Ratio,(m = La/Lb) = 1.000 Cb, neg = 0.061 Ratio,(m = La/Lb) = 0.449 C, mid = N/A
Minimum thickness, t = 94 mm Ca, pos dl = 0.020 Minimum thickness, t = FALSE mm C, con = N/A
Use thickness, t = 100 mm Cb, pos dl = 0.023 Use thickness, t = 100 mm
Use floor finish = 25 mm Ca, pos ll = 0.028 Use floor finish = 25 mm
LOAD DATA AND CALCULATIONS: Cb, pos ll = 0.030 LOAD DATA AND CALCULATIONS:
Liveload = 1.90 kPa MOMENTS: Liveload = 2.40 kPa MOMENTS:
Partition/Others = 0.60 kPa Ma, neg = 4.786 Partition/Others = 0.60 kPa M, dis #VALUE!
Slab Weight = 2.35 kN/m Ma, pos = 3.359 Slab Weight = 2.35 kN/m M, mid #VALUE!
Total Deadload = 3.54 kN/m 1/3 Ma, neg = 1.120 Total Deadload = 3.54 kN/m M, con #VALUE!
Factored wDL = 4.95 kN/m Mb, neg = 8.847 Factored wDL = 4.95 kN/m
Factored wLL = 3.23 kN/m Mb, pos = 3.736 Factored wLL = 4.08 kN/m
Total Factored wu = 8.18 kN/m 1/3 Mb, neg = 1.245 Total Factored wu = 9.03 kN/m
SHEAR COEFFICIENTS: CHECK FOR SHEAR: SHEAR COEFFICIENTS: CHECK FOR SHEAR:
Wa = 0.330 Va (kN)= 5.68 Wa = 1.000 Va (kN)= 10.21
Wb = 0.670 Vb (kN)= 11.54 Wb = 0.000 Vb (kN)= 0.00
fVc = 26.104 kN Ok for Shear! fVc = 26.104 kN Ok for Shear!
LOADS TRANSMITTED TO BEAMS: (kN/m) LOADS TRANSMITTED TO BEAMS: (kN/m)
Short span, wDL = 2.46 Long span, wDL = 4.99 Short span, wDL = 4.00 Long span, wDL = 0.00
Short span, wLL = 1.32 Long span, wLL = 2.68 Short span, wLL = 2.71 Long span, wLL = 0.00
Short span, wu = 5.68 Long span, wu = 11.54 Short span, wu = 10.21 Long span, wu = 0.00

SLAB DESIGNATION : S-1C SLAB TYPE: TWO-WAY SLAB DESIGNATION : S-1D SLAB TYPE: TWO-WAY
Occupancy: residential CASE NO.: 9 Occupancy: residential CASE NO.: 3
Short Span, La = 2.610 m MOMENT COEFFICIENTS: Short Span, La = 2.210 m MOMENT COEFFICIENTS:
Long Span, Lb = 5.030 m Ca, neg = 0.088 Long Span, Lb = 3.970 m Ca, neg = 0.000
Ratio,(m = La/Lb) = 0.519 Cb, neg = 0.003 Ratio,(m = La/Lb) = 0.557 Cb, neg = 0.028
Minimum thickness, t = 85 mm Ca, pos dl = 0.038 Minimum thickness, t = 69 mm Ca, pos dl = 0.071
Use thickness, t = 100 mm Cb, pos dl = 0.002 Use thickness, t = 100 mm Cb, pos dl = 0.009
Use floor finish = 25 mm Ca, pos ll = 0.067 Use floor finish = 25 mm Ca, pos ll = 0.080
LOAD DATA AND CALCULATIONS: Cb, pos ll = 0.004 LOAD DATA AND CALCULATIONS: Cb, pos ll = 0.009
Liveload = 2.40 kPa MOMENTS: Liveload = 2.40 kPa MOMENTS:
Partition/Others = 0.60 kPa Ma, neg = 5.415 Partition/Others = 0.60 kPa Ma, neg = 0.000
Slab Weight = 2.35 kN/m Ma, pos = 3.144 Slab Weight = 2.35 kN/m Ma, pos = 3.312
Total Deadload = 3.54 kN/m 1/3 Ma, neg = 1.048 Total Deadload = 3.54 kN/m 1/3 Ma, neg = 1.104
Factored wDL = 4.95 kN/m Mb, neg = 0.686 Factored wDL = 4.95 kN/m Mb, neg = 3.986
Factored wLL = 4.08 kN/m Mb, pos = 0.664 Factored wLL = 4.08 kN/m Mb, pos = 1.281
Total Factored wu = 9.03 kN/m 1/3 Mb, neg = 0.221 Total Factored wu = 9.03 kN/m 1/3 Mb, neg = 0.427
SHEAR COEFFICIENTS: CHECK FOR SHEAR: SHEAR COEFFICIENTS: CHECK FOR SHEAR:
Wa = 0.970 Va (kN)= 11.43 Wa = 0.690 Va (kN)= 6.89
Wb = 0.030 Vb (kN)= 0.68 Wb = 0.310 Vb (kN)= 5.56
fVc = 26.104 kN Ok for Shear! fVc = 26.104 kN Ok for Shear!
LOADS TRANSMITTED TO BEAMS: (kN/m) LOADS TRANSMITTED TO BEAMS: (kN/m)
Short span, wDL = 4.48 Long span, wDL = 0.27 Short span, wDL = 2.70 Long span, wDL = 2.18
Short span, wLL = 3.04 Long span, wLL = 0.18 Short span, wLL = 1.83 Long span, wLL = 1.48
Short span, wu = 11.43 Long span, wu = 0.68 Short span, wu = 6.89 Long span, wu = 5.56