LOAD AND MOMENT COMPUTATIONS OF FLOOR SLABS

PROJECT: PROPOSED TWO-STOREY RESIDENTIAL BUILDING


LOCATION: San Vicente, Lilo-an, Cebu

DESIGN SPECIFICATIONS:
fc' = 20.7 MPa fy = 276 MPa

SLAB DESIGNATION : SLAB SLAB TYPE: TWO-WAY SLAB DESIGNATION : SLAB SLAB TYPE: TWO-WAY
Occupancy: Residential CASE NO.: 2 Occupancy: Residential CASE NO.: 9
Short Span, La = 3.000 m MOMENT COEFFICIENTS: Short Span, La = 3.000 m MOMENT COEFFICIENTS:
Long Span, Lb = 3.000 m Ca, neg = 0.045 Long Span, Lb = 3.000 m Ca, neg = 0.061
Ratio,(m = La/Lb) = 1.000 Cb, neg = 0.045 Ratio,(m = La/Lb) = 1.000 Cb, neg = 0.033
Minimum thickness, t = 67 mm Ca, pos dl = 0.018 Minimum thickness, t = 67 mm Ca, pos dl = 0.023
Use thickness, t = 100 mm Cb, pos dl = 0.018 Use thickness, t = 100 mm Cb, pos dl = 0.020
Use floor finish = 25 mm Ca, pos ll = 0.027 Use floor finish = 25 mm Ca, pos ll = 0.030
LOAD DATA AND CALCULATIONS: Cb, pos ll = 0.027 LOAD DATA AND CALCULATIONS: Cb, pos ll = 0.028
Liveload = 1.90 kPa MOMENTS: Liveload = 1.90 kPa MOMENTS:
Partition/Others = 1.40 kPa Ma, neg = 3.768 Partition/Others = 1.40 kPa Ma, neg = 5.107
Slab Weight = 2.35 kN/m Ma, pos = 1.769 Slab Weight = 2.35 kN/m Ma, pos = 2.129
Total Deadload = 4.34 kN/m 1/3 Ma, neg = 0.590 Total Deadload = 4.34 kN/m 1/3 Ma, neg = 0.710
Factored wDL = 6.07 kN/m Mb, neg = 3.768 Factored wDL = 6.07 kN/m Mb, neg = 2.763
Factored wLL = 3.23 kN/m Mb, pos = 1.769 Factored wLL = 3.23 kN/m Mb, pos = 1.907
Total Factored wu = 9.30 kN/m 1/3 Mb, neg = 0.590 Total Factored wu = 9.30 kN/m 1/3 Mb, neg = 0.636
SHEAR COEFFICIENTS: CHECK FOR SHEAR: SHEAR COEFFICIENTS: CHECK FOR SHEAR:
Wa = 0.500 Va (kN)= 6.98 Wa = 0.670 Va (kN)= 9.35
Wb = 0.500 Vb (kN)= 6.98 Wb = 0.330 Vb (kN)= 4.60
φVc = 26.104 kN Ok for Shear! φVc = 26.104 kN Ok for Shear!
LOADS TRANSMITTED TO BEAMS: (kN/m) LOADS TRANSMITTED TO BEAMS: (kN/m)
Short span, wDL = 3.25 Long span, wDL = 3.25 Short span, wDL = 4.36 Long span, wDL = 2.15
Short span, wLL = 1.43 Long span, wLL = 1.43 Short span, wLL = 1.91 Long span, wLL = 0.94
Short span, wu = 6.98 Long span, wu = 6.98 Short span, wu = 9.35 Long span, wu = 4.60

SLAB DESIGNATION : SLAB SLAB TYPE: ONE-WAY SLAB DESIGNATION : SLAB TYPE:
Occupancy: Residential SPAN TYPE: B Occupancy: SPAN TYPE:
Short Span, La = 1.350 m MOMENT COEFFICIENTS: Short Span, La = m MOMENT COEFFICIENTS:
Long Span, Lb = 3.000 m C, dis = 0.042 Long Span, Lb = m C, dis = N/A
Ratio,(m = La/Lb) = 0.450 C, mid = 0.071 Ratio,(m = La/Lb) = C, mid = N/A
Minimum thickness, t = 45 mm C, con = 0.100 Minimum thickness, t = mm C, con = N/A
Use thickness, t = 100 mm Use thickness, t = mm
Use floor finish = 25 mm Use floor finish = mm
LOAD DATA AND CALCULATIONS: LOAD DATA AND CALCULATIONS:
Liveload = 1.90 kPa MOMENTS: Liveload = kPa MOMENTS:
Partition/Others = 1.40 kPa M, dis 0.706 Partition/Others = kPa M, dis
Slab Weight = 2.35 kN/m M, mid 1.211 Slab Weight = 0.00 kN/m M, mid
Total Deadload = 4.34 kN/m M, con 1.695 Total Deadload = 0.00 kN/m M, con
Factored wDL = 6.07 kN/m Factored wDL = 0.00 kN/m
Factored wLL = 3.23 kN/m Factored wLL = 0.00 kN/m
Total Factored wu = 9.30 kN/m Total Factored wu = 0.00 kN/m
SHEAR COEFFICIENTS: CHECK FOR SHEAR: SHEAR COEFFICIENTS: CHECK FOR SHEAR:
Wa = 1.000 Va (kN)= 6.28 Wa = 1.000 Va (kN)= 0.00
Wb = 0.000 Vb (kN)= 0.00 Wb = 0.000 Vb (kN)= 0.00
φVc = 26.104 kN Ok for Shear! φVc = -8.701 kN
LOADS TRANSMITTED TO BEAMS: (kN/m) LOADS TRANSMITTED TO BEAMS: (kN/m)
Short span, wDL = 2.93 Long span, wDL = 0.00 Short span, wDL = 0.00 Long span, wDL = 0.00
Short span, wLL = 1.28 Long span, wLL = 0.00 Short span, wLL = 0.00 Long span, wLL = 0.00
Short span, wu = 6.28 Long span, wu = 0.00 Short span, wu = 0.00 Long span, wu = 0.00
DESIGN OF FLOOR SLABS

PROJECT: PROPOSED TWO-STOREY RESIDENTIAL BUILDING


LOCATION: San Vicente, Lilo-an, Cebu

LEVEL: SECOND

Design Specifications:
fc' = 20.7 MPa bar d = 10 mm Ab = 79 mm2
fy = 276 MPa min ρ = 0.00507

MARK SECTION Slab type t (mm) Mu (kN.m) d (mm) Ru (Mpa) req'd ρ use ρ As (mm2) Ast (mm2) sreq'd. (mm) smax (mm) use s (mm)

SLAB Ma, neg = two way 100 3.768 75 0.744 0.00276 0.00367 276 200 285 300 285
Ma, pos = 1.769 75 0.349 0.00128 0.00170 128 200 393 300 300
1/3 Ma, neg = 0.590 75 0.116 0.00042 0.00056 42 200 393 300 300
Mb, neg = 3.768 65 0.991 0.00370 0.00493 320 200 245 300 245
Mb, pos = 1.769 65 0.465 0.00171 0.00228 148 200 393 300 300
1/3 Mb, neg = 0.590 65 0.155 0.00056 0.00075 49 200 393 300 300

SLAB Ma, neg = two way 100 5.107 75 1.009 0.00377 0.00502 377 200 209 300 209
Ma, pos = 2.129 75 0.421 0.00154 0.00206 154 200 393 300 300
1/3 Ma, neg = 0.710 75 0.140 0.00051 0.00068 51 200 393 300 300
Mb, neg = 2.763 65 0.727 0.00269 0.00359 233 200 337 300 300
Mb, pos = 1.907 65 0.502 0.00184 0.00246 160 200 393 300 300
1/3 Mb, neg = 0.636 65 0.167 0.00061 0.00081 53 200 393 300 300

SLAB M, dis one way 100 0.706 75 0.140 0.00051 0.00068 51 200 393 300 300
M, mid 1.211 75 0.239 0.00087 0.00116 87 200 393 300 300
M, con 1.695 75 0.335 0.00123 0.00163 123 200 393 300 300
0.000 65 0.000 0.00000 0.00000 0 200 393 300 300
0.000 65 0.000 0.00000 0.00000 0 200 393 300 300
0.000 65 0.000 0.00000 0.00000 0 200 393 300 300