Professional Documents
Culture Documents
SIEMENS
.c
Vacuum Circuit Breaker Instructions
Installation
Operator Module
ls
Operation
Maintenance
Type 3AH
ua
SGIM-99180
4.16kV to 38kV
an
tM
ar
lP
ca
tri
lec
Medium-Voltage
Equipment
.E
w
ww
om
A DANGER
.c
Hazardous voltages and high-speed moving parts.
ls
q u al ified person nel.
ua
the equ ipment.
an
IMPORTANT
The information contained herein is genera l in natu re and not intended for
specific application purposes. It does not relieve the user of responsibility to
use sound practices in a pplication, installation, operation, and maintenance
tM
of the e q uipment purchased. Siemens reserves the right to make cha nges in
the specifications shown herein or to make im provements at any time without
notice or obligations. Should a conflict a rise between the genera l information
contained in this publication and the contents of drawings or supplementary
material or both, the latter shall take precedence.
ar
QUALIFIED PERSON
lP
SUMMARY
lec
The contents of this instruction m a n u a l sha l l not become part of or mod ify any
prior or existing agreement, commitment or relationship. The sales contract
contains the entire obligation of Siemens Energy, Inc. The warranty conta ined
in the contract between the parties is the sole warranty of Siemens Energy,
I nc. Any statements contained herein do not create new warranties or mod ify
the existing warranty.
w
ww
om
Vacuum Circuit Breaker Operator Module
.c
Table of Contents
ls
Recommended HandTools .......................................................19
Introduction and Safety ........................................................3 Recommended Maintenance and Lubrication .........................19
Introduction ...............................................................................3 Checks of the Primary Power Path ...........................................20
Qualified Person ........................................................................3 Cleanliness Check ....................................................................20
ua
Signal Words .............................................................................3 Inspection of Flexible Connectors ............................................20
Dangerous Procedures ..............................................................3 Checks of the Stored Energy Operator Mechanism ................20
Field Service Operation .............................................................3 Maintenance and Lubrication ..................................................20
Receiving, Handling and Storage 4 Fastener Check .........................................................................22
...............................................................................4
....................................... ..
an
Check of the Wirin andTerminals ...........................................23
������� ���=�� � ���� -����� -���� �· ·�- -��..·.·.·.·.·.·:.·:..'· .'.'.'.'.'..'.·.'.·.'..' '..' .' '.t"
�
i i a �
C
���:�� �g��� :����S �����............... ... . ......................
r Au
Storage Procedure ....................................................................4 ( R
Electrical Close and Trip Check
.. . . 23
Installation Checks and Initial Functional Tests ..................5 (Control Power Required) ......................................................25
Introduction ...............................................................................5 Checks of the Spring Charging Motor (88) ...............................25
tM
Inspections. Checks andTests without Control Power .............5 Vacuum Interrupters .................................................................25
Spring Discharge Check (Figure 1) ............................................5 Vacuum Integrity Check (using Mechanical Test) (Figure 18)....25
Manual Spring Charging Check ................................................5 High-Potential Tests ..................................................................25
As-Found and Vacuum CheckTests ...........................................5 Vacuum Integrity Check (using DielectricTest) .........................25
Automatic Spring Charging Check ............................................5 High Potential Test Voltages .....................................................25
Final Mechanical Inspections without Control Power ...............5 Vacuum Integrity Test Procedure ..............................................26
ar
Vacuum Interrupter/Operator Description . & ........ .................
As-Found Insulation and Contact Resistance Tests ................. 26
Insulation and Contact Resistance Test Equipment ................. 26
Introduction ...............................................................................6 Insulation and Contact Resistance Test Procedure .................. 27
Vacuum Interrupters .................................................................7
Primary Disconnects (Figure 4) . ............... ................................
.?
Inspection and Cleaning of Circuit Breaker Insulation ............. 27
FunctionalTests ........................................................................27
Phase Barriers ..........................................................................7
.. . ... .. ............ ... ........
lP
!l.OVer ::>l:JIIVI-!:I!:IHl-UI
om
Vacuum Circuit Breaker Operator Module
.c
Table of Illustrations
Figures Tables
Figure 1 Front Panel Controls of Circuit Breaker Table 1 Maintenance Tasks ............................................ 20
ls
and Manual Charging of Closing Spring ............. 5
Table 2 Maintenance and Lubrication Intervals
Figure 2 Vacuum Circuit Breaker Module .......................... 6 (ANSI C37.06) .................................................... 20
Figure 3 Cutaway View of Vacuum Interrupter .................. 7 Table 3 Typical Vacuum Interrupter Contact
ua
Figure 4 Vacuum Interrupter /Operating Life Expectancy ................................................. 23
Mechanism Module ............................................ 7 Table 4 High PotentiaiTest Voltages .............................. 25
Figure 5 Pole Assembly ..................................................... 8 Table 5 Maximum Contact Resistance .......................... 27
Figure 6a Stored Energy Operating Mechanism ...................... 9 Table 6 Overhaul Schedule ............................................ 28
Figure 6b Stored Energy Operating Mechanism ..................... 10 Table 7 Vacuum Interrupter Stroke ............................... 32
an
Figure 7a-b Operating Mechanism Section Diagram .............. 12 Table 8 Troubleshooting .............................................. 33-34
Figure 7c-d Operating Mechanism Section Diagram .............. 13
Figure 8 Operator Sequential Operation Diagram ............ 14
Appendix
Figure 9a-b Use of Manual Spring Charging Crank ................ 15
Table A-1 a 3AH Circuit Breaker Ratings
tM
Figure 10Typical Elementary Diagram ..................................... 16 (Historic "Constant MVff Rating Basis) ..................... 35
Figure 11 Construction of Secondary Shunt Release .............. 17 Table A-1 b 3AH Circuit Breaker Ratings
Figure 12 Latch Details 18
............................................................
(New "Constant kA" Rating Basis) .............................. 36
Figure 13 Undervoltage Locked/Unlocked Selection .............. 18 Table A-2 3AH Circuit Breaker Ratings ................................... 37
Figure 14 Capacitor Trip Device ............................................... 18 Table A-3 Interrupting Capacity of Circuit Breaker
ar
Auxiliary Switch Contacts ........................................... 37
Figure 15 Operator Lubrication Points ..................................... 21
Table A-4 Circuit Breaker Weights .......................................... 37
Figure 16 Contact Erosion Check Mark ................................... 22
Figure 17Typica1Vacuum Interrupter Contact Life Curves ....... 24
lP
2
om
Introduction and Safety
.c
Introduction Signal Words
The 3AH family of vacuum circuit breakers is designed to The signal words "Danger:"'Warningn and "Cautionn used
meet a l l the applicable ANSI, N EMA a n d IEEE standards. in this manual ind icate the degree of hazard that may be
Successful a pplication and operation of this equipment de encountered by the user. These words are defined as:
pends as much upon proper installation a n d maintenance by
the user as it does upon the careful design and fabrication Danger - Indicates an imminently hazardous situation
ls
by Siemens. which, if not avoided, will result in death or serious
injury.
The pu rpose of this Instruction Manual is to assist the user Warning - Indicates a potentially hazardous situation
ua
in developing safe and efficient procedures for the installa which, if not avoided, could result in death or serious
tion, ma intena nce and use of the equ ipment. inj u ry.
NOTE: IEEE Standards Requ irements for Conversion of Caution - indicates a potentially hazardous situation
Power Switchgear Equ ipment ( C37.59); Siemens has devel which, if not avoided, may result in minor or moderate
an
oped instruction manuals for particular replacement circuit inj u ry.
breaker drawout vehicles, consult factory.
Dangerous Procedures
Contact the nearest Siemens representative if a ny a d d itional In addition to other procedu res described in th is manual as
information is desired. dangerous, user personnel must adhere to the following:
A DANGER
Hazardous voltages and high-speed
moving parts.
tM
1. Always work on de-energized equ ipment. Always d e-ener
g ize a circuit breaker, a n d remove it from the switchgear
before perform ing any tests, ma intenance or repair.
ar
Will cause death, personal injury or
property damage.
2. Always perform maintenance on the circuit breaker after
Only qualified persons thoroughly fa miliar the spring-charged mechanisms are discharged.
with the equipment, instruction m a n uals and
lP
Qualified Person
For the pu rpose of th is manual a Qualified Person is one Field Service Operation
who is familiar with the installation, construction or opera Siemens can provide competent, well-trained Field Service
tion of the equipment and the hazards involved. In addition, Representatives to provide technical g u id ance a n d advisory
this person has the following qualifications: assistance for the installation, overhaul, repair and main
tri
•Tra ining in the proper care and use of protective equ ip
ment such as rubber gloves, hard hat, safety glasses, face
shields, flash clothing, etc., in accord a nce with estab
lished safety procedures.
3
om
Receiving, Handling and Storage
.c
Introduction
This manual covers the Receiving, Handl ing and Storage A WARNING
instructions forType 3AH vacu um circuit breakers shipped
Heavy weight. Can cause death, serious
separately from the switchgear. This section of the m anual injury, or property damage.
is intended to help the user identify, inspect and protect the
Use of a q u a lified rigger to hoist the circ u it
circuit breaker prior to its installation.
ls
b reaker.
Receiving Procedure
M a ke a physical inspection of the sh ipping container before
Circuit breaker weights (Table A-4) .
ua
removing or unpacking the circuit breaker. Check for ship
ment d a m a g e or indications of rough h andling by the carrier.
4.The palleted circuit breaker can also be moved using a
Check each item against the manifest to identify any short
properly rated fork-lift vehicle. The pallets are designed
ages.
for movement by a standard fork-lift vehicle.
an
Accessories such as the manual charging crank, the racking
Storage Procedure
crank and the split plug jumper are shipped separately.
ment damage.
When no other option is available, the circuit breaker m ust
be completely covered and protected from ra in, snow, dirt
4. Arrange for carrier's inspection. Do not move the unit
and all other contaminants.
from its unloading point.
ca
claims.
4
om
Installation Checks and Initial FunctionaiTests
Introduction
.c
This section provides a description of the inspections,
checks and tests to be performed on the circuit breaker
module only.
ls
primary contacts open and their springs d ischa rged. How
ever, it is critical to first verify the discharged condition of
the spring-loaded mechanisms after de-energizing control
ua
power.
an
The spring discharge check consists of simply performing
the following tasks in the order g iven. This check assures
that both the opening and closing springs are fully dis
charged.
A DANGER
Hazardous voltages and high-speed
moving parts.
tMFigure 1. Front Panel Controls of Circuit Breaker and
Manual Charging of Closing Spring
1. Press red Open push button. The automatic spring charging features of the circuit breaker
must be checked. Control power is required for automatic
ca
3. Again press red Open pushbutton. 1. Open control power circuit by opening the control power
disconnect device.
4. Verify Spring Condition Indicator shows DISCHARGED.
tri
5
om
Vacuum Interrupter/Operator Description
.c
Introduction
The Type 3AH vacu u m circuit breaker operator is intended connect the circuit breaker to both primary and control
for application in a d rawout truck for use in medium voltage power and an operator housing. In a typical installation in
metal-clad switchgear. The 3AH circuit breaker conforms a drawout truck, insulating barriers a re located between the
to the requirements of ANSI Standards, including C37.20.2, vacuum interrupters and along the sides.
C37.04, C37.06, C37.09 and C37.010.
ls
This section describes the operation of each major subas
The circuit breaker consist of three vacuum interrupters, a sembly as an aid in the operation, instal lation, maintenance
stored energy operating mechanism, necessary electrical and repair of the circuit breaker.
ua
control s and interlock devices, disconnect devices to
an
.------ Pole Plate
Pole Bottom-----'
'--- Insu lating Coupler
6
om
Vacuum Interrupter/Operator Description
.c
RxedContact
current
connection-------..
Ceramic
ls
lnsiJator --�
ua
FIXed
an
Contact
Moving
Contact------
Ceranic
lnsuahr -----"'
Metal
tM
ar
Bellov.s-------./
Figure 4. Vacuum Interrupter/Operating Mechanism Module
Guide _____ ./
movable contact is connected to the pole bottom and driv breaker is an integrated arrangement of springs, coils and
ing mechanism of the circuit breaker. The metal bellows mechanical devices designed to provide a number of critical
provide a secure seal around the movable contact, prevent functions. The energy necessary to close and open the con
ing loss of vacu um while permitting vertical motion of the tacts of the vacu um interrupters is stored in powerful open
movable contact. ing and closing springs. These springs are normally charged
.E
achieve arc motion and to minimize switching disturbances. Vacuum Interrupter/Operator Module
The vacu u m interrupter/operator module consists of the
three poles, each with its vacuu m interrupters and primary
ww
7
om
Vacuum Interrupter/Operator Description
.c
Each of the circuit breaker poles a re fixed to the rear of the T h e current-path assembly consists of t h e pole h e a d , the
operating mech a n ism housing by two cast-resin insulators. stationary contact, and the moving contact, which is con
The i n sulators also connect to the upper and lower pole nected to the pole bottom by a term i n a l clamp and a flexible
supports which in turn support the ends of the vacuum inter connector.
rupter. The pole supports are aluminum castings ( 1 200A a n d
2000A) or copper castings (3000A). Primary stud extensions Vacuum Interrupter (Figure 5 )
ls
may be attached d irectly to the uppe r and lower pole sup T h e moving contact motion is a l i g n e d and stabil ized b y a
ports. guide bushing. The metal bellows fol l ows the travel of the
contact and seals the vacuum interrupter against the sur
ua
The energy-stori ng mecha nism and all the control and rounding atmosphere.
actuating d evices are instal led in the mechan ism housing.
The mecha nism is of the spring stored energy type and is Switching Operation (Figures 5 and 6a)
mech a n ically and electrically trip free. When a closing command is initiated, the closing spring
(62). which was previously charg ed by h a n d or by the mo
an
The close-open i n d icator, closing spring charge ind icator, tor, a ctuates the moving contact through the jack shaft (63),
a n d the operation counter are located on the front of the lever, contact pressure spring (49), insulating coupler (48),
mechanism housing. and angled lever.
The control connector for the control and sig nalling cables is The forces that occur when the action of the insulating cou
tM
a multi contact plug. pler (48) is converted into the vertical action of the moving
contact are a bsorbed by the guide l in k, wh ich pivots on the
pole bottom and the eye bolt.
PdeBotto m--------f 1. Charge the closing spring with sufficient potential energy
to close the circuit breaker a n d to store opening energy
.E
tions and the contact pressure are absorbed by the struts. 5. Provide indication of the circuit breaker status (open/
closed), spring condition (charged/discharged). and
number of operations.
8
om
Vacuum Interrupter/Operator Description
.c
62.5
50.5 50.3 62.6
50.2
ls
62.1
ua
62.2
an
55.1
62
tM
.1
50.4.1
62.8.1
ar
55
lP
58
ca
63.7
59
tri
lec
Figure 6a. Stored Energy Operating Mechanism (Circuit Breaker Shown in Open Position)
9
om
Vacuum Interrupter/Operator Description
.c
ls
ua
54
an
64.2
tM
ar
lP
ca
tri
lec
Figure 6b. Stored Energy Operating M echanism (Circuit Breaker Shown in Closed Positio n )
10
om
Vacuum Interrupter/Operator Description
.c
Construction As the closing spring d ischarges, th e ch arging shaft (62.1 ) is
The essential parts of the operating mecha nism are shown turned by crank (62.2). The cam d isc (62.3) at the other e n d
in Figures 6a and 6b. The control and sequence of operation o f t h e charging shaft actuates t h e d rive lever (62.6), with th e
of the mechanism is described in Figure 8. result that jack shaft (63) is turned by lever (63.5) via the trip
free cou pling rod (62.8). At the same time, the levers (63.1 ) ,
Motor Operating Mechanism (Figure 6a) (63.5) a n d (63.7) fixed on t h e jack s h a ft operate the three in
ls
Th e spring ch arging motor (50.4) is bolted to the charg i n g sulating couplers (48) (Figure 5) for the circuit breaker poles.
mechan ism (50.2) gear box instal led in t h e operator housing. Lever (63.7) cha nges the Open-close ind icator (58) over to
Neither the charging mech anism nor the motor require any Open. Lever (63.5) charges the opening spring (64) d u r-
ua
maintenance. i n g closing, a n d the circuit breaker is latched in the closed
position by lever (64.3) with pawl rol ler (64.3.1 ) and by pawl
Mode of Operation (64.2). Lever (63.1 ) actuates the a uxiliary switch (68) th rou g h
The operating mechanism is of the stored-energy trip free t h e linkage (68.1 ) .
type, i.e., the charging of the closing spri n g is not a utomati
an
cally followed by the contacts cha n g i n g position, a n d the Th e crank (62.2) o n the charg i n g shaft (62.1 ) moves the link
closing function may be overridden by an opening com age (55.1 ) by acting on the control lever (55.2). The closing
mand at any time. spring charged ind ication is thus canceled, and the l imit
switches (50.4) switch in the control su pply to cause the
When the stored-energy mechan ism has been charged, the closing spri n g to recha rge immediately.
tM
instant of operation can be chosen as d esired.
Trip Free Operation (Figures 6a and 6b)
The mechanical energy for carrying out a n "open-close The trip free coupling rod (62.8) permits th e immediate
open" sequence for auto-reclosing d uty is stored in the clos decoupling of the d rive lever (62.6) a n d the jack s h aft (63) to
ing and opening springs. override closing action by trip command or by means of the
ar
racking interlocks.
Charging
The details of th e closing spring cha rging mechanism are The trip free coupling rod (62.8) forms a link between the
shown in Figure 6a. The ch a rg i n g shaft is supported in the drive lever (62.6) and the jack shaft (63). The rigidity of this
lP
charging mechanism (50.2), but is not coupled mech a n i link depends upon a spring return latch (62.8.1 ) carried
cally with the charg i n g mech a n ism. Fitted to it are the cra n k within the coupling rod. The latch pivots within the cou pling
(62.2) a t one end, and t h e c a m (62.3), together with lever rod a n d is norm a l ly positioned to ensure the rigidity of the
(62.5), at the other. coupling rod. Trip free coupling link (62.8.2) and trip free
ca
charg i n g shaft to follow. The cra n k (62.2) charges the closing effectively decou pling the d rive lever and jack shaft. U nder
spring (62). When the closing spring has been fully cha rged, these conditions the vacuum interrupter contacts cannot be
the cra n k actuates the linkage ( 55.1 ) via the control lever closed.
(55.2) for the "closing spring cha rg e d " ind icator (55), a n d
lec
The opening spring (64) turns the jack shaft (63) via lever
Closing (Figures 6a, 6b and 7 a - 7 d) (63.5); the sequence being similar to that for closing.
If the circ u it breaker is to be closed locally, th e closing spri ng
is released by pressing the CLOSE button (53) . I n th e case
of remote control, the close coil 52SRC (53.1 ) unlatches th e
closing spring (62).
w
ww
11
om
Vacuum Interrupter/Operator Description
.c
50.3.1 Driver 62.5.1 Pawl roller 63.5 Lever-phase B
53 Close pushbutton 62.5.2 Close l atch pawl 63. 7 Lever-phase A
53.1 "Close coil, 52SRC" 62.6 Drive lever 64. Opening spring
54 Open pushbutton 62.8 Trip free coupling rod 64.2 Trip l atch pawl
54.1 "Trip coil, 52T" 62.8.2 Trip free coupling l i n k (Draw bar) 64.2.1 Trip latch pin
62.1 Charging shaft 62.8.3 Trip free coupling lever 64.2.2 Latching pawl release lever
ls
62.2 Cra n k 62.8.5 Push rod & cam assembly 64.3 Lever
62.2.2 Closing spring mounting 62.8.6 Interlock l ever-push rod 64.3.1 Jack shaft pawl
62.8.1 Spring return latch 62.8.7 Interlock lever-actuator 64.5 Opening spring shaft
ua
62.8.2 Trip free draw bar 62.8.8 Trip free actuator
an
tM
ar
lP
ca
tri
lec
.E
w
ww
Figure 7a. Operating M echa n ism Section Diagram Figure 7b. Operating Mech a n ism Section Diagra m Operat
Operating Mech a n ism Open, Closing Spring Discharged ing Mechanism Open, Closing Spri ng Charged
* Items changed from 7c on 'Trip' Operation) (Underlined items * Items changed from 7d o n 'Trip' Operation) (Underlined items
changed from 7b on 'Closed Spring Discharge' Operation) changed from 7a on 'Closed Spring Cha rge' Operation)
12
om
Vacuum Interrupter/Operator Description
.c
62.5.2 Close latch pawl 62.8.6 Interlock lever-push rod 64.2.1 Trip latch pin
62.8.1 Spring return latch 62.8.7 Interlock lever-actuator 64.2.2 Latchi n g pawl release lever
62.8.2Trip free d raw bar 62.8.8Trip free actuator 64.3 Lever
62.8.3Trip free lever 63.5 Lever-phase 8 64.3.1 Jack shaft pawl
62.8.5 Push rod & cam assembly 64 Opening spring 64.5 Opening spring shaft
ls
62.5. 1
ua
an
tM
ar
lP
ca
tri
lec
.E
• I
.L J.
Figure 7 c. Operating Mechan ism Section Diagram Figure 7 d. Operating M echa n ism Section Diagram Op
w
M echan ism Closed, Closing Spring Discharged erating Mechanism Closed, Closing Spring Charged
(Callout items changed from 7b on 'Circuit Breaker Close' Opera (Callout items changed from 7c o n 'Closing Spring Charge' Opera
tion) tion)
ww
13
om
Vacuum Interrupter/Operator Description
.c
Elementary Diagram (Figure 10)
A typical elementary diagram is shown in Figure 10 for DC motor, close and trip operation.
ls
Symbd List
ua
J-
88 Sprirg Chargirg Motor
(+)
01 52SRC CloseCol
1' S'Z'( Closirg Relay (Ant�purrp)
2J
c 52T Trip Coi l
LS Sprirg Charged Lin it Switch
tJI Mecharlcallnte�ock
52a Aux. Sw. OpenWhenC irOJit B"eBkBr is O
52b Aux. Sw. Closed WhBnCircuit B'eaker i; Qpen
an
Red ln:li:ati1g Lgtt (Closed) Typical
r:t:·
A
G Greenlroi:ati1glgtt(Trip) Pemote
W Wtite lndicatirg Ught (Spri1g Ct"arged) Devi:es
tl11C C ont d Switch
31 t'ltfT C ontd Switch (Trip )
Slb
�
iXoD2��·-
"'
tM
::>
"'
<.)
c
X007
52a
ar
52> Slb
53 Ill
Xo011
lP
��------�---4�-
Shown with springs discharged, trip latch reset, circuit breaker open and located i1 test co meet, o rwithdrawnposition.
tri
16
om
Vacuum Interrupter/Operator Description
.c
The close coil (3AY1 510) is a standard component of the
11 21 25 27 7 31
circuit breaker which is used to unlatch the stored energy of
the closing spring and thus close the circuit breaker elec
trically. It is available for both AC and DC operation. After
com pletion of a closing operation, the close coil is de-en
ergized internally. If operated with AC voltage, a rectifier is
ls
insta l led in the circuit breaker.
ua
breaker. The electrically supplied tripping signal is passed on
to the trip latch ing mecha nism by means of a d i rect action
solenoid armature and the circuit beaker is thus opened. It is
availabl e for both AC a n d DC operation. After completion of
an opening operation, the trip coil is de-energized i nternally.
an
If operated with AC voltage, a rectifier is installed in the
circuit breaker.
1 Magnet core 1 5Tripping pin
3 Housing 21 Locking pin
Indirect Releases (Secondary Shunt Release (DualTrip)
tM
5 Mounting holes (3) 23 Striker pin
(52T1) or Undervoltage (27))
7 Magnet coil 25 Latch
The indirect release provides for the conversion of modest
9 Magnet armature 27 Spring
control signals into powerful mechanical energy i m pulses. 11 Tension spring 31 Striker pin spring
It is primarily used to open medium voltage circuit breakers 13 Adjusting (Factory set) 33Terminal block
while functioning as a secondary shunt release (dual trip) or screw for 11
ar
undervoltage device. 1 94-94
ing coi l. If this scheme is used, a resistor must be provided the pole faces. When this happens, the latch (25) loses its
to limit current when th e normally open contact is close d . support and releases the striker pin (23), which is forced out
by the spring (31 ).
ww
17
om
Vacuum Interrupter/Operator Description
On the undervoltage release 3AX1103, the latch (25) is held absorber is to l imit overtravel and rebound of the vacuum
.c
by the locking pin ( 2 1 ) as long as the armature (9) is ener interrupter movable contacts during the conclusion of an
gized. If the circuit of the m a g n et coil (7) is interrupted, the opening operation. The shock absorber action affects only
armature (9) d rops off, th us causing the latch (25) to lose its the end of an opening operation.
support and release the striker pin (23).
Auxiliary Switch ( 52alb)
Following every tripping operation, the striker pin (23) m ust Figure 6a shows the circuit breaker mounted a uxiliary
ls
be reset to its normal position by loading the spring (3 1 ) .This switch (68). This switch provid es auxiliary contacts for
takes place automatically via the operating mecha nism of control of circuit breaker closing and opening functions.
the circuit breaker. Contacts are available for use in relaying and external logic
circu its. This switch is driven by l i n kage (68.1 ) connected
ua
Since the striker pin of the undervoltage release 3AX1103 is to the jack shaft (63). The auxiliary switch contains both 'b'
latched only when the armature is energ ized, the undervolt ( Normally Closed) and 'a' ( N ormally Open ) contacts. When
age release is provided with a screw (29), for locking the the circuit breaker is open, the 'b' contacts are closed and
striker pin (23) in the normal position for adjusting purposes the 'a' contacts are open.
or for carrying out trial operations d uring circuit breaker ser
an
vicing. Position A ( locked) d isables the undervoltage release. Spring Charging Motor (88)
Position B ( u n locked) is the normal operating position. Spring charging motors (50.4) (Figure 6a) are ava ilable for
both AC and DC operation. If operated with AC voltage, a
rectifier is insta lled in the circuit breaker.
Locl<edii.Jrlocked SelectionSC"ew
tM
(Undervoltage Release Only)
,A
Position A:
I
23 25 Locked
:�
ar
"
23 Strker pin "'"""'29
29 Scre.v
lP
Position B
Unlocked
(Ope ratirg positiOn) '� :� "' I
ca
21
""""""29
Figure 12. Latch Details (shown charged).
Cancel Tt'e Lod< For Urdervdtage Reease By
(29)
St>iltirg Loc�ng ScreN From A To B
CapacitorTrip Device
tri
Shock Absorber
Circuit breakers are equipped with a hydrau l ic shock ab
sorber (61.8) (Fig ure 6a). The purpose of this shock Figure 14. CapacitorTrip Device
18
om
Maintenance
.c
Introduction and Maintena nce Intervals may be used as a guide to establish such a progra m . A
Periodic inspections and maintenance a re essential to obtain preventive maintenance program is not intended to cover
safe and reliable operation of the circuit breaker. reconditioning or major repair, but should be designed to re
veal, if p ossible, the need for such a ctions in time to prevent
malfunctions during operation.
A DANGER
ls
Hazardous voltages and high-speed moving Recommended HandTools
parts. Metric h a rdware is used on these circuit breakers. Following
Will cause death, personal injury, and list of hand tools describes those normally used in d isas
ua
property damage. sem bly and re-assembly procedures.
De-energize before working on this equi pment.
Read instruction manuals, observe safety in- • Open end wrenches: 7, 8, 10, 1 3, 17 and 19 mm
• Open end wrench: 55 mm used to exchange shock
structions, and l i m it use to q ua l ified person nel.
a bsorber (Oty: 2 pes are required for the task).
an
• Sockets: 7, 8, 10, 13 and 1 7 m m
• Socket: 3 6 mm (used for replacing post insulators)
• Deep Sockets: 19 and 24 m m
When circuit breakers a re operated under "Usual Service • Hex keys: 5, 6, 8 a n d 10 m m
Conditions;'maintenance a n d l u brication is recommended •Torque wrench: 0-1 50Nm (0-1 00ft-lbs)
tM
at ten year intervals or at the n umber of operations indicated • Screwdrivers: 0.032 x 1/4 in. wide
in Table 2. " Usua l " and " U n us u a l " service conditions for and 0.55 x 7/1 6 in. wide
Medium Voltage Metal-Clad Switchgear (incl udes Circuit • Pliers
Breaker Module) are defined in ANSI C37.20.2, section 8.1. • Light Hammer
Generally, "usual service cond itions" are defined as an envi • Dental M i rror
ar
ronment in which the eq uipment is not exposed to exces • Flashlight
sive dust, acid fumes, damaging chemicals, salt air, rapid or • Drift Pins: 1/8, 3/16, a n d 1/4 in.
frequent changes in temperature, vibration, high humidity, • Reta ining Ring Plier
a n d extremes of temperature. (external type, tip d i a m eter 0.040 in.)
lP
The definition of "usual service conditions" is subject to Recommended Maintenance and Lubrication
a variety of interpretations. Because of this, you are best Periodic maintenance and lubrication should include a l l the
served by adjusti ng maintena nce and lu brication intervals tasks shown in Table 1. Recommended procedures for each
based on your experience with the equipment in the actual
ca
be inspected and exercised annually. Failure to properly maintain the equipment could result
in death, serious injury or product failure, and can prevent
For the safety of ma intenance personnel as wel l as others successful functioning of connected apparatus.
who might be exposed to hazards associated with mainte Instructions should be ca refu lly reviewed, understood, and
lec
19
om
Maintenance
Table 1 - MaintenanceTasks All of these components must be clean and free of dirt or a ny
foreign objects. Use a dry l int-free cloth. For stubborn d i rt,
.c
• Checks of the pri m a ry power path use a clean cloth saturated with denatured alcohol (except
• Clean l iness check for the vacuu m interrupters ) . For stubborn dirt on a vacu u m
• I nspection of flexible connectors interrupter u s e a d a m p cloth a n d then thoroughly d ry i t using
Checks of the stored energy operator mechanism a d ry l int-free cloth.
• Maintena n ce and l u brication
Inspection of Flexible Connectors
• Fastener check
ls
Inspect the flexible connectors that connect the bottom
• M a n u a l spring charging check movable contacts of the vacu u m interrupters to the lower
• Contact erosion check connection pad for tightness and absence of mech a n ical
• Electrical control checks damage, burning, or pitting.
ua
• Wiring a n d terminals check
Checks of the Stored Energy Operator Mechanism
• Secondary disconnect check
The stored energy operator checks a re divided into mechani
• Automatic spring charg ing check
cal a n d electrical checks for simplicity a n d better organ iza
• Electrical close and trip check tion. Th is first series of checks determine if the basic mecha
an
• Vacuum integrity check nism is clean, l ubricated and operates smoothly without
• High potenti a l test control power. The contact erqsion check of the vacuum
• Insu lation test interrupter is a l so performed d uring these tasks.
• Contact resistance test
Maintenance and Lubrication
• I nspection a n d cleaning of circuit breaker insulation
• Functional tests
Checks of the Primary Power Path shown . The movable end of the closing spring is connected
The primary power path consists of the three vacuum inter to a cra n k arm. The movable end of the opening spri n g is
ru pters, the three u pper and the three lower primary discon connected to the jack shaft by a pull rod.
nects. These components are checked for cleanliness a n d
lec
contacts in the closed position. Lu bricate a l l non-electrical moving or sliding s u rfaces with a
light coat of synthetic g rease or oil. Lubricants composed of
Also, the vacu u m integrity check is usually performed in
ester oils and lith i u m thickeners will be compatible.
conj u n ction with the High Potential tests.
Shell ( d rawn cup) needle bearings:
These instructions follow the recommendation that these
tests (contact erosion/manual spring charging check, and Use either Klueber lsoflexTopas L32 ( reference 3AX11 333H)
w
vacuum integrity/h igh potential tests) will be combined as Anderol 732 ( reference 1 5-1 72-81 6-058) or Beacon ( Exxon
described. 325 (reference# 1 8-658-676-422, pa rt # 1 5-337- 1 3 1-001 ) .
Cleanliness Check Pivots, sliding, and/or rolling surfaces and general l ubrication:
ww
Figure 2 is a side view of the circuit breaker with the insu Use either Klueber lsoflexTopas L32 (reference 3AX11 333H)
lating barriers removed (if furnished) to show the vacu u m Anderol 732 ( reference 1 5-1 72-81 6-058) or Beacon (Exxon
interru pter, and t h e upper and lower connection pad. 325 (reference# 1 8-658-676-422, part # 1 5-337- 1 3 1 -001 ) .
20
om
Maintenance
.c
ls
ua
an
tM
ar
lP
ca
tri
lec
.E
w
21
om
Maintenance
.c
Fastener Check
Inspect all fasteners for tightness. Both lock-n uts a n d retain
ing rings are used. Replace a ny fasteners that a ppear to have
�
been frequently removed and replaced.
� cr-
-
-
1----,
p Varnum
Manual Spring Charging and Contact Erosion Checks
F I nterrupter
ls
Perform the M a nu a l Spring Charging Check conta ined in the -
p
section describing the Installation Check and I n itia l Function
F r--'
I!- -
ua
r--i
r- -
f=j
1. I nsert the hand charg i n g crank into the m a n u a l charge cr-
socket at the front of the operator control panel. Turn
the cra n k clockwise (about 45 revolutions) to charge the
� 11-h .t--1
�
IJ::t' '1::::1 White Contact
closing spri n g . Conti nue cra n king until the Charged flag ....... _____ Erosion Mark
a ppears in the window of the spring indicator.
II
an
!L
2. Press the Close ( black) pushbutton. The contact position
indicator on the operator control panel should indicate
\
that the circuit breaker contacts are Closed.
tM j-
3. Perform the contact erosion check. Contact erosion occurs
when high fau lt cu rrents are interrupted or when the
vacu u m interrupter is nearing the limit of its contact life.
+
Determination of acceptable contact cond ition is checked
by the visibility of the white contact erosion m ark shown ++
ar
in Fig ure 1 6. The white contact erosion mark is located .)
on the movable stem of the vacuum interru pter, near the
plastic guide bushing.
lP
A WARNING
High Speed Moving Parts. Can cause
+
serious injury.
lec
ment.
22
om
Maintenance
.c
Electrical Control Checks Table 3. Typical Vacuum Interrupter Contact Life Expectancy
The electrical controls of the circuit breaker should be
checked d u ring inspections to verify a bsence of a ny me Rated Max. Interrupting Rated Curve Number
cha nical damage, and proper operation of the a utomatic Voltage Class Current
spring charging a n d Close a n d Trip circ u its.
4.76kV 25DMVA 36kA A 3
ls
Unless otherwise noted, all of these tests a re performed 4.76kV 35DMVA 49kA c 10
ua
Check of the Wiring andTerminals 1 5kV 750MVA 36kA A 3
an
4.76kV 31.5kA 31.5kA 8 6
4.76kV 40kA 40kA c 7
2. Check a l l terminals to be certain they are solidly attached
4.76kV 50kA 50kA c 11
to their respective device.
8.25kV 40kA 40kA c 7
1 5 kV 20kA 20kA A 1
A WARNING
tM
1 5kV 25kA 25kA 8 5
1 5kV 31.5kA 31.5kA 8 6
Hazardous voltages and high-speed
mechanical parts. 1 5kV 40kA 40kA c 7
1 5kV 50kA 50kA c 11
Will cause death, severe personal injury, or
38kV 31.5kA 31.5kA D 12
property damage.
ar
De-energize before working on this equ ipment. Primary tasks o f this check are:
1.The circuit breaker is energ ized with control power for this
Read instruction m a n u a ls, observe safety in
check.
lP
23
om
Mai n tenance
.c
100,000 100,000
50,000 &lPOO
20,000 Ul 20POO
ls
Ul
..m .!1!
0
>-
0
10,000
0
a- 10,000
Cl
Cl
c:
"" 5,000 c: 5poo
ua
e! '\. -�
(I)
2,000 l't.. 8. 2POO
8- 0
(I)
�
.c 1 .000 � 1 POO
·m
.!a
"iii
&lO -� 500
an
E " (I) "'
(I)
0.. '\.
0..
200 '
200
100 \ 100 [\
so
40 &l
tM
k3
20 l2I II I 20
CR._ I I 10
10
1 2 5 10 20 I I 5o kA 1oo 1 2 5 10 44o1 b 100
20 kA
25 36 � r 4 s�::@®
ar
lood GraJil ' A' Loaj G�h 'C'
B rea ki ng c urrent ( sym. wl ue) -- Breaki ng c urrent (sym. va ue) -- \!)
lP
100,000 100POO
ca
Ul 20,000 20POO
.!1! �
� 10,000 0
10POO
tri
>-
0 0
Cl
""
c: 5poo Cl
-� 5,000
t1l ' -e
�(I) 2POO 1\. 8. 2,000
lec
1\ 0
JR
�
·m
1 POO .c
·u;
1 POO
Ul .!12
"§(I) 500 E &lO
"' "'
0..
� � \.
200 200
\ i\.
.E
lllJQQ.
100
50 50
�\::!/" �
20 20
10
CD- I 10
1 2 5 10 2ol l 3 \ . 5 &J kA 100 1 2 s 10 20 lL50 1oo
kA
w
23 25
Lred GraJil 'B' lDad Gra� 'D' 3�(®
B reaking c u rrent (sym . va ue ) -- Breaking current (sym. value) - @
ww
24
om
Maintenance
Electrical Close andTrip Check ( Control Power Required) A vacuum interrupter may be assumed to be intact if it
.c
A check of the circuit breaker control circu its shall be shows the following cha racteristics:
performed . This check is made with the circuit breaker
energ ized by control power either from the switchgear or an An appreciable closing force has to be overcome when lever
external control power source. (48. 6) is moved to the "Open" position by h a n d ( Figure 18).
When th e lever is released, it must automatically return to
1. Once the circuit breaker springs are charged, move the the "Closed" position with an audible soun d as the contacts
ls
switchgear Close/Trip switch to the Close position. Verify touch.
by both the sound of the circuit breaker closing and by
the main contact status indicator that th e circuit breaker After checking the vacuum, reconnect the lever (48.6) to the
contacts are closed. insulati ng coupler (48) ( Figure 18).
ua
2. As soon as the circuit breaker has closed, the automatic
High-Potentia lTests
spring charging process is repeated.
The next series of tests (Vacuum Integrity Test a n d Insulation
3. After a satisfactory close operation is verified, move the Tests) involve use of high voltage test equipment. The circuit
switchgear Close/Tri p switch to the Tri p position. Verify breaker u n der test should be inside a suitable test barrier
an
by both the sound of the circuit breaker o pening and by equipped with warning lights.
the maih contact status indicator that the circuit breaker
contacts are open. Vacuum Integrity Check ( using DielectricTest)
A high potentia l test is used to verify the vacuum integrity
4. After a satisfactory open operation is verified, h old the of the circuit breaker. The test is conducted on the circ u it
tM
circuit breaker manual Trip button and apply and main breaker with its primary contacts in the Open position.
tain an electrical close signal. The circuit breaker should
close, immediately trip, the close spring should charge,
and the circuit breaker should not attempt to close. A DANGER
Hazardous voltages used in high potential
Completion of these checks demonstrates satisfactory
ar
tests.
operation of auxiliary switches, internal relays a n d open a n d
close coils. Will cause severe personal injury and death.
No additional checks of the spring charging motor are neces from the circuit breaker during application of
sary. test voltages.
The vacu um interrupter contact l ife curves Fig ure 17 a re of Can cause personal injury.
fered as a guide to life expectancy. Keep personnel more tha n six (6) feet away fro
a circuit breaker under test.
Vacuum Integrity Check
( using MechanicaiTest) ( Figure 18)
High PotentialTest Voltages
Before putting the circuit breaker into service, or if a vacuum
.E
The atmospheric pressure will force the moving contact of a 8.25kV 27kV 38kV
hermetically sealed vacu u m interrupter into the " Closed" po
ww
25
om
Mai n ten ance
.c
ls
ua
Prinary Contact
Res stance Test
an
Step 2
PrimarY Contact
tM In sui alingC oupleq 48)
(Operating Posti:ln)
ar
Closed Positi:l n - �nsulated
C ol-Per Dl!connected)
L---- lnsuatng Couj:ler (48)
5� 3 --------_J (Lo.vered Position)
prinary contact
Open Position - (Forced (Se p 2)
lP
Figure 18. Circuit Breaker Pole Assembly /Vacuum Check Mech anical / Contact Resistance Test
ca
3. Apply test voltage across each pole for one minute (Circuit Insulation and Contact ResistanceTest Equipment
Breaker open). In a ddition to the High PotentiaiTest Equipment capable of
test voltages as listed in Table 4, the following equ ipment is
4. If the pole sustains the test voltage for that period, its also req uired:
w
but also the other insulation components in parallel with the •Test equipment for contact resistance tests.
vacuum interrupter. These include the post insulators
26
om
Maintenance
.c
Insulation and Contact ResistanceTest Procedure Inspection and Cleaning of Circuit Breaker Insulation
1. Observe safety precaution listed in the danger and caution 1. Perform the Spring Discharge Check on the circuit breaker
advisories for the Vacuum Integrity Check tests. after all control power is removed. The Spri n g Disch a rg e
Check consists of 1 ) pressing the red Open push button,
2. Close the circuit breaker. Ground each pole not under test. 2) then pressing the black Close push button, and 3) again
ls
Use manual charging, closing and tripping procedures. pressing the red Open push button . All of these controls
are on the circuit breaker front panel (Figure 1 ) . Visually
verify the Discharge con d ition of the springs.
ua
3. Apply the proper AC or DC (Table 4) high potentia l test
voltage between a primary conductor of the pole and
ground for one mi nute. 2. Remove a ny interphase and outerphase barriers if fur
nished (applicable for certain types only).
4. If no d isruptive discharge occurs, the insulation system is
an
satisfactory. 3. Clean ba rriers and post insulators using clean cloth
a n d one of the following solvents:
5. After test, g round both ends and the middle of each
• Isopropyl or isobutyl alcohol
vacuum bottle to d issipate any static cha rge.
8. If no d isruptive discharge occurs, the secondary control These compounds will damage the phenylene ether
lP
FunctionalTests
Refer to the I nsta l l ation Checklist in the I n stallation Checks
10. Perform contact resistance tests of the primary contacts.
a n d I n itial Functional Tests section of this manual. Func
The resistance should be read between the lower and
upper connection pads (Figure 18). Contact resista nce tional tests consist of perform ing at least three (3) Manual
Spring Charging Checks a n d three (3) Automatic Spring
tri
1 200 35
2000 30
3000 30
.E
w
ww
27
om
Overhaul
.c
charts at the end of this section, provide maintenance per 1 5-1 33-281-007) and primer ( Loctite primerT, Siemens
sonnel with a g u i d e to identifying a n d correcting possible part 1 5- 1 33-28 1-005) .
malfunctions of the circuit breaker.
e) Connect wires to coils with new wire terminals
(Siemens part # 1 5- 1 7 1 -600-002)
A WARNING
ls
Hazardous voltages and high speed moving 3. Lubricate operating mechanism according to M a i ntenance
parts. Section.
Can cause death, severe personal injury, or
ua
property damage. 4. When work is finished operate circuit breaker, close
open, several times, and check that all screw con nec
De-energize circuit breaker and discharge
springs before working on circuit breaker. tions are tight.
an
Replacement vacuu m interrupters are furnished as a
Circuit Breaker Overh.aul complete assembly. They have been completely tested a n d
Table 6 lists the recommended overhaul schedu l e for 3AH dielectrically and mechanically conditioned.
circuit breakers operating under ANSI usual cond itions.
When actual operating cond itions are more severe, over For 3000A circuit breaker with flexible current shunts which
tM
haul periods should occur more frequently. The counter on are electron-beam welded to the vacu u m i nterrupters, the
the front panel of the circuit breaker records the n u mber of vacuum interrupters are not field replaceable. Contact the
operations. nearest Siemens representative.
kV kA(MVA)
5 kV 36kA (250MVA)
30,000 1. Removing the Vacuum Interrupter
15 kV 23kA (500MVA)
ca
b. Remove two M4 hex head screws and coils. 1.2 Loosen the lateral bolt(s) on terminal clamp (29.2).
ww
.c
3 1 .2
r--- 1 6 . 1
ls
ua
an
30 ---i--tit-..
28 ---+..
tM
ar
lP
ca
tri
29.2 ----
lec
29
.E
29
om
Overhaul
.c
1 .3 Withdraw pin (48.5) from insu lating coupler (48) a n d 2. I n stalling a Vacuum Interrupter
levers (48.6) .
ls
strut hardwa re on the pole bottom (40) and swing
the struts forward and downward.
2.1 I nspect all silver plated connection surfaces for clean
1.6 Loosen screws fastening the centering ring (28.1 ).
ua
liness. Clean only with a cloth and solvent.
Do not abra i d .
1.7 Remove bolt (31.2), lockwasher and l a rge washer at
stationary contact of the vacu u m interrupter. 2.2 I n s e rt vacuum interrupter (30) into the lower pole
support (40). Slip terminal clamp (29.2) into posi
tion on the movable stem.
an
1.8 Using a deep socket, loosen a n d remove hex cap
screw fastening the pole head to the post insulator.
Completely remove the pole head a n d set aside. 2.3 Align vacuum interrupter a n d fasten "finger tight"
using heavy flat washer, lock washer and bolt, (31.2).
1.9 Grasp the vacuum interrupter (30) and withdraw
tM
vertical ly. Assistance may be requ i red to work the
terminal clamp off the movable stem of the vacuum
interrupter. FORCIBLE TWIST ING EFFORT IS NOT
ALLOWED. If the terminal clamp (29.2) cannot be
easily rem oved, STOP! , check to be certain hard
ar
ware is loose, and that the term i n a l clamp (29.2) is
not binding.
lP
Torque Wrenc h
w
P = Direction Of Fon::e
ww
30
om
Overhaul
.c
2.4 Fasten the pole head to the post insulator ( 1 6.1 ) 3. Checking the Contact Stroke
"finger tight" using hex head bolt, lock washer a n d
flat washer. 3.1 Open the circuit breaker.
2.5 Attach struts (28) to the upper pole su pport (20), 3.2 Free insulating coupler (48) by removing pin (48.5).
replace h a rdware ( M 10). but do not tighten at this The vacu u m interrupter contacts m ust now close
ls
time. a utomatically as a consequence of atmospheric
pressure.
2.6 Couple levers (48.6) and drive link (48.9) to the eye
ua
bolt (36.3), using the pin supplied. Apply retaining 3.3 Observe the terminal clamp (29.2) th rou g h the open
clips. Appropriate pin is modestly chamfered, not ings on each side of the pole bottom (40). Using
to be confused with pin for the insulating coupler. vernier calipers (automatic circuit breaker test
equipment preferable) measure the d istance from
2.7 Raise the terminal clamp (29.2) against the step the bottom surface of the terminal clamp to the bot
an
or the spacer (if applicable) of the moving contact tom edge of the cutout opening. M easure carefu lly
(36.1 ) of the vacu um interrupter (30) so that the a n d record your result.
ra dius of the movable contact faces the connect
ing surface of the flexible connector (29.1 ). Refer to 3.4 Connect the insulating coupler (48) using pin (48.5)
Figure 20 and employ technique ill ustrated to fasten and the reta i n i n g clips provided.
terminal clamp. Note opposing wrenches.Tighten
the bolt(s) of the terminal clamp to a torq ue of 40
moves freely. If any binding or lack of freedom is 4. After eyebolt is tightened t o proper torq ue, repeat all
noted, loosen bolt (31.2) and adj ust the vacuum measurement procedures, making certain they are in
interrupter in pole head by turning and moving it agreement with values ind icated in 3.6.
slig htly.
lec
ware which secures the centering ring. Re-check The mechanism is equipped with a hydraulic shock absorber
that the movable contact is free to move vertically that functions when the circuit breaker opens. See item 6 1 .8
without binding. (Figure 6a) . The shock absorber should req uire no adj u st
ment. However, at maintenance checks, the shock absorber
2.11 Attach insulating coupler (48) a n d lever (48.6) should be examined for evidence of leaking. If evidence of
together, using pin (48.5). Apply retaining clips. fluid leakage is found, the shock absorber must be replaced
Correct pin has ends which h ave been generously to prevent damage to the vacuum interrupter bellows.
w
chamfered.
31
om
Maintenance andTroubleshooting
.c
Table 7. Vacuum I nterrupter Stroke
ls
4.76 kV 350 MVA VS1 5052 8.4 - 9.2 m m
ua
1 5 kV 750 MVA VS1 5052 8.4 - 9.2 m m
Notes:
an
1. Stroke settings a re a pplicable to both 1 200A and 2000A continuous current rated circuit breakers.
2.The vacu u m interrupter type designation is labeled on the vacu u m interru pter. If vac u u m interrupter does not match
rating, contact the nea rest Siemens representative.
3. If you need assistance achieving adjustments, contact the nea rest Siemens representative.
tM
ar
lP
ca
tri
lec
.E
w
ww
32
om
Maintenance andT rou b leshooting
.c
Table 8. Troubleshooti ng
Circuit breaker fails to close Closing spring will not automatically 1 . Secondary control circuit is de-
charge energ ized or control circuit fus-
ls
esare blown. Check and energize
or replace if necessary
2. Secondary d isconnect contacts
ua
A 1 or D 1 6 are not engaging.
Check a n d replace if req uired.
3. Damage to wiring, terminals or
connectors. Check and repair as
necessary.
an
4. Failure of charging motor (88)
Replace if requ ired.
5. Motor cut-off switch LS21 or LS22
fails to operate. Replace if nee-
tM
essary.
6. Mechanical fa ilure of operating
mechanism. Refer to factory or
authorized service shop.
ar
Closing springs charge, but circu it-
breaker does not close
close.
33
om
Maintenance andTroubleshooting
.c
N uisance or false close Electrical problem 1. N u isance or false closing signal
to secondary discon nect contact
A2. Check relay logic. Correct as
req u ired.
2 . Close coil (52SRC) terminal A2 is
ls
shorted to g round. Check to deter-
mine if problems in wiring or coil.
Correct as required.
ua
M echa n ical Problem
1. Mech a n ical failure of operating
mech a n ism. Check and contact
factory or a uthorized service shop.
an
Circuit breaker will n ot trip Trip coil, (52T) does not energize: 1. Second a ry control power is de-
There is no tripping sound. energized or control power fus-
esare blown. Correct as indicated.
2. Damage to wiring, terminals or
tM
con nectors. Check and repair as
necessary.
3. N o tripping signal to secondary
disconnect contact C2. Check for-
contin uity a n d correct relay logic.
ar
4. Secondary d isconnect contacts
C2 or 02 a re not enga g i n g . Check-
a n d replace if req u ired .
lP
c u it breaker is closed.
Check l i n kage and switch. Replace
or adjust as necessa ry.
tri
Trip coil (52T) energ izes. Tripping 1. Mech a n ical failure of operating
sou nd is heard, but circu itbreaker mechan ism . Check a n d contact
contacts do not open. factory or a uthorized service
shop.
2. One or more of the vacuum in-
.E
34
om
Appendix
Table A-1 a
Type 3AH Circuit Breaker Ratings (Historic "Constant MVA" Rating Basis)
.c
These ratings are in accordance with the following standards:
ANSI C37.04-1979 Standard Rating Structure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
ANSI C37.06-1987 AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis- Preferred Ratings and Related Required Capabilities
ANSI C37.09-1979 Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
ls
ANSI C37.010-1979 Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
ua
Circuit Breaker Type
Measured Parameter Units 5-3AH 5-3AH- 7-3AH- 1 5-3AH- 1 5-3AH- 1 5-3AH- 38-3AH-
250 350 500 500 750 1000 1 500
an
Nominal 3-Phase MVA Class •• MVA 250 350 500 500 750 1000 1 500
Maximum Design Voltage ( V ) "' kV rms 4.76 4.76 8.25 1 5.0 1 5.0 1 5.0 38
Rated
Voltage
Voltage Range Factor ( K ) "' -- 1.24 1.19 1.25 1.30 1.30 1.30 1.65
tM
Insulation Power Frequency kV rms 19 19 36 36 36 36 80
Withstan d
Levels Voltage Levels
Lightning Impulse (BIL) kV crest 60 60 95 95 95 95 1 50
Capabili-
ties 58 66 37 58
Closing Asymmetrical ( 1.6 x K x I ) '" kA rms 78 77 56
78 opt"' 77 opt"' 58 opt"' 77 opt"'
and
Latching 97 111 62 97
Peak ( 2.7 x K x I ) "' kA peak 132 1 30 95
(Momentary) 1 32 optm 1 30 opt"' 97 opt"' 130 opt"'
lec
Footnotes
1. High close and latch ( m o mentary) rating available for special application
2. Maxi m u m voltage for which the circuit breaker is designed, and the upper l i m it for operation.
3. K is the ratio of the rated maxi m u m design voltage to the lower limit of the range of operating voltage in which the required symmetrical
and asym metrical interrupting ca pabilities vary in inverse proportion to the operating voltage.
.E
4.To obtain the required symmetrical interrupting capability of a circuit breaker at an operating voltage between 1 /K times rated
maxi m u m design voltage and rated maxi m u m design voltage, the following formula shall be used: Required Sym metrical Interrupting
Ca pability = Rated S hort-Circuit Cu rrent ( I ) X [ ( Rated Maxi m u m Design Voltage ) I ( Operating Voltage ) 1
For operating voltages be low 1/K times rated maxim u m design voltage, the req u i red symmetrical interrupting capability of the circ u it
breaker shall be equal to K times rated short-circuit cu rrent.
5. Within the l i m itations stated in ANSI C37.04-1979, a l l values a pply to polyphase and l i ne-to-line fau lts. For single phase-to-g round fa u lts,
the specific conditions stated in clause 5.10.2.3 of ANSI C37.04-1979 a pply.
w
6. Current values in this row are not to be exceeded even for operating voltage below 1 /K times rated maxim u m design voltage. For ope rat-
ing voltages between rated maxi m u m design voltage and 1/K times rated maxi m u m design voltage, follow footnote 5 above.
7. Cu rrent values i n this row are independent of operating voltage up to and including rated maxi m u m design voltage.
8. " Nominal 3-Phase MVA Class" is included for reference only - this information is not l isted in ANSI C37.06-1987.
ww
35
om
Appendix
.c
Table A-1 b
Type 3AH Circuit Breaker Ratings (New "Constant kAR Rating Basis)
ANSI C37.06-2000 AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis- Preferred Ratings and Related Required Capabilities
ls
ANSI C37.09-1999 Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
ANSI C37.010-1999 Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
ua
Circuit BreakerType
an
Maximum Design Voltage ( V ) '" kV rms 4.76 4.76 4.76 8.25 1 5.0 1 5.0 1 5.0 1 5.0 1 5.0 38.0
Voltage Range Factor ( K ) " -- 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
tM
kV crest 60 60 60 95 95 95 95 95 95 150
lrTI_!l_u lse (BIL)
kA rms-
) 31.5 40 50 40 20 25 31.5 40 50 31.5
ar
Short-Circuit ( I " �
l;'{m
I nterrupting Time ms 83 83 83 83 83 83 83 83 83 83
Cycles 5 5 5 5 5 5 5 5 5 5
kA rms-
Max. Sym Interrupting ( I ) 31.5 40 50 40 20 25 31.5 40 50 31.5
svm
% de Component % 47 47 47 47 47 47 47 47 47 47
kA rms 40 40 40
ca
Footnotes
1. Maxi m u m volta ge for which the circuit breaker is designed, and the upper l i m it for operation.
2. K is l isted for i nformational pu rposes on ly. For circuit breakers rated o n a " kA basis;'the Voltage Range Factor is 1.0.
lec
3. 3000FC indicates that fan cooling may be required i n the switchgear structure to achieve this rating.
4 . A I I values apply to polyphase and l ine-to-line faults.
5. Standard duty cycle is 0 - 0.3sec - CO - 1 5sec - CO.
.E
w
ww
36
om
Appendix
.c
Table A-2
Type 3AH Circuit Breaker Ratings
ls
Close Trip AmpereS "' Amperes •" Run (Avg.)"' Seconds
ua
1 25 VDC 100-140 70-140 1.0 5.4 4 10
an
1. Current at nominal voltage. 2. Capacitor trip.
Table A-3
Interrupting Capacity of Circuit Breaker Auxiliary Switch Contacts
Type of Circuitto
Interrupt
Continuous Current
Amperes 120VAC
tM I
I
240 VAC
I
I
24VDC
Control Circuit Voltage
l 48VDC
l
Interrupting Capacity in Amperes
I I
125VDC
l
I
250VDC
ar
Non-Inductive 20 10 5 2()" 20"' 5 3
Inductive 20 10
I 5
I 2()"
I 20"'
I 5
I 3
1. 2 Contacts in series.
lP
37
om
SIEMENS Siemens Energy, Inc.
7000 Siemens Rd.
Wendell. NC 27591
.c
ls
ua
an
tM
ar
lP
ca
tri
lec
.E
w
ww