Edtfvn391827 Fxsq-Pa

You might also like

You are on page 1of 68

EDTFVN391827

201803

Engineering Data

FXSQ-PAVE
50 / 60 Hz
FXSQ-PAVE EDTFVN391827

FXSQ-PAVE
Middle Static Pressure
Ceiling Mounted Duct Type
50 / 60 Hz
1. Lineup..........................................................................................................2
2. Specifications..............................................................................................3
3. Dimensions..................................................................................................8
4. Piping Diagrams........................................................................................14
5. Wiring Diagrams........................................................................................15
6. Electric Characteristics..............................................................................16
7. Safety Devices Setting..............................................................................17
8. Capacity Tables.........................................................................................18
8.1 Cooling Capacity for Te: Auto..........................................................18
8.2 Cooling Capacity for Te: 6°C...........................................................18
8.3 Cooling Capacity for Te: 9°C...........................................................19
8.4 Heating Capacity..............................................................................19
9. Fan Performances.....................................................................................20
10. Airflow Auto Adjustment Characteristics...................................................29
11. Sound Levels.............................................................................................38
12. Centre of Gravity.......................................................................................43
13. Accessories...............................................................................................44
13.1 Optional Accessories (for Unit)........................................................44
13.2 Optional Accessories (for Controls).................................................45
14. Installation Manual....................................................................................46

1
FXSQ-PAVE EDTFVN391827

1. Lineup

2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW 9.0 kW 11.2 kW 14.0 kW 16.0 kW
Capacity range
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 6 HP
Capacity index 20 25 31.25 40 50 62.5 80 100 125 140

FXSQ 20PAVE 25PAVE 32PAVE 40PAVE 50PAVE 63PAVE 80PAVE 100PAVE 125PAVE 140PAVE

VE : 1 phase, 220-240/220 V, 50/60 Hz

2
FXSQ-PAVE EDTFVN391827

2. Specifications

Model FXSQ20PAVE FXSQ25PAVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 1,900 2,400
1 3 Cooling capacity Btu/h 7,500 9,600
kW 2.2 2.8
kcal/h 2,200 2,800
2 3 Heating capacity Btu/h 8,500 10,900
kW 2.5 3.2
50 Hz kW 0.058 0.058
Cooling
7 60 Hz kW 0.058 0.058
Power input 50 Hz kW 0.053 0.053
Heating
60 Hz kW 0.053 0.053
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 245×550×800 245×550×800
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 78×1 78×1
Number of units
m³/min 9/7.5/6.5 9/7.5/6.5
Fan
Airflow rate (H/M/L) l/s 150/125/108 150/125/108
cfm 318/265/230 318/265/230
External static
Pa Rated 50 (150-30 4) Rated 50 (150-30 4)
pressure
Drive Direct drive Direct drive
Microprocessor thermostat for Microprocessor thermostat for
Temperature control cooling and heating cooling and heating
Air filter — 5 — 5
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection)
connections VP25 VP25
Drain pipe mm
(External dia. 32
Internal dia. 25 ) (
External dia. 32
Internal dia. 25 )
Mass kg 25 25
6 Sound pressure level (H/M/L) dB(A) 33/30/28 33/30/28
Sound power level (H) dB 61 61
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing material, Clamps, Washers, hose, Sealing material, Clamps, Washers,
Standard accessories Screws, Thermal insulation, Hose band, Air Screws, Thermal insulation, Hose band, Air
discharge flange, Air suction flange discharge flange, Air suction flange
Specification C: 3D105249B C: 3D105249B
Drawing No.
Sound level C: 4D095804B C: 4D095804B

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class)
by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.

3
FXSQ-PAVE EDTFVN391827

Model FXSQ32PAVE FXSQ40PAVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 3,100 3,900
1 3 Cooling capacity Btu/h 12,300 15,400
kW 3.6 4.5
kcal/h 3,400 4,300
2 3 Heating capacity Btu/h 13,600 17,100
kW 4.0 5.0
50 Hz kW 0.066 0.101
Cooling
7 60 Hz kW 0.066 0.101
Power input 50 Hz kW 0.061 0.096
Heating
60 Hz kW 0.061 0.096
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 245×550×800 245×700×800
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 78×1 130×1
Number of units
m³/min 9.5/8/7 15/12.5/10.5
Fan
Airflow rate (H/M/L) l/s 158/133/116 250/208/175
cfm 335/282/247 530/441/371
External static
Pa Rated 50 (150-30 4) Rated 50 (150-30 4)
pressure
Drive Direct drive Direct drive
Microprocessor thermostat for Microprocessor thermostat for
Temperature control cooling and heating cooling and heating
Air filter — 5 — 5
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection)
connections VP25 VP25
Drain pipe mm
(External dia. 32
Internal dia. 25 ) (
External dia. 32
Internal dia. 25 )
Mass kg 25 27
6 Sound pressure level (H/M/L) dB(A) 34/32/30 36/33/30
Sound power level (H) dB 62 64
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing material, Clamps, Washers, hose, Sealing material, Clamps, Washers,
Standard accessories Screws, Thermal insulation, Hose band, Air Screws, Thermal insulation, Hose band, Air
discharge flange, Air suction flange discharge flange, Air suction flange
Specification C: 3D105249B C: 3D105249B
Drawing No.
Sound level C: 4D095805B C: 4D095806B

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class)
by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.

4
FXSQ-PAVE EDTFVN391827

Model FXSQ50PAVE FXSQ63PAVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 4,800 6,100
1 3 Cooling capacity Btu/h 19,100 24,200
kW 5.6 7.1
kcal/h 5,400 6,900
2 3 Heating capacity Btu/h 21,500 27,300
kW 6.3 8.0
50 Hz kW 0.075 0.106
Cooling
7 60 Hz kW 0.075 0.106
Power input 50 Hz kW 0.070 0.101
Heating
60 Hz kW 0.070 0.101
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 245×1,000×800 245×1,000×800
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 230×1 230×1
Number of units
m³/min 17/14.5/11.5 21/17.5/14.5
Fan
Airflow rate (H/M/L) l/s 283/242/192 350/292/242
cfm 600/512/406 741/618/512
External static
Pa Rated 50 (150-50 4) Rated 50 (150-50 4)
pressure
Drive Direct drive Direct drive
Microprocessor thermostat for Microprocessor thermostat for
Temperature control cooling and heating cooling and heating
Air filter — 5 — 5
Liquid pipes mm φ6.4 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ15.9 (Flare connection)
connections VP25 VP25
Drain pipe mm
(External dia. 32
Internal dia. 25 ) (
External dia. 32
Internal dia. 25 )
Mass kg 35 35
6 Sound pressure level (H/M/L) dB(A) 34/32/29 36/32/29
Sound power level (H) dB 62 64
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing material, Clamps, Washers, hose, Sealing material, Clamps, Washers,
Standard accessories Screws, Thermal insulation, Hose band, Air Screws, Thermal insulation, Hose band, Air
discharge flange, Air suction flange discharge flange, Air suction flange
Specification C: 3D105249B C: 3D105249B
Drawing No.
Sound level C: 4D095807B C: 4D095808B

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class)
by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.

5
FXSQ-PAVE EDTFVN391827

Model FXSQ80PAVE FXSQ100PAVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 7,700 9,600
1 3 Cooling capacity Btu/h 30,700 38,200
kW 9.0 11.2
kcal/h 8,600 10,800
2 3 Heating capacity Btu/h 34,100 42,700
kW 10.0 12.5
50 Hz kW 0.126 0.151
Cooling
7 60 Hz kW 0.126 0.151
Power input 50 Hz kW 0.121 0.146
Heating
60 Hz kW 0.121 0.146
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 245×1,000×800 245×1,400×800
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 230×1 300×1
Number of units
m³/min 23/19.5/16 32/27/22.5
Fan
Airflow rate (H/M/L) l/s 383/325/267 533/450/375
cfm 812/688/565 1,130/953/794
External static
Pa Rated 50 (150-50 4) Rated 50 (150-50 4)
pressure
Drive Direct drive Direct drive
Microprocessor thermostat for Microprocessor thermostat for
Temperature control cooling and heating cooling and heating
Air filter — 5 — 5
Liquid pipes mm φ9.5 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ15.9 (Flare connection) φ15.9 (Flare connection)
connections VP25 VP25
Drain pipe mm
(External dia. 32
Internal dia. 25 ) (
External dia. 32
Internal dia. 25 )
Mass kg 37 46
6 Sound pressure level (H/M/L) dB(A) 37.5/34/30 39/35/32
Sound power level (H) dB 65.5 67
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing material, Clamps, Washers, hose, Sealing material, Clamps, Washers,
Standard accessories Screws, Thermal insulation, Hose band, Air Screws, Thermal insulation, Hose band, Air
discharge flange, Air suction flange discharge flange, Air suction flange
Specification C: 3D105249B C: 3D105249B
Drawing No.
Sound level C: 4D095809B C: 4D095810B

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class)
by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.

6
FXSQ-PAVE EDTFVN391827

Model FXSQ125PAVE FXSQ140PAVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 12,000 13,800
1 3 Cooling capacity Btu/h 47,800 54,600
kW 14.0 16.0
kcal/h 13,800 15,500
2 3 Heating capacity Btu/h 54,600 61,400
kW 16.0 18.0
50 Hz kW 0.206 0.222
Cooling
7 60 Hz kW 0.206 0.222
Power input 50 Hz kW 0.201 0.217
Heating
60 Hz kW 0.201 0.217
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 245×1,400×800 245×1,550×800
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 300×1 350×1
Number of units
m³/min 37/31.5/26 39/33.5/28
Fan
Airflow rate (H/M/L) l/s 617/525/433 650/558/467
cfm 1,306/1,112/918 1,377/1,183/988
External static
Pa Rated 50 (150-50 4) Rated 50 (140-50 4)
pressure
Drive Direct drive Direct drive
Microprocessor thermostat for Microprocessor thermostat for
Temperature control cooling and heating cooling and heating
Air filter — 5 — 5
Liquid pipes mm φ9.5 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ15.9 (Flare connection) φ15.9 (Flare connection)
connections VP25 VP25
Drain pipe mm
(External dia. 32
Internal dia. 25 ) (
External dia. 32
Internal dia. 25 )
Mass kg 47 52
6 Sound pressure level (H/M/L) dB(A) 42/38.5/35 43/40/36
Sound power level (H) dB 70 71
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing material, Clamps, Washers, hose, Sealing material, Clamps, Washers,
Standard accessories Screws, Thermal insulation, Hose band, Air Screws, Thermal insulation, Hose band, Air
discharge flange, Air suction flange discharge flange, Air suction flange
Specification C: 3D105249B C: 3D105249B
Drawing No.
Sound level C: 4D095811B C: 4D095812B

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class)
by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.

7
FXSQ-PAVE EDTFVN391827

3. Dimensions

FXSQ20PAVE / FXSQ25PAVE / FXSQ32PAVE


Unit: mm

3D095725C

8
FXSQ-PAVE EDTFVN391827

FXSQ40PAVE
Unit: mm

3D095726C

9
FXSQ-PAVE EDTFVN391827

FXSQ50PAVE
Unit: mm

3D096164C

10
FXSQ-PAVE EDTFVN391827

FXSQ63PAVE / FXSQ80PAVE
Unit: mm

3D095426F

11
FXSQ-PAVE EDTFVN391827

FXSQ100PAVE / FXSQ125PAVE
Unit: mm

3D095427H

12
FXSQ-PAVE EDTFVN391827

FXSQ140PAVE
Unit: mm

3D095727D

13
FXSQ-PAVE EDTFVN391827

4. Piping Diagrams

FXSQ20PAVE / FXSQ25PAVE / FXSQ32PAVE / FXSQ40PAVE / FXSQ50PAVE / FXSQ63PAVE /


FXSQ80PAVE / FXSQ100PAVE / FXSQ125PAVE / FXSQ140PAVE

4D104913

„„ Refrigerant pipe connection port diameters


Unit: mm
Model Gas Liquid
FXSQ20PAVE / FXSQ25PAVE / FXSQ32PAVE / FXSQ40PAVE / FXSQ50PAVE φ12.7 φ6.4
FXSQ63PAVE / FXSQ80PAVE / FXSQ100PAVE / FXSQ125PAVE / FXSQ140PAVE φ15.9 φ9.5

14
FXSQ-PAVE EDTFVN391827

5. Wiring Diagrams

FXSQ20PAVE / FXSQ25PAVE / FXSQ32PAVE / FXSQ40PAVE / FXSQ50PAVE / FXSQ63PAVE /


FXSQ80PAVE / FXSQ100PAVE / FXSQ125PAVE / FXSQ140PAVE

3D092752C

15
FXSQ-PAVE EDTFVN391827

6. Electric Characteristics

FXSQ20PAVE / FXSQ25PAVE / FXSQ32PAVE / FXSQ40PAVE / FXSQ50PAVE / FXSQ63PAVE /


FXSQ80PAVE / FXSQ100PAVE / FXSQ125PAVE / FXSQ140PAVE

4D105290

16
FXSQ-PAVE EDTFVN391827

7. Safety Devices Setting

Model FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A
Drain pump thermal fuse °C — — — —

Model FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A
Drain pump thermal fuse °C — — — —

Model FXSQ125PAVE FXSQ140PAVE


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A
Drain pump thermal fuse °C — —
C: 3D104897

17
FXSQ-PAVE EDTFVN391827

8. Capacity Tables
8.1 Cooling Capacity for Te: Auto

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXSQ20PAVE 20 1.9 1.9 2.1 2.0 2.2 1.9 2.2 1.8 2.2 1.8 2.3 1.7 2.3 1.7
FXSQ25PAVE 25 2.5 2.2 2.6 2.2 2.8 2.3 2.8 2.2 2.8 2.1 2.9 2.0 3.0 2.0
FXSQ32PAVE 32 3.2 2.6 3.4 2.7 3.5 2.8 3.6 2.7 3.6 2.6 3.7 2.5 3.8 2.5
FXSQ40PAVE 40 4.0 3.5 4.2 3.8 4.4 4.0 4.5 3.7 4.6 3.6 4.7 3.4 4.8 3.4
FXSQ50PAVE 50 4.9 4.2 5.3 4.6 5.5 4.7 5.6 4.3 5.7 4.2 5.8 4.1 5.9 3.9
FXSQ63PAVE 63 6.3 5.3 6.7 5.7 7.0 5.9 7.1 5.4 7.2 5.4 7.3 5.2 7.5 5.1
FXSQ80PAVE 80 7.9 6.3 8.5 6.8 8.8 7.1 9.0 6.5 9.1 6.4 9.3 6.2 9.5 6.0
FXSQ100PAVE 100 9.9 8.2 10.5 8.9 11.0 9.2 11.2 8.5 11.3 8.4 11.6 8.1 11.8 7.9
FXSQ125PAVE 125 12.3 9.9 13.2 10.7 13.8 10.9 14.0 10.1 14.2 10.0 14.5 9.7 14.8 9.3
FXSQ140PAVE 140 14.1 11.0 15.0 11.8 15.7 12.4 16.0 11.6 16.2 11.4 16.5 11.1 16.9 10.6

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

8.2 Cooling Capacity for Te: 6°C

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXSQ20PAVE 20 1.5 1.5 1.8 1.7 2.1 1.8 2.2 1.8 2.2 1.8 2.3 1.7 2.3 1.7
FXSQ25PAVE 25 1.9 1.8 2.3 1.9 2.6 2.1 2.8 2.2 2.8 2.1 2.9 2.0 3.0 2.0
FXSQ32PAVE 32 2.4 2.0 2.9 2.3 3.4 2.6 3.6 2.7 3.6 2.6 3.7 2.5 3.8 2.5
FXSQ40PAVE 40 3.0 2.8 3.6 3.2 4.2 3.6 4.5 3.7 4.6 3.6 4.7 3.4 4.8 3.4
FXSQ50PAVE 50 3.8 3.3 4.5 3.8 5.2 4.2 5.6 4.3 5.7 4.2 5.8 4.1 5.9 3.9
FXSQ63PAVE 63 4.8 4.2 5.7 4.8 6.6 5.3 7.1 5.4 7.2 5.4 7.4 5.2 7.5 5.1
FXSQ80PAVE 80 6.1 5.0 7.2 5.7 8.4 6.4 9.0 6.5 9.1 6.4 9.3 6.2 9.5 6.0
FXSQ100PAVE 100 7.6 6.5 9.0 7.5 10.5 8.4 11.2 8.5 11.3 8.4 11.6 8.1 11.9 7.9
FXSQ125PAVE 125 9.4 7.7 11.3 8.9 13.1 9.9 14.0 10.1 14.2 10.0 14.5 9.7 14.9 9.4
FXSQ140PAVE 140 10.8 8.8 12.9 10.1 15.0 11.3 16.0 11.6 16.2 11.4 16.6 11.1 17.0 10.7

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

18
FXSQ-PAVE EDTFVN391827

8.3 Cooling Capacity for Te: 9°C

For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXSQ20PAVE 20 1.0 1.0 1.3 1.3 1.7 1.6 1.8 1.6 1.8 1.6 1.9 1.5 2.0 1.5
FXSQ25PAVE 25 1.3 1.3 1.7 1.6 2.0 1.8 2.3 1.9 2.3 1.8 2.5 1.8 2.6 1.8
FXSQ32PAVE 32 1.7 1.6 2.2 1.9 2.7 2.3 2.9 2.4 3.0 2.3 3.2 2.3 3.3 2.3
FXSQ40PAVE 40 2.1 2.1 2.6 2.6 3.3 3.1 3.6 3.2 3.8 3.2 4.0 3.0 4.2 3.1
FXSQ50PAVE 50 2.5 2.5 3.2 3.1 4.0 3.6 4.5 3.7 4.6 3.6 4.9 3.6 5.1 3.5
FXSQ63PAVE 63 3.3 3.3 4.1 4.0 5.1 4.5 5.7 4.7 5.9 4.7 6.2 4.6 6.5 4.6
FXSQ80PAVE 80 4.1 3.9 5.3 4.8 6.6 5.5 7.3 5.7 7.5 5.6 7.9 5.6 8.3 5.5
FXSQ100PAVE 100 5.3 5.2 6.7 6.3 8.3 7.3 9.1 7.5 9.3 7.4 9.9 7.3 10.4 7.2
FXSQ125PAVE 125 6.5 6.1 8.4 7.5 10.4 8.6 11.4 8.9 11.7 8.8 12.4 8.8 13.1 8.6
FXSQ140PAVE 140 7.5 7.1 9.6 8.6 12.0 9.9 13.0 10.2 13.5 10.1 14.3 10.1 15.0 9.8

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

8.4 Heating Capacity

Indoor air temp.


Capacity
Model 16°CDB 18°CDB 20°CDB 21°CDB 22°CDB 24°CDB
indication
kW kW kW kW kW kW
FXSQ20PAVE 20 2.6 2.6 2.5 2.4 2.3 2.2
FXSQ25PAVE 25 3.4 3.2 3.2 3.1 3.0 2.8
FXSQ32PAVE 32 4.2 4.2 4.0 3.9 3.7 3.5
FXSQ40PAVE 40 5.2 5.2 5.0 4.8 4.7 4.4
FXSQ50PAVE 50 6.6 6.6 6.3 6.1 5.9 5.5
FXSQ63PAVE 63 8.4 8.4 8.0 7.7 7.5 7.0
FXSQ80PAVE 80 10.5 10.5 10.0 9.7 9.4 8.7
FXSQ100PAVE 100 13.1 13.1 12.5 12.1 11.7 10.9
FXSQ125PAVE 125 16.8 16.8 16.0 15.5 15.0 13.9
FXSQ140PAVE 140 18.9 18.9 18.0 17.4 16.8 15.7

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

19
FXSQ-PAVE EDTFVN391827

9. Fan Performances

FXSQ20PAVE / FXSQ25PAVE

3D095855A

20
FXSQ-PAVE EDTFVN391827

FXSQ32PAVE

3D095856A

21
FXSQ-PAVE EDTFVN391827

FXSQ40PAVE

3D095857A

22
FXSQ-PAVE EDTFVN391827

FXSQ50PAVE

3D095858A

23
FXSQ-PAVE EDTFVN391827

FXSQ63PAVE

3D095859A

24
FXSQ-PAVE EDTFVN391827

FXSQ80PAVE

3D095860A

25
FXSQ-PAVE EDTFVN391827

FXSQ100PAVE

3D095861A

26
FXSQ-PAVE EDTFVN391827

FXSQ125PAVE

3D095862A

27
FXSQ-PAVE EDTFVN391827

FXSQ140PAVE

3D095863A

28
FXSQ-PAVE EDTFVN391827

10. Airflow Auto Adjustment Characteristics

FXSQ20PAVE / FXSQ25PAVE

3D095846A

29
FXSQ-PAVE EDTFVN391827

FXSQ32PAVE

3D095847A

30
FXSQ-PAVE EDTFVN391827

FXSQ40PAVE

3D095848A

31
FXSQ-PAVE EDTFVN391827

FXSQ50PAVE

3D095849A

32
FXSQ-PAVE EDTFVN391827

FXSQ63PAVE

3D095850A

33
FXSQ-PAVE EDTFVN391827

FXSQ80PAVE

3D095851A

34
FXSQ-PAVE EDTFVN391827

FXSQ100PAVE

3D095852A

35
FXSQ-PAVE EDTFVN391827

FXSQ125PAVE

3D095853A

36
FXSQ-PAVE EDTFVN391827

FXSQ140PAVE

3D095854A

37
FXSQ-PAVE EDTFVN391827

11. Sound Levels

FXSQ20PAVE / FXSQ25PAVE

4D095804B
FXSQ32PAVE

4D095805B

38
FXSQ-PAVE EDTFVN391827

FXSQ40PAVE

4D095806B
FXSQ50PAVE

4D095807B

39
FXSQ-PAVE EDTFVN391827

FXSQ63PAVE

4D095808B
FXSQ80PAVE

4D095809B

40
FXSQ-PAVE EDTFVN391827

FXSQ100PAVE

4D095810B
FXSQ125PAVE

4D095811B

41
FXSQ-PAVE EDTFVN391827

FXSQ140PAVE

4D095812B

42
FXSQ-PAVE EDTFVN391827

12. Centre of Gravity

FXSQ20PAVE / FXSQ25PAVE / FXSQ32PAVE / FXSQ40PAVE / FXSQ50PAVE / FXSQ63PAVE /


FXSQ80PAVE / FXSQ100PAVE / FXSQ125PAVE / FXSQ140PAVE

Unit: mm

4D095814B

43
FXSQ-PAVE EDTFVN391827

13. Accessories
13.1 Optional Accessories (for Unit)

Model
Item
FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE

High efficiency filter 65% KAFP632B36 KAFP632B56


(Note 1) 90% KAFP633B36 KAFP633B56
Filter chamber (for rear suction) KDDFP63B36 KDDFP63B56
(Note 1)
Long life replacement filter (Note 1) KAFP631B36 KAFP631B56
White KTBJ25K36W KTBJ25K56W

Service panel Fresh KTBJ25K36F KTBJ25K56F


white
Brown KTBJ25K36T KTBJ25K56T
Air discharge adapter KDAP25A36A KDAP25A56A
Shield plate for side plate KDBD63A160

Model
Item
FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE

High efficiency filter 65% KAFP632B80


(Note 1) 90% KAFP633B80
Filter chamber (for rear suction)
KDDFP63B80
(Note 1)
Long life replacement filter (Note 1) KAFP631B80
White KTBJ25K80W

Service panel Fresh KTBJ25K80F


white
Brown KTBJ25K80T
Air discharge adapter KDAP25A71A
Shield plate for side plate KDBD63A160

Model
Item
FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE

High efficiency filter 65% KAFP632B160 KAF632B160B


(Note 1) 90% KAFP633B160 KAF633B160B
Filter chamber (for rear suction)
KDDFP63B160 KDDF63B160B
(Note 1)
Long life replacement filter (Note 1) KAFP631B160 KAF631B160B
White KTBJ25K160W
Fresh
Service panel white KTBJ25K160F

Brown KTBJ25K160T
Air discharge adapter KDAP25A140A KDAP25A160A (Note 2)
Shield plate for side plate KDBD63A160 —
3D095818E
Notes:
1. If installing high efficiency filter and long-life filter to the unit, filter chamber is required.
2. This option is a set of KDAP25A140A and KDBHP37A160.

44
FXSQ-PAVE EDTFVN391827

13.2 Optional Accessories (for Controls)

Model
Item
FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE
Cooling Only BRC4C66 (Note 4)
Remote Wireless
controller Heat Pump BRC4C65 (Note 4)
Wired BRC1C62 (Note 4)
Navigation remote controller BRC1E62 (Note 4, 5)
(Wired remote controller)
Simplified remote
BRC2C51
controller (Exposed type)
Remote controller for hotel use BRC3A61
(Concealed type)
Adaptor for wiring  KRP1C64
Wiring adaptor for  KRP2A61
electrical appendices (1)
Wiring adaptor for  KRP4AA51
electrical appendices (2)
Remote sensor
KRCS01-4B
(for indoor temperature)
Installation box for adaptor KRP4A98 (Note 2, 3)
printed circuit board
External control adaptor  DTA104A61
for outdoor unit
Adaptor for multi tenant  DTA114A61

Model
Item
FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE
Cooling Only BRC4C66 (Note 4)
Remote Wireless
Heat Pump BRC4C65 (Note 4)
controller
Wired BRC1C62 (Note 4)
Navigation remote controller
BRC1E62 (Note 4, 5)
(Wired remote controller)
Simplified remote BRC2C51
controller (Exposed type)
Remote controller for hotel BRC3A61
use (Concealed type)
Adaptor for wiring  KRP1C64
Wiring adaptor for  KRP2A61
electrical appendices (1)
Wiring adaptor for  KRP4AA51
electrical appendices (2)
Remote sensor KRCS01-4B
(for indoor temperature)
Installation box for adaptor
KRP4A98 (Note 2, 3)
printed circuit board
External control adaptor  DTA104A61
for outdoor unit
Adaptor for multi tenant  DTA114A61
C: 3D095822D
Notes:
1. Installation box is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Wireless remote controller does not have AUTO fan mode.
Use wired remote controller to select AUTO fan mode.
5. Auto airflow rate can be set only via wired remote controller BRC1E62. Cannot be set via other remote controllers.

45
FXSQ-PAVE EDTFVN391827

14. Installation Manual

FXSQ20PAVE FXSQ50PAVE FXSQ125PAVE


FXSQ25PAVE FXSQ63PAVE FXSQ140PAVE VRV SYSTEM
Installation manual
FXSQ32PAVE FXSQ80PAVE Air Conditioner
FXSQ40PAVE FXSQ100PAVE

CONTENTS WARNING
• Ask your local dealer or qualified personnel to carry out
1. SAFETY PRECAUTIONS .............................................. 1
installation work.
2. BEFORE INSTALLATION .............................................. 2 Improper installation may result in water leakage, electric
3. SELECTION OF INSTALLATION LOCATION ................ 4 shocks or a fire.
4. PREPARATION BEFORE INSTALLATION .................... 5 • Perform installation work in accordance with this installation
manual.
5. INSTALLATION OF INDOOR UNIT ............................... 6 Improper installation may result in water leakage, electric
6. REFRIGERANT PIPING WORK .................................... 7 shocks or a fire.
7. DRAIN PIPING WORK .................................................. 8 • Consult your local dealer regarding what to do in case of
refrigerant leakage.
8. DUCT WORK ............................................................... 11
When the air conditioner is installed in a small room, it is
9. ELECTRIC WIRING WORK ......................................... 11 necessary to take proper measures so that the amount of
10. FIELD SETTING .......................................................... 15 any leaked refrigerant does not exceed the concentration
11. TEST OPERATION ...................................................... 16 limit in the event of a leakage.
Otherwise, this may lead to an accident due to oxygen
12. WEIGHT AND DIMENSION ........................................16 deficiency.
• Be sure to use only the specified parts and accessories for
1. SAFETY PRECAUTIONS installation work.
Failure to use the specified parts may result in the air
Please read the these " SAFETY CONSIDERATIONS" conditioner falling down, water leakage, electric shocks, a
carefully before installing air conditioning unit and be sure to fire, etc.
install it correctly. After completing the installation, make sure • Install the air conditioner on a foundation that can withstand
that the unit operates properly during the start-up operation.
its mass.
Please instruct the customer on how to operate the unit and
Insufficient strength may result in the air conditioner falling
keep it maintained.
down and causing injury.
Also, inform customers that they should store this installation
In addition, it may lead to vibration of indoor units and cause
manual along with the operation manual for future reference.
unpleasant chattering noise.
This product comes under the term “appliances not accessible
• Carry out the specified installation work in consideration of
to the general public”.
strong winds, typhoons, or earthquakes.
This is a class A product. In a domestic environment this Improper installation may result in an accident such as air
product may cause radio interference in which case the user conditioner falling.
may be required to take adequate measures. • Make certain that all electrical work is carried out by qualified
personnel according to the applicable legislation (Note 1)
• This manual classifies the precautions into WARNINGS and and this installation manual, using a separate circuit.
CAUTIONS. In addition, even if the wiring is short, make sure to use a
Be sure to follow all the precautions below: They are all wiring that has sufficient length and never connect additional
important for ensuring safety. wiring to make the length sufficient.
Insufficient capacity of the power supply circuit or improper
WARNING ..............Indicates a potentially electrical construction may lead to electric shocks or a fire.
hazardous situation which,
(Note 1) applicable legislation means “All international,
if not avoided, could result in
national and local directives, laws, regulations
death or serious injury.
and/or codes which are relevant and applicable for
CAUTION ...............Indicates a potentially a certain product or domain”.
hazardous situation which, • Earth the air conditioner.
if not avoided, may result in Do not connect the earth wiring to gas or water piping,
minor or moderate injury. lightning conductor or telephone earth wiring.
It may also be used to alert Incomplete earthing may cause electric shocks or a fire.
against unsafe practices. • Be sure to install an earth leakage breaker.
• After the installation is completed, test the air conditioner Failure to do so may cause electric shocks and a fire.
and check if the air conditioner operates properly. Give the • Disconnect the power supply before touching the electric
user adequate instructions concerning the use and cleaning components.
of the indoor unit according to the Operation Manual. Ask the If you touch the live part, you may get electric shocks.
user to keep this manual and the Operation Manual together • Make sure that all wiring is secure, using the specified
in a handy place for future reference. wirings and ensuring that external forces do not act on the
terminal connections or wirings.
Incomplete connection or fixing may cause an overheat or a
fire.

3P432203-4B

46
FXSQ-PAVE EDTFVN391827

• When wiring between the indoor and outdoor units, and • Make sure to provide for adequate measures in order to prevent
wiring the power supply, form the wirings orderly so that the that the outdoor unit be used as a shelter by small animals.
control box lid can be securely fastened. Small animals making contact with electrical parts can cause
If the control box lid is not in place, overheating of the malfunctions, smoke or fire. Please instruct the customer to
terminals, electric shocks or a fire may be caused. keep the area around the unit clean.
• If refrigerant gas leaks during installation work, ventilate the • Install in a machine room that is free of moisture. The unit is
area immediately. designed for indoor use.
Toxic gas may be produced if refrigerant gas comes into • Disposal requirements
contact with a fire. Dismantling of the unit, treatment of the refrigerant, of oil and of
• After completing the installation work, check to make sure other parts must be done in accordance with relevant local and
that there is no leakage of refrigerant gas. national legislation.
Toxic gas may be produced if refrigerant gas leaks into the
room and comes into contact with a source of a fire, such as
a fan heater, stove or cooker. SPECIAL NOTICE PRODUCT
• Never directly touch any accidental leaking refrigerant. This • The refrigerant R410A requires that strict precautions be
could result in severe wounds caused by frostbite. observed for keeping the system clean, dry and tightly sealed.
• Do not allow children to climb on the outdoor unit and avoid A. Clean and dry
placing objects on the unit. Strict measures must be taken to keep impurities
Injury may result if the unit becomes loose and falls. (including SUNISO oil and other mineral oils as well as
moisture) out of the system.
CAUTION B. Tightly sealed
R410A contains no chlorine, does not destroy the ozone
• Install drain piping according to this installation manual to layer and so does not reduce the earth's protection against
ensure good drainage, and insulate the piping to prevent harmful ultraviolet radiation. R410A will contribute only slightly
condensation. to the greenhouse effect if released into the atmosphere.
Improper drain piping may cause water leakage, make the
furniture get wet. • Since design pressure is 4.0 MPa or 40 bar (for R407C units:
3.3 MPa or 33 bar), the thickness of pipes must be greater
• Install the air conditioner, power supply wiring, remote
than previously. Since R410A is a mixed refrigerant, the
controller wiring and transmission wiring at least 1 meter
required additional refrigerant must be charged in its liquid state.
away from televisions or radios to prevent image interference
(If the system is charged with refrigerant in its gaseous state,
or noise.
due to composition change, the system will not function
(Depending on the radio waves, a distance of 1 meter may
normally). The indoor unit is designed for R410A use.
not be sufficient to eliminate the noise.)
See the catalogue for indoor unit models that can be
• Install the indoor unit as far as possible from fluorescent
connected. (Normal operation is not possible when connecting
lamps.
units that are originally designed for other refrigerants.)
If a wireless remote controller kit is installed, the transmission
distance may be shorter in a room where an electronic lighting
type (inverter or rapid start type) fluorescent lamp is installed.
• Do not install the air conditioner in places such as the 2. BEFORE INSTALLATION
following: When unpacking the indoor unit or moving the unit after
1. Where there is mist of oil, oil spray or vapour for example unpacked, hold the hangers (4 places) and do not apply
a kitchen. force to other parts (particularly refrigerant piping, drain
Resin parts may deteriorate, and fall out or water may piping).
leak. • Make sure to check in advance that the refrigerant to be
2. Where corrosive gas, such as sulfurous acid gas, is used for installation work is R410A.
produced. (The air conditioner will not properly operate if a wrong
Corrosion of copper pipings or brazed parts may cause refrigerant is used.)
the refrigerant to leak. • For installation of the outdoor unit, refer to the installation
3. Where there is machinery which emits electromagnetic manual attached to the outdoor unit.
waves. • Do not throw away the accessories until the installation work
Electromagnetic waves may disturb the control system, is completed.
and cause malfunction of the equipment. • After the indoor unit is carried into the room, to avoid the
4. Where gases may leak, where carbon indoor unit from getting damaged, take measures to protect
or ignitable dust is suspended in the air or where volatile the indoor unit with packing materials.
such as thinner or gasoline, are handled. (1) Determine the route to carry the unit into the room.
If the gas should leak and remain around the air condi- (2) Do not unpack the unit until it is carried to the installa-
tioner, it may cause ignition. tion location.
• The air conditioner is not intended for use in a potentially Where unpacking is unavoidable, use a sling of soft
explosive atmosphere. material or protective plates together with a rope when
• Pay careful attention when transporting the product. lifting, to avoid damage or scratches to the indoor unit.
Carry the product by the handle sections indicated on the
• Have the customer actually operate the air conditioner while
packaging material.
looking at the operation manual.
Do not hold the PP band since the PP band can become
Instruct the customer how to operate the air conditioner
loose and may result in danger.
(particularly cleaning of the air filters, operation procedures,
• Do not touch the heat exchanger fins.
and temperature adjustment).
Inadvertently touching the fins can cause injury.

3P432203-4B

47
FXSQ-PAVE EDTFVN391827

• Do not use the air conditioner in a salty atmosphere such as CARRY OUT THE WORK GIVING CAUTION
coastal areas, vehicles, vessels or where voltage fluctuation
is frequent such as factories.
TO THE FOLLOWING ITEMS AND AFTER THE
• Take off static electricity from the body when carrying out WORK IS COMPLETED CHECK THESE AGAIN.
wiring and the control box lid is removed.
The electric parts may be damaged. (1) Items to be checked after the installation work is
completed
2-1 ACCESSORIES
Check if the following accessories are attached to the Items to be checked In case of defective Check column
indoor unit. Are the indoor and outdoor Drop · vibration ·
(1) Metal (3) Duct flange connection units rigidly fixed? noise
Name (2) Drain hose Are the installation works of
clamp screw Does not operate ·
the outdoor and indoor units
Quantity 1 pc. 1 pc. See below burnout
completed?
20·25·32 Have you carried out a leakage
6 pcs.
class test with the test pressure Does not cool / Does
40 specified in the outdoor unit not heat
10 pcs.
class installation manual?
50·63·80 Is the insulation of refrigerant
Shape 18 pcs.
class piping and drain piping Water leakage
100·125 completely carried out?
30 pcs.
class Does the drain flow out
Water leakage
140 smoothly?
34 pcs.
class Is the power supply voltage
identical to that stated in the Does not operate ·
Joint insulating (6) Sealing (7) Sealing manufacturer’s label on the burnout
Name (8) Clamp air conditioner?
material material material
Are you sure that there is no
Quantity 1 each 1 sheet 2 sheets 9 pcs. Does not operate ·
wrong wiring or piping or no
burnout
loose wiring?
Thin
Danger in case of
(4) For liquid Is earthing completed?
leakage
piping Are the sizes of electric
Shape Does not operate ·
wiring according to the
Large Medium burnout
Thick specification?
(Dark gray) (Dark gray)
(5) For gas Are any of air outlets or inlets
piping of the indoor and outdoor
units blocked with obstacles? Does not cool /
(It may lead to capacity drop Does not heat
(9) Washer (10) Wire (11) Washer due to fan speed drop or
Name Others
clamp sealing material for hanger malfunction of equipment.)
Quantity 4 pcs. 2 sheets 8 pcs. • Operation Is the external static Does not cool /
manual pressure set correctly? Does not heat
Shape Small • Installation
manual Have you recorded the
(Gray) refrigerant piping length Refrigerant charge
and the refrigerant charge amount is not clear
2-2 OPTIONAL ACCESSORIES amount added?
• A remote controller is required for the indoor unit. Make sure to recheck the items of “SAFETY PRECAUTIONS”.
• There are 2 kinds of remote controller; wired type and
wireless type. (2) Items to be checked at delivery
Install the remote controller to the place where the customer
has given consent. Items to be checked Check column
Refer to the catalog for the applicable model.
Have you carried out field setting? (if necessary)
(Refer to the installation manual attached to the remote
controller for how to install.) Are the control box lid, the air filter and the suction
• The indoor unit can be switched to lower suction. grille attached?
(Refer to 4. PREPARATION BEFORE INSTALLATION.) Does the cool air discharge during the cooling
The side cover plate (KDBD63A160) is required in the case operation and the warm air discharge during the
heating operation? Does the indoor unit makes
of wiring from the bottom surface at bottom suction.
unpleasant sound of air discharge?
For installation work, refer to the instruction sheet provided
Have you explained how to operate the air
with the side cover plate. <Except for 140 class>
conditioner showing the operation manual to the
customer?
Have you explained the description of cooling,
heating, program dry and automatic (cooling/
heating) given in the operation manual to the
customer?

3P432203-4B

48
FXSQ-PAVE EDTFVN391827

If you set the fan speed at thermostat OFF, did you [ Required installation space ]
explain the set fan speed to the customer. Figures indicate the minimum required installation space.
Have you handed the operation manual and the
installation manual to the customer?
Have you checked that there is no generation
of abnormal noise (i.e., noise resulting from
contamination or missing parts)?
Is the printed circuit board switch not on the
emergency (EMG.) side?
The switch is factory set to the normal (NORM.) side.
If an optional accessory is in use, did you check the
operation of the optional accessory and make field

or more
settings as needed?

450mm
Maintenance Maintenance
space for
Is the remote controller icon displayed? Is the space for
electrical
drain pan
remote controller connected to the master unit if the components
system is in simultaneous multi operation? Secure the maintenance
Have you explained failure examples of space for the drain pan and
3. SELECTION OF INSTALLATION LOCATION? electrical components.
Fig. 1
Points of the operation explanation

or more
20mm
In addition to the general usage, since the items in the
operation manual with the WARNING and
CAUTION marks are likely to result in human bodily

H1=245mm*

H2 or more*
injuries and property damages, it is necessary not only
to explain these items to the customer but also to have
the customer read them.
Furthermore, it is necessary to have the customer read
through the troubleshooting items while explaining the

2500mm
or more
above items.
Ceiling

3. SELECTION OF INSTALLATION LOCATION Floor

Hold the hangers at 4 locations to move the indoor unit Fig. 2


when unpacking or after unpacked, and do not apply force
to the piping (refrigerant and drain) and air outlet flange. • * Dimension H1 indicates the product height.
If the temperature and humidity in the ceiling is likely to • * Secure a downward slope of at least 1/100 in
exceed 30°C, RH80%, use the additional insulation stick to 7. DRAIN PIPING WORK and determine dimension H2.
the indoor unit.
<Failure example>
Use the insulation such as glass wool or polyethylene
If there is an obstacle in the airflow path or proper installation
that has thickness of 10 mm or more. However, keep the
space is not provided, the indoor unit will cause air volume
insulated outside dimension smaller than the ceiling
reduction and take in air blown out of the indoor unit,
opening so that the unit may go through the opening at
thus resulting in performance degradation or turning the
installation.
thermostat OFF frequently.
(1) Select the installation location that meets the following
conditions and get approval of the customer. CAUTION
• Where the cool and warm air spreads evenly in the • Install the indoor and outdoor units, power supply wiring,
room. remote controller wiring and transmission wiring at least
• Where there are no obstacles in the air passage. 1 meter away from televisions or radios to prevent image
• Where drainage can be ensured. interference or noise.
• Where the ceiling’s lower surface is not remarkably (Depending on the radio waves, a distance of 1 meter may
inclined. not be to eliminate the noise.)
• Where there is strength to withstand the mass • Install the indoor unit as far as possible from
of the indoor unit. (If the strength is the in- lamps.
door unit may vibrate and get in contact with the ceiling If a wireless remote controller kit is installed, the transmis-
and generate unpleasant chattering noise.) sion distance may be shorter in a room where an electronic
• Where a space for installation and service can lighting type (inverter or rapid start type) lamp is
be ensured. (Refer to Fig. 1 and Fig. 2) installed.
• Where the piping length between the indoor and the out -
door units is ensured within the allowable length. (Refer
to the installation manual attached to the outdoor unit.)
• Where there is no risk of gas leak.

3P432203-4B

49
FXSQ-PAVE EDTFVN391827

(2) Use hanging bolts for installation. Control box


Investigate if the installation place can withstand the mass

20 or more
of the indoor unit and, if necessary, hang the indoor unit
with bolts after it is reinforced by beams etc.
Ceiling

4. PREPARATION BEFORE INSTALLATION


(1) Check the relation of location between the ceiling Inspection port
opening and the indoor unit hanging bolts. (unit [mm]) A
• Provide one of the following service spaces for the Inspection Inspection
maintenance and inspection of the control box and port 1 port 3
drain pump or for other services. (450×450)

200mm
(Indoor unit size

or less
1. Inspection ports 1 and 2 (450 × 450) (Fig. 3-1) and + 300 or more)
a minimum space of 300 mm at the bottom of the

D=B+300 or more
product (Fig. 3).
2. Inspection port 1 (450 × 450) on the control box side
and inspection port 2 on the bottom of the product. Control box
(Fig. 4, arrow A-1)

B
3. Inspection port 3 on the bottom of the product and on
the bottom side of the control box. (Fig. 4, arrow A-2) Inspection port 2
800 800 Control box
Control box
(Indoor unit
300 or more

Arrow A-1 size or more) Arrow A-2

< In the case of (1)-2, 3 >

Fig. 4
Table 1 (unit [mm])
Model B C D
Ceiling Inspection port 20·25·32 class 550 588 850
40 class 700 738 1000
< In the case of (1)-1 >
50·63·80 class 1000 1038 1300
Fig. 3
100·125 class 1400 1438 1700
800 140 class 1550 1588 1850
Inspection port 1
630 (450×450)
(Hanging bolt pitch)
(2) Mount canvas ducts to the air outlet and inlet so that
200 or less

Hanging bolts (× 4)
the vibration of the indoor unit will not be transmit-
ted to the ducts or ceiling. Furthermore, attach sound
Control box
absorbing material (thermal insulation material) to the
duct inner walls and anti-vibration rubber to the hang-
ing bolts (refer to 8. DUCT WORK).
500

(Hanging bolt pitch)

(3) The indoor unit is set to standard external static pres-


sure.
• If external static pressure is higher or lower than the
C
B

Air outlet standard set value, the remote controller may be used to
make on-site setting change in the external static pres-
Bottom of Air inlet
Inspection port 2* indoor unit
sure.
(450×450) Refer to 10. FIELD SETTING.
(For drain pan
removal and * Inspection port 2 is not required
(4) Open installation holes
component replacement) if the bottom space under the product (in the case of installation onto the existing ceiling).
is accessible for work. • Open the installation holes on the ceiling of the instal-
Fig. 3-1 lation location, and work on the refrigerant piping, drain
piping, remote controller wiring (unless a wireless re-
mote controller is used), and wiring between the indoor
and outdoor units to the piping connection port and
wiring connection port of the indoor unit (refer to each
piping and wiring procedure items).
• Ceiling framework reinforcement may be required in
order to keep the ceiling horizontal and prevent ceiling
vibration after opening the ceiling holes. For details,
consult your building and upholstery work contractors.
(5) Install the hanging bolts.
• Use M8 or M10 bolts for hanging the indoor unit.
Use hole-in-anchors for the existing bolts and embed-
ded inserts or foundation bolts for new bolts, and the
indoor unit to the building so that it may withstand
the mass of the unit.

3P432203-4B

50
FXSQ-PAVE EDTFVN391827

In addition, adjust clearance (50 - 100 mm) from the ceil- 5. INSTALLATION OF INDOOR UNIT
ing in advance.
Depending on the optional parts, it may be easier to attach
them before installing the indoor unit. Refer to also the
<Installation examples> installation manual attached to the optional parts.
For installation, use the attached installation parts and
Ceiling slab
specified parts.
Foundation bolt (1) Install the indoor unit temporarily.
Long nut or • Fix the hanger to the hanging bolt.
Indoor turnbuckle Make sure to securely the hanger with the nut and the
unit washer for hanger (11) from the upper and lower side.
Hanging bolt
(Refer to Fig. 6)
Note) Components shown in the figure above are If the washer clamp (9) is used, the upper side washer
all local procurement. for hanger (11) may be protected from falling off.
(Refer to Fig. 7)
(6) In the case of changing the preset suction to bottom [ Fix the hanger ]
side suction, replace the chamber cover and the suc- Field supply
tion (Refer to Fig. 5)
1. Remove the suction and chamber cover.
2. Replace the suction and the chamber cover. Washer for
hanger (11)
CAUTION (accessory)
• Secure a maintenance space for the drain pan
and electrical components before installing the indoor
unit.
Tighten
• Secure a maintenance space for the
(double nut)
chamber, and peripheral components before installing the
indoor unit. Fig. 6

<20-125 class> [ Washer fixing ]


Suction flange Washer Upper nut
clamp (9)
(accessory)
Insert Washer for
hanger (11)
(accessory)

Replacement
Chamber cover Fig. 7
<140 class> • Keep the air outlet covered with a protective sheet to prevent
Suction flange weld spatter and other foreign materials from entering the
indoor unit and damaging the resin drain pan.
(If holes or cracks are generated in the resin drain pan, water
can leak.)
(2) Adjust so that the unit is properly positioned.
(3) Check the level of the unit. (Refer to Fig. 8)
(4) Remove the washer clamp (9) used for preventing the
washer for hanger (11) from dropping and tighten the up-
Chamber cover Replacement per side nut.
Hanger

Note)
1. Be sure to remove chamber cover one side by
one side.
2. For this model, maintenance of the control box
through side is only available. Bottom of
Maintenance through bottom is not available. Level product
Fig. 5 Vinyl tube
Feed water into the tube and
set the indoor unit to the water
levels on the left and right.
[Maintaining horizontality]
Fig. 8

3P432203-4B

51
FXSQ-PAVE EDTFVN391827

Torque wrench
CAUTION
• Install the indoor unit leveled.
If the indoor unit is inclined and the drain piping side gets Spanner
high, it may cause malfunction of switch and result in
water leakage.
• Attach nuts on the upper and lower side of hanger. Flare nut
If there is no upper nut and the lower nut is over-tightened,
the hanger and the top plate will deform and cause abnormal
sound.
• Do not insert materials other than that into Union joint
the clearance between the hanger and the washer for Fig. 9
hanger (11).
Unless the washers are properly attached, the hanging Coat the flared inner surface
bolts may come off from the hanger. only with ether oil or ester oil

WARNING
The indoor unit must be securely installed on a place
that can withstand the mass. Fig. 10
If the strength is the indoor unit may fall down Table 2
and cause injuries. Piping Tightening Dimension for
size torque processing flare Flare shape
(mm) (N·m) A (mm)
6. REFRIGERANT PIPING WORK φ 6.4 15.7 ± 1.5 8.9 ± 0.2


• For the outdoor unit refrigerant piping, refer to the installation

°±
manual attached to the outdoor unit.

45
φ 9.5 36.3 ± 3.6 13.0 ± 0.2 R0.4-0.8
• Carry out insulation of both gas and liquid refrigerant piping

90°±2°
securely. If not insulated, it may cause water leakage. For φ 12.7 54.9 ± 5.4 16.4 ± 0.2

A
gas piping, use insulation material of which heat resistant
temperature is not less than 120°C. φ 15.9 68.6 ± 6.8 19.5 ± 0.2
For use under high humidity, strengthen the insulation
material for refrigerant piping. If not strengthened, the
surface of insulation material may sweat. CAUTION
• Before installation work, make sure that the refrigerant
Do not have oil adhere to the screw part of resin
is R410A. (Unless the refrigerant is R410A, the normal
parts.
operation cannot be expected.)
If oil adheres, it may weaken the strength of screwed part.
CAUTION Do not tighten nuts too tight.
If a flare nut cracks, the refrigerant may leak.
This air conditioner is a dedicated model for new re-
frigerant R410A. Make sure to meet the requirements • If there is no torque wrench, use Table 3 as a rule of
shown below and carry out installation work. thumb.
• Use dedicated piping cutters and tools for When tightening a nut with a spanner harder and
R410A. harder, there is a point where the tightening torque sud-
• When making a connection, coat the inner denly increases.
surface only with ether oil or ester oil. From that position, tighten the nut additionally at the angle
• Use only the nuts attached to the air conditioner. shown in Table 3.
If other nuts are used, it may cause refrigerant After the work is check securely that there is no
leakage. gas leak.
• To prevent contamination or moisture from getting If the nut is not tightened as instructed, it may cause slow
into the piping, take measures such as pinching or refrigerant leak and result in malfunction (such as does
taping the pipings. not cool or heat).
Do not mix substance other than the refriger- Table 3
ant such as air into the refrigeration circuit. Piping size Tightening Recommended arm length of
If the refrigerant leaks during the work, ventilate the (mm) angle tool used
room. φ 6.4 60° - 90° approx. 150 mm
• The refrigerant is pre-charged in the outdoor unit. φ 9.5 60° - 90° approx. 200 mm
• When connecting the pipings to the air conditioner, make φ 12.7 30° - 60° approx. 250 mm
sure to use a spanner and a torque wrench as shown in φ 15.9 30° - 60° approx. 300 mm
Fig. 9.
• For the dimension of part and the tightening torque, CAUTION
refer to the Table 2. Insulation of piping must be carried out up to the
• When making a connection, coat the inner connection inside the casing.
surface only with ether oil or ester oil. If the piping is exposed to the atmosphere, it may cause
(Refer to Fig. 10) sweating, burn due to touching the piping, electric shocks or
Then, turn the nut 3 to 4 times with your hand and a fire due to the wiring touching the piping.
screw in the nut.

3P432203-4B

52
FXSQ-PAVE EDTFVN391827

• After leak test, referring to Fig. 11, insulate both the gas • Before brazing refrigerant piping, have nitrogen
and liquid piping connection with the attached joint in- through the refrigerant piping and substitute air with nitro-
sulating material (4) and (5) to prevent the pipings from gen (NOTE 1) (Refer to Fig. 12). Then, carry out brazing
getting exposed. (NOTE 2).
Then, tighten both the ends of insulating material with the After all the brazing works are carry out
clamp (8). connection with the indoor unit. (Refer to Fig. 11)
• Wrap the sealing material (Medium) (7) around the joint
insulating material (4) and (5) nut section), both the Pressure reducing valve
gas and liquid piping. Taping
• Make sure to bring the seam of joint insulating material (4) Brazing place
and (5) to the top.
Gas side piping insulating method Nitrogen
Joint insulating
material (5) Refrigerant piping Stop valve
(accessory) Nitrogen
Flare nut Piping insulating Fig. 12
connection material (main unit) Wind around the
piping until top of the
Bring the flare nut connection,
NOTE
seam Do not leave beginning at the base. 1. The proper pressure for having nitrogen through the
to the top. clearance. piping is approximately 0.02 MPa, a pressure that makes
one feel like slight breeze and can be obtained through a
pressure reducing valve.
Indoor unit
2. Do not use when brazing refrigerant piping.
Clamp (8) Use phosphor copper brazing metal (BCuP-2: JIS Z
Piping (accessory) Sealing material 3264/B-Cu93P-710/795: ISO 3677) that does not require
insulating
Tighten the portion (7) Medium
material
where overlapped by (accessory)
(field supply) (If chlorinated is used, the piping will be corroded and,
the piping insulating
material. in addition if is contained, the refrigerant oil will
Do not expose the
piping in order to be deteriorated and the refrigerant circuit will be affected
prevent the vapor badly.)
condensation. 3. When carrying out leakage test of refrigerant piping and
the indoor unit after the installation of indoor unit is -
ished, the connecting outdoor unit installation
manual for test pressure.
Refer to also the outdoor unit installation manual or techni-
cal document for refrigerant piping.
4. In case of refrigerant shortage due to forgetting additional
refrigerant charge etc., it will result in malfunction such as
Gas piping does not cool or does not heat.
Refer to the outdoor unit installation manual or technical
Liquid piping document for refrigerant piping.

Liquid side piping insulating method CAUTION


Joint insulating Do not use antioxidant when brazing piping.
material (4) It may result in malfunction of components and clogging of
(accessory) piping due to residue.
Flare nut Piping insulating
connection material (main unit)
Wind around the
Bring the piping, beginning 7. DRAIN PIPING WORK
seam Do not leave at the base.
clearance. (1) Carry out drain piping.
to the top.
Carry out drain piping so that drainage is ensured.
• Select the piping diameter equal to or larger than
Indoor unit (except for riser) that of the connection piping (polyvi-
nyl chloride piping, nominal diameter 25 mm, outside
Piping Clamp (8) Sealing material diameter 32 mm).
insulating (accessory) (7) Medium • Install the drain piping as short as possible with down-
material (accessory)
Tighten the portion ward inclination of 1/100 or more and without such that
(field supply)
where overlapped by air may not stagnate. (Refer to Fig. 13) (It may cause
Do not expose the the piping insulating
material. abnormal sound such as bubbling noise.)
piping in order to
prevent the vapor
condensation.

Fig. 11

3P432203-4B

53
FXSQ-PAVE EDTFVN391827

1~1.5 m <In case of sticking vinyl tape>

Support Tightened part


Downward

approx. 90°
inclination of
1/100 or more
Good Vinyl tape

Stick vinyl tape without


tearing the sealing
material (Large) (6).

Wrong
<In case of bending the tip>
Fig. 13
Tightened part
CAUTION

approx. 90°
If drain stagnates in the drain piping, the piping may be
clogged.

• If downward inclination cannot be ensured,


carry out upward drain piping.
Bend the tip without tearing the
• Install supports at a distance of 1 to 1.5 m so that the pip-
sealing material (Large) (6).
ing may not (Refer to Fig. 13)
• Make sure to use the attached drain hose (2) and the Fig. 15
metal clamp (1).
< Caution to be taken when carrying out upward drain
Insert the drain hose (2) into the drain socket up to the
piping (Refer to Fig. 16) >
point where the socket diameter becomes larger.
• The maximum height of the drain riser is 675 mm. Since
Put the metal clamp (1) to the taped hose end and
the drain pump mounted on this indoor unit is a high
tighten the metal clamp (1) with torque 1.2~1.5 N·m
head type, from the characteristic point of view, the
(120~150 N·cm).
higher the drain riser the lower the draining noise.
Indoor unit Metal clamp (1) Therefore, the drain riser of 300 mm or higher is recom-
(accessory) mended.
Drain hose (2) • For upward drain piping, keep the horizontal piping dis-
(accessory) tance of 300 mm or less between the drain socket root
to the drain riser.
VP25 side (unit [mm])
Tape Ceiling slab
Fig. 14 300 or less 1~1.5 m
Support
CAUTION

(850 or less)
• Do not tighten the metal clamp (1) with the torque more
than the value.
Adjustable
The drain hose (2), the socket or the metal clamp (1) may
(675 or less)
be damaged.
Upward drain piping
• Wrap the vinyl tape around the end of the metal clamp Metal clamp (1)
(Field supply)
(1) so that the sealing material (Large) (6) to be used at (accessory)
the next process may not be damaged with the clamp Drain hose (2)
end or bend the tip of the metal clamp (1) inward as (accessory)
shown. (Refer to Fig. 15)

Drain hose (2)


(accessory)

Level or upward
inclination
Keep the drain hose level or make a slight up-grade so
that air may not stagnate in the drain hose.
If air stagnates, the drain may flow oppositely when
the drain pump stops and generate abnormal sound.

Fig. 16

3P432203-4B

54
FXSQ-PAVE EDTFVN391827

• If a person is not present, after the electric wir-


CAUTION ing work is check the drainage according to the
• To avoid the attached drain hose (2) getting excessive method in [When the electric wiring work is
force, do not bend nor twist it. .
It may cause water leakage. 1. Open the control box lid and connect the single phase
• As for drain piping connection, do not connect the drain 220 - 240 V power supply to the terminal (L, N) on the
hose directly to a sewage that gives off ammonia odor. terminal block (X1M).
(The ammonia in the sewage may go through the drain Connect the earth wiring to the earth terminal.
piping and corrode the heat exchanger of the indoor unit.) 2. Make sure the control box lid is closed before turning
• In case of centralized drain piping, carry out piping work on the power supply.
according to the procedure shown in the following Fig. 17. • Throughout the whole process, carry out the work
giving caution to the wiring around the control box
0 ~ 675 mm

so that the connectors may not come off.


3. Gradually pour 1 liter of water from the air outlet on
the left side of the drain socket into the drain pan
giving caution to avoid splashing water on the electric
components such as drain pump. (Refer to Fig. 18)
Centralized drain piping 4. When the power supply is turned on, the drain pump
Make a downward inclination of 1/100 will operate. Drainage can be checked at the trans-
or more to avoid stagnation of air. parent part of the drain socket.
(The drain pump will automatically stop after 10
If water stagnates in the drain
piping, it may cause clogging of minutes.)
drain piping. The drainage of water can be with water
level change in the drain pan through the access
Fig. 17 window.
• As for the size of centralized drain piping, select the size • Do not connect the drain piping directly to the sew-
that meets the capacity of indoor units to be connected. age that gives off ammonia odor.
(Refer to the technical document.) The ammonia in the sewage may go through the
• Positioning the upward drain piping at an angle may cause drain piping and corrode the heat exchanger of the
switch malfunction and lead to water leakage. indoor unit.
• While replacing with new indoor unit, use the attached • Do not apply external force to the switch. (It
new drain hose (2) and the metal clamp (1). may result in malfunction)
If an old drain hose or a metal clamp is used, it may • Do not touch the drain pump.
cause water leakage. Touching the drain pump may cause electric shocks.
5. Turn off the power supply after checking drainage,
(2) After piping is check if the drain and remove the power supply wiring.
smoothly. 6. Attach the control box lid as before.
[When the electric wiring work is
(3) Sweating may occur and result in water leakage.
• Gradually pour 1 liter of water from the inspection port
Therefore, make sure to insulate the following 2 loca-
at the bottom of the drain socket on the left side of the
tions (drain piping that laid indoors and drain sockets).
drain socket into the drain pan giving caution to avoid
• Use the provided sealing material (large) (6), and per-
splashing water on the electric components such as
form the thermal insulation of the metal clamp (1) and
drain pump and drainage by operating the
drain hose (2) after checking the drainage of water.
indoor unit under cooling mode according to
(Refer to Fig. 19)
10. FIELD SETTING. (Refer to Fig. 18)
Control box
Sealing material - Large
(6) (accessory)
Drain socket Control box lid
Filling port
Drain pan
No clearance is
allowed.

Terminal block Drain hose (2) Sealing material (Large) (6)


for wiring between (accessory)
the indoor and
(accessory)
outdoor units
Start wrapping from where the
Air outlet metal clamp (1) is tightened.
Screw
Access Drain pump
Drain socket window position
(with rubber cap)
Plastic container
for pouring water Metal clamp (1)
(accessory)
[Method of adding water]
Fig. 18
Wrap the sealing material (Large) (6)
[When the electric wiring work is not so that the metal clamp (1) end side
• The electric wiring works (including earthing) must be may be doubled.
carried out by a electrician. Fig. 19

10

3P432203-4B

55
FXSQ-PAVE EDTFVN391827

8. DUCT WORK 9. ELECTRIC WIRING WORK


Pay the utmost attention to the following items and
conduct the ductwork. 9-1 GENERAL INSTRUCTIONS
• Check that the duct is not in excess of the setting range of • Make certain that all electric wiring work is carried out by
external static pressure for the unit. (Refer to the technical qualified personnel according to the applicable legislation
datasheet for the setting range.) and this installation manual, using a separate dedicated
• Attach a canvas duct each to the air outlet and air inlet so circuit.
that the vibration of the equipment will not be transmitted to Insufficient capacity of the power supply circuit or improper
the duct or ceiling. electrical construction may lead to electric shocks or a fire.
Use a sound-absorbing material (insulation material) for the • Make sure to install an earth leakage breaker.
lining of the duct and apply vibration insulation rubber to the Failure to do so may cause electric shocks and a fire.
hanging bolts. • Do not turn on the power supply (branch switch, branch
• At the time of duct welding, perform the curing of the duct so overcurrent circuit breaker) until all the works are finished.
that the sputter will not come in contact with the drain pan for • Multiple number of indoor units are connected to one
the filter. outdoor unit. Name each indoor unit as A-unit, B-unit ….. and
• If the metal duct passes through a metal lath, wire lath, or the like. When these indoor units are wired to the outdoor unit
plate of a wooden structure, separate the duct and wall and the BS unit, always wire the indoor unit to the terminal
electrically. indicated with the same symbol on the terminal block. If the
• Be sure to heat insulate the duct for the prevention of wiring and the piping are connected to the different indoor
dew condensation. (Material: Glass wool or styrene foam; units and operated, it will result in malfunction.
Thickness: 25 mm) • Make sure to earth the air conditioner.
• Be sure to attach the field supply air filter to the air inlet of the Earthing resistance should be according to applicable
unit or field supply inlet in the air passage on the air suction legislation.
side. (Be sure to select an air filter with a duct collection • Do not connect the earth wiring to gas or water pipings,
efficiency of 50 weight percent.) lightning conductor or telephone earth wiring.
• Explain the operation and washing methods of the locally • Gas piping .................Ignition or explosion may occur if
procured components (i.e., the air filter, air inlet grille, and air the gas leaks.
outlet grille) to the customer. • Water piping ..............Hard vinyl tubes are not effective
• Locate the air outlet grille on the indoor side for the earths.
prevention of drafts in a position where indirect contact with • Lightning conductor or telephone earth wiring ..................
people. Electric potential may rise abnormally if struck by a light-
• The air conditioner incorporates a function to adjust the fan ning bolt.
to rated speed automatically. (10. FIELD SETTING) • For electric wiring work, refer to also the “WIRING
Therefore, do not use booster fans midway in the duct. DIAGRAM” attached to the control box lid.
• Carry out wiring between the outdoor units, indoor units and
Connection method of ducts on air inlet and outlet sides. the remote controllers according to the wiring diagram.
• Connect the field supply duct in alignment with the inner side • Carry out installation and wiring of the remote controller
of the flange. according to the “installation manual” attached to the remote
• Connect the flange and unit with the flange connection screw (3). controller.
• Wrap aluminum tape around the flange and duct joint in • Do not touch the Printed Circuit Board assembly. It may
order to prevent air leakage. cause malfunction.
Flange on air inlet side Flange on air outlet side
(provided with the unit) (provided with the unit) 9-2 ELECTRICAL CHARACTERISTICS
Screws for duct Insulation material Table 4
flanges (3) (field supply)
Screws Units Power supply Fan motor
(accessory)
Air inlet Unit Air outlet for duct
flanges (3) Voltage
Insulation material Canvas duct Model Hz Volts MCA MFA kW FLA
(accessory) range
(field supply) (field supply)
Fig. 20 FXSQ20PAVE 0.8 15 0.078 0.6
FXSQ25PAVE 0.8 15 0.078 0.6
CAUTION
FXSQ32PAVE 0.8 15 0.078 0.7
Connect the flange and unit with the flange connection screw
(3) regardless of whether the duct is connected to the air FXSQ40PAVE 1.4 15 0.130 1.2
inlet side. FXSQ50PAVE 1.3 15 0.230 1.1
220- Max. 264
50
FXSQ63PAVE 240 Min. 198 1.8 15 0.230 1.4

FXSQ80PAVE 1.8 15 0.230 1.5

FXSQ100PAVE 2.5 15 0.300 2.0

FXSQ125PAVE 2.8 15 0.300 2.2

FXSQ140PAVE 3.1 15 0.350 2.5

11

3P432203-4B

56
FXSQ-PAVE EDTFVN391827

FXSQ20PAVE 0.8 15 0.078 0.6


• Connect the terminal as shown in Fig. 22.
• Do not carry out soldering finish when stranded wires are
FXSQ25PAVE 0.8 15 0.078 0.6 used. (Otherwise, the loosening of wires may result in
FXSQ32PAVE 0.8 15 0.078 0.7 abnormal heat radiation.)

FXSQ40PAVE 1.4 15 0.130 1.2


FXSQ50PAVE Max. 242 1.3 15 0.230 1.1
60 220
FXSQ63PAVE Min. 198 1.8 15 0.230 1.4

FXSQ80PAVE 1.8 15 0.230 1.5

FXSQ100PAVE 2.5 15 0.300 2.0

FXSQ125PAVE 2.8 15 0.300 2.2


Use wires the same in size
FXSQ140PAVE 3.1 15 0.350 2.5
(if the air conditioner is
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A) in simultaneous multi operation)
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A) Fig. 22
(Abnormal heating may occur if the wirings are not tightened
9-3 SPECIFICATION FOR FIELD SUPPLY FUSES securely.)
AND WIRING
• Use the required wirings, connect them securely and fix
Table 5 these wirings securely so that external force may not apply to
Remote controller wiring the terminals.
Power supply wiring • Use a proper screw driver for tightening the terminal screws.
Transmission wiring
Model If an improper screw driver is used, it may damage the screw
Field
fuses Wiring Size Wiring Size
head and a proper tightening cannot be carried out.
• If a terminal is over tightened, it may be damaged.
Refer to the table shown below for tightening torque of
FXSQ20PAVE
terminals.
FXSQ25PAVE Table 6
FXSQ32PAVE Tightening torque (N·m)
Terminal block for remote controller
FXSQ40PAVE Vinyl cord 0.88 ± 0.08
and transmission wirings
with sheath
FXSQ50PAVE H05VV-U3G 2.5 mm 2
Terminal for power supply 1.47 ± 0.14
or cable 0.75-
16A Earth terminal 1.47 ± 0.14
FXSQ63PAVE (2 core) 1.25 mm2
NOTE 1) NOTE 3)
• Do not carry out soldering when stranded wirings
FXSQ80PAVE NOTE 2) are used.
FXSQ100PAVE

FXSQ125PAVE WARNING
FXSQ140PAVE • When wiring, form the wirings orderly so that the control box
lid can be securely fastened. If the control box lid is not in
The lengths of remote controller wiring are as follows:
place, the wirings may come out or be sandwiched by the
Remote controller wiring (indoor unit - remote controller) ....Max. 500 m
box and the lid and cause electric shocks or a fire.
NOTE
1. Shows only in case of protected piping. Use H07RN-F in (1) Remove the control box lid.
case of no protection. (Do not lighter than 60245 IEC 57.)
2. Vinyl cord with sheath or cable (Insulated thickness : 1 mm
or more)
3. This size is based on IEC 60335-1 (Table 11), and this size
must comply with local codes.
Screws
(2 points)
9-4 WIRING CONNECTION METHOD
CAUTION FOR WIRING
Fig. 23
• For connection to the terminal block, use ring type crimp
style terminals with insulation sleeve or insulate the wirings
properly.
Wiring
Insulation sleeve

Ring type crimp


style terminals
Fig. 21

12

3P432203-4B

57
FXSQ-PAVE EDTFVN391827

(2) Connect the wiring into the control box through the (5) Securely each wire with the provided clamp mate-
wiring intake beside the control box. rial (8).
Wiring intake Wiring intake Clamp (8)
(low voltage) (high voltage) (accessory)
Remote controller Power supply
wiring wiring
Transmission Earth wiring
wiring
Power supply wiring,
Remote controller wiring and earth wiring
Transmission wiring
Fig. 27

9-5 WIRING EXAMPLE


Fig. 24 CAUTION
(3) Follow the instructions below and perform wiring in Be sure to install an earth leakage breaker to the outdoor unit.
the control box. This is to avoid electric shocks or a fire.

Terminal block (X1M) < No. 1 system: When 1 remote controller is used for 1
for power supply wiring, indoor unit. >
and earth wiring
Power supply
1~
220-240 V
Connection method 50 Hz
for power supply wiring,
X1M or
and earth wiring
1~
220 V Outdoor
Securely fix the wiring to 60 Hz unit
the provided wiring fixture L N
IN/D OUT/D
with the clamp (8). F1 F2 F1 F2

Remote controller wiring


(low voltage)

Connect the wiring Indoor Indoor


through the control box unit A unit B
up to the sheathed part.
L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2
Terminal block (X2M) for remote controller wiring,
and transmission wiring
P1 P2 F1 F2 T1 T2 Prohibited Most
Never connect the downstream
power supply wiring. Indoor unit
Transmission wiring P1 P2 P1 P2 P1 P2
No polarity
Remote controller wiring Power supply wiring Remote Remote Remote
No polarity (high voltage) controller controller controller
Earth wiring (high voltage) (option) (option) (option)
<Remote controller wiring method>
Fig. 25

(4) Mount the control box lid and wrap the wire sealing
material (small) (10) so that the wiring through hole
will be covered by the sealing material.
• Seal the clearance around the wirings with putty or insu-
lating material supply).
(If insects and small animals get into the indoor unit,
short-circuiting may occur inside the control box.)
Wiring through
hole Wire sealing material (small) (10)
(accessory)
Power supply wiring,
earth wiring, remote
controller wiring, or
transmission wiring

Wiring fixture
Fig. 26

13

3P432203-4B

58
FXSQ-PAVE EDTFVN391827

< No. 2 system: When carrying out group control or 2


remote controller control. > Terminal block
Power supply (X2M)
1~
220-240 V Terminal for remote
50 Hz controller wiring (P1, P2)
or
1~ No polarity
220 V Outdoor
60 Hz unit Note) It is not needed to set the
L N indoor unit address when
using group control.
IN/D OUT/D
F1 F2 F1 F2

(It is automatically set when


the power is turned on.) Remote Remote
controller 1 controller 2
Most down- (Main) (Sub)
stream
L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 < Caution >
indoor unit
Indoor Indoor • When using the group control and the 2 remote control-
unit A unit B lers control at the same time, connect the remote control-
ler 2 (Sub) to the indoor unit at the end of the crossover
Remote P1 P2 P1 P2 P1 P2 wiring (the largest No.). (Refer to Fig. 28)
controller
Case of group Remote Remote Indoor unit
(option) Indoor unit 1 Indoor unit 2 largest No.
control controller controller
(option)
For use with 2
remote controllers

< No. 3 system: When BS unit is used > Remote Crossover Remote
controller 1 wiring (Remote controller 2
Outdoor unit BS unit (Main) controller) (Sub)
Power supply L N
IN/D OUT/D OUT/D IN/D
Fig. 28
1~ F1 F2 F1 F2 F1 F2 F1 F2

220-240 V 9-7 FOR CENTRALIZED CONTROL


50 Hz • When centralized equipment (such as centralized controller)
or is used for control, it is required to set the group No. on the
1~ remote controller.
220 V For details, refer to the manuals attached to the centralized
60 Hz equipment.
L N P1 P2 F1 F2 T1 T2
• Connect the centralized equipment to the indoor unit
Indoor unit A connected to the remote controller.

9-8 FOR REMOTE CONTROL (FORCE OFF OR ON /


P1 P2 Remote controller
(option)
OFF OPERATION)
(1) Wiring method and specification
NOTE • Remote control is available by connecting the external
1. Remote controller wiring and transmission wiring have no input to the terminal T1 and T2 on the terminal block for
polarity. remote controller and transmission wiring (X2M).
Sheathed vinyl
WARNING Wiring
cord or 2 core
Be sure to install an earth leakage breaker. F2 T1 T2 cable
Failure to do so may cause electric shocks and a FORCED Wiring size 0.75-1.25 mm2
OFF Wiring length Max. 100 m
Contact that can
9-6 FOR CONTROL WITH 2 REMOTE CONTROL- Input A External make and break
LERS (TO CONTROL 1 INDOOR UNIT WITH 2 contact spec the min. load of
REMOTE CONTROLLERS) DC 15 V · 1 mA
• For control with 2 remote controllers, set one remote
controller as Main and the other remote controller as Sub. (2) Actuation
• Input A of FORCED OFF and ON/OFF OPERATION will
< Changeover method from Main to Sub and vice versa > be as the table shown below.
Refer to the installation manual attached to the remote
controller. Input A = ON Input A = OFF
In case of FORCED Remote controller Remote controller
< Wiring method > OFF prohibited permitted
(1) Remove the control box lid. In case of ON/OFF
(2) Carry out additional wiring from the remote controller Operation Stop
OPERATION
2 (Sub) to the terminals (P1, P2) for remote controller
wiring on the terminal block (X2M) in the control box. (3) How to choose FORCED OFF or ON/OFF OPERATION
• For choosing FORCED OFF or ON/OFF OPERATION,
setting by remote controller is required.
(Refer to 10. FIELD SETTING)

14

3P432203-4B

59
FXSQ-PAVE EDTFVN391827

10. FIELD SETTING Return to the “Basic screen” (“Normal mode” if a wireless
remote controller is used), and press the ON/OFF button.
CAUTION The operation lamp is lit, and the indoor unit will go into fan
operation for air volume automatic adjustments (at which
Before carrying out field setting, check the items mentioned in time, do not adjust the opening of the air outlet or inlet).
(1) Items to be checked after the installation work is The air volume adjustments will automatically terminate
completed on page 3. approximately 1 to 15 minutes after the indoor unit comes
• Check if all the installation and piping works for the air into operation, and the operation lamp will be OFF and the
conditioner are completed. indoor unit will come to a stop.
• Check that the outside panel and piping cover of the indoor Table 7
and outdoor units are closed. FIRST SECOND CODE No.
Setting
Mode No. CODE
content 01 02 03
< FIELD SETTING > No.
After turning on the power supply, carry out field setting Air volume
Air volume Air volume
adjust-
from the remote controller according to the installation 11 (21) 7 adjust- OFF adjust-
ment
state. ment ment start
completion
• Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.”
and “SECOND CODE No.”. (4) After the air conditioner comes to a stop, be sure to check
The settings shown by in the following tables indicate with Mode No. [21] per indoor unit that the above SECOND
those when shipped from the factory. CODE No. is “02”. If the operation of the air conditioner
• The method of setting procedure and operation is shown in does not stop automatically or the SECOND CODE No. is
the installation manual attached to the remote controller. not set to “02”, repeat the setting procedure from (3).
(Note) Though setting of “Mode No.” is carried out as a group, CAUTION
if you intend to carry out individual setting by each
indoor unit or confirmation after setting, carry out • If airflow pathway changes, such as duct and air outlet
setting with the Mode No. shown in the parenthesis ( ). changes, are made after air volume adjustments, be sure to
• Ask your customer to keep the manual attached to the remote make “Air volume automatic adjustment” again.
controller together with the operation manual. • If airflow pathway changes, such as duct and air outlet
• Do not carry out settings other than those shown in the table. changes, are made after 11. TEST OPERATION or air
• Settings are performed by selecting “Mode No.”, “FIRST conditioner relocation, contact your dealer.
CODE No.”, and “SECOND CODE No.”. (b) Select external static pressure with the remote controller.
Check with Mode No. [21] per indoor unit that the SECOND CODE
10-1 Settings for external static pressure No. for the above “Air volume adjustment” is set to “01” (OFF).
• Make settings in either method (a) or method (b). (The SECOND CODE No. is factory set to “01” (OFF).)
(a) Make settings with Air volume automatic adjustment Change the SECOND CODE No. by referring to the table below
function. according to the external static pressure of the duct to be
“Air volume automatic adjustment” function: The air volume connected.
is adjusted to the rated air volume automatically. Table 8
In case of 20-125 class
CAUTION FIRST SECOND
External static
Mode No.
• Be sure to check that the external static pressure is within pressure CODE No. CODE No.
the specification range before making settings. The external 30Pa (*1) 03
static pressure will not be automatically adjusted and air 40Pa (*1) 04
volume insufficiency or water leakage may result if the 50Pa 05
external static pressure is outside the range. (Refer to the 60Pa 06
technical document for the setting range of external static 70Pa 07
pressure.) 80Pa 08
90Pa 13(23) 6 09
(1) Check that the electrical wiring and duct work have been
100Pa 10
completed.
110Pa 11
(If the closing damper is set midway, be sure to check that
120Pa 12
the damper is opened. Furthermore, check that the air
passage on the suction side is provided with an air filter 130Pa 13
(field supply)). 140Pa 14
150Pa 15
(2) If air conditioner has more than one air outlet and air inlet,
(*1) The FXSQ50-125 class cannot be set to 30Pa or 40Pa.
be sure to make adjustments so that the air volume ratio of
each air outlet and the corresponding air inlet will conform In case of 140 class
to the designed air volume ratio. External static FIRST SECOND
Mode No.
pressure CODE No. CODE No.
In that case, set the operating mode to “Fan”. (In the case
of changing the air volume, press the fan speed button on 50Pa 05
the remote controller and change the current selection to 60Pa 06
“High”, “Medium”, or “Low”.) 70Pa 07
80Pa 08
(3) Make settings to adjust the air volume automatically.
After setting the operating mode to “Fan”, set the air con- 90Pa 09
13(23) 6
ditioner to setting mode with the operation of the air 100Pa 10
conditioner stopped. Select Mode No. [21] (11 in the case 110Pa 11
of batch settings), select FIRST CODE No. “7”, and set the 120Pa 12
SECOND CODE No. to “03”. 130Pa 13
140Pa 14

15

3P432203-4B

60
FXSQ-PAVE EDTFVN391827

10-2 SETTING WHEN AN OPTIONAL ACCESSORY IS 11. TEST OPERATION


ATTACHED • After cleaning the indoor unit inside, carry out test operation
• For setting when attaching an optional accessory, refer to the according to installation manual attached to the outdoor unit.
installation manual attached to the optional accessory.
• When the remote controller operation lamp flashes, it shows
10-3 SETTING FAN SPEED DURING THERMOSTAT OFF that something is abnormal.
• Set the fan speed according to the using environment after Check the malfunction codes on the remote controller.
consultation with your customer. The relation between the malfunction codes and malfunction
• When the fan speed is changed, explain the set fan speed to details is described in the operation manual attached to the
your customer. outdoor unit.Particularly, if the indication is one of those
Table 9 shown in the Table 11, it may be an error in the electrical
FIRST SECOND
wiring or the power supply is disconnected. Therefore,
Setting Mode No.
CODE No. CODE No.
recheck wiring.
Fan speed during LL 01 Table 11
cooling (Extra low) 12 (22) 6
thermostat OFF Setting 02 Remote controller
Details
LL indication
Fan speed during 01
heating (Extra low) 12 (22) 3 Though the central-
• The terminals (T1 · T2) for FORCED OFF on
thermostat OFF Setting 02 ized control is not
the indoor unit transmission terminal block is
carried out, the lamp
short circuited.
10-4 SETTING FILTER SIGN “ ” turns on.
• A message to inform the air filter cleaning time will be • The power supply to the outdoor unit is not
indicated on the remote controller. connected.
• Set the SECOND CODE No. shown in the Table 10 • The power supply wiring to the outdoor unit
according to the amount of dust or pollution in the room. “U4” turns on is not carried out.
• The periodical filter cleaning time can be shortened “UH” turns on • The transmission wiring and the remote
depending on the environment. controller wiring and FORCED OFF wiring
Table 10 are connected wrongly.
• The transmission wiring is disconnected.
Hours until FIRST SECOND
Contamination Mode No. • The power supply to the indoor unit is not
indication CODE No. CODE No.
connected.
Approx.
Normal
2500 hrs
01 • The power supply wiring to the indoor unit is
0 not carried out.
More Approx. No indication
contaminated 1250 hrs 10 (20) 02 • The remote controller wiring and the
transmission wiring and FORCED OFF
With indication 01
3 wiring are connected wrongly.
No indication* 02 • The remote controller wiring is disconnected.
* Use “No indication” setting when cleaning indication is not
necessary such as the case of periodical cleaning being carried out.
CAUTION
10-5 SWITCHING TIME OF THE DRY OPERATION AT After test operation is completed, check the items mentioned
VRTsmart control SETTING. in the clause 2 (2) Items to be checked at delivery on
• If you change the operation mode to “Dry” when VRTsmart page 3.
control is in effect, the operation mode is change to “Cooling” If the interior finish work is not completed when the test
after certain period of time.
If you want to continue dry operation longer, please change operation is finished, for protection of the air conditioner,
the setting position as mentioned in the table below. ask the customer not operate the air conditioner until the
(Setting position of factory setting is “0”.) interior finish work is completed.
※ If you keep dry operation longer, energy saving If the air conditioner is operated, the inside of the indoor
performance decrease. units may be polluted by substances generated from the
coating and adhesives used for the interior finish work
Mode Setting switch Setting position and cause water splash and leakage.
Dry operation number
number number
30 min 01
To the operator carrying out test operation
60 min 02
After test operation is completed, before delivering the air
10 10
90 min 03 conditioner to the customer, that the control box
Continuous (Not return lid, the air and suction grille are attached.
04 In addition, explain the power supply status (power supply
to Cooling)
ON/OFF) to the customer.
※ At the time of Group control setting, Dry operation time for the
indoor units in the same group shall be the same setting value.
12. WEIGHT AND DIMENSION
NOTE
Width Length Hight Weight
For VRTsmart control function it is necessary to connect Model
(mm.) (mm.) (mm.) (kg.)
with an outdoor unit with a compatible function.
FXSQ20•25•32PAVE 800 550 245 25

FXSQ40PAVE 800 700 245 27

FXSQ50•63PAVE 800 1,000 245 35

FXSQ80PAVE 800 1,000 245 37

FXSQ100PAVE 800 1,400 245 46

FXSQ125PAVE 800 1,400 245 47

FXSQ140PAVE 800 1,550 245 52

16

3P432203-4B

61
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

VRV is a trade mark of Daikin Industries, Ltd.


VRV Air Conditioning System is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982.
VRV is the trade mark of Daikin Industries, Ltd., which is derived from the technology we call “variable refrigerant volume.”

●Specifications, designs and other content appearing in this brochure are current as of March 2018 but subject to change without notice.

©All rights reserved 03/18 AK

You might also like