Professional Documents
Culture Documents
Edtfvn391827 Fxsq-Pa
Edtfvn391827 Fxsq-Pa
Edtfvn391827 Fxsq-Pa
201803
Engineering Data
FXSQ-PAVE
50 / 60 Hz
FXSQ-PAVE EDTFVN391827
FXSQ-PAVE
Middle Static Pressure
Ceiling Mounted Duct Type
50 / 60 Hz
1. Lineup..........................................................................................................2
2. Specifications..............................................................................................3
3. Dimensions..................................................................................................8
4. Piping Diagrams........................................................................................14
5. Wiring Diagrams........................................................................................15
6. Electric Characteristics..............................................................................16
7. Safety Devices Setting..............................................................................17
8. Capacity Tables.........................................................................................18
8.1 Cooling Capacity for Te: Auto..........................................................18
8.2 Cooling Capacity for Te: 6°C...........................................................18
8.3 Cooling Capacity for Te: 9°C...........................................................19
8.4 Heating Capacity..............................................................................19
9. Fan Performances.....................................................................................20
10. Airflow Auto Adjustment Characteristics...................................................29
11. Sound Levels.............................................................................................38
12. Centre of Gravity.......................................................................................43
13. Accessories...............................................................................................44
13.1 Optional Accessories (for Unit)........................................................44
13.2 Optional Accessories (for Controls).................................................45
14. Installation Manual....................................................................................46
1
FXSQ-PAVE EDTFVN391827
1. Lineup
2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW 9.0 kW 11.2 kW 14.0 kW 16.0 kW
Capacity range
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 6 HP
Capacity index 20 25 31.25 40 50 62.5 80 100 125 140
FXSQ 20PAVE 25PAVE 32PAVE 40PAVE 50PAVE 63PAVE 80PAVE 100PAVE 125PAVE 140PAVE
2
FXSQ-PAVE EDTFVN391827
2. Specifications
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class)
by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.
3
FXSQ-PAVE EDTFVN391827
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class)
by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.
4
FXSQ-PAVE EDTFVN391827
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class)
by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.
5
FXSQ-PAVE EDTFVN391827
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class)
by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.
6
FXSQ-PAVE EDTFVN391827
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: Btu/h=kW×3412
7.5 m, level difference: 0 m. cfm=m³/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m³/min×1000/60
+4. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class)
by remote controller.
+5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust
collection efficiency (gravity method) 50% or more.
+6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
+7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.
7
FXSQ-PAVE EDTFVN391827
3. Dimensions
3D095725C
8
FXSQ-PAVE EDTFVN391827
FXSQ40PAVE
Unit: mm
3D095726C
9
FXSQ-PAVE EDTFVN391827
FXSQ50PAVE
Unit: mm
3D096164C
10
FXSQ-PAVE EDTFVN391827
FXSQ63PAVE / FXSQ80PAVE
Unit: mm
3D095426F
11
FXSQ-PAVE EDTFVN391827
FXSQ100PAVE / FXSQ125PAVE
Unit: mm
3D095427H
12
FXSQ-PAVE EDTFVN391827
FXSQ140PAVE
Unit: mm
3D095727D
13
FXSQ-PAVE EDTFVN391827
4. Piping Diagrams
4D104913
14
FXSQ-PAVE EDTFVN391827
5. Wiring Diagrams
3D092752C
15
FXSQ-PAVE EDTFVN391827
6. Electric Characteristics
4D105290
16
FXSQ-PAVE EDTFVN391827
17
FXSQ-PAVE EDTFVN391827
8. Capacity Tables
8.1 Cooling Capacity for Te: Auto
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
18
FXSQ-PAVE EDTFVN391827
For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXSQ20PAVE 20 1.0 1.0 1.3 1.3 1.7 1.6 1.8 1.6 1.8 1.6 1.9 1.5 2.0 1.5
FXSQ25PAVE 25 1.3 1.3 1.7 1.6 2.0 1.8 2.3 1.9 2.3 1.8 2.5 1.8 2.6 1.8
FXSQ32PAVE 32 1.7 1.6 2.2 1.9 2.7 2.3 2.9 2.4 3.0 2.3 3.2 2.3 3.3 2.3
FXSQ40PAVE 40 2.1 2.1 2.6 2.6 3.3 3.1 3.6 3.2 3.8 3.2 4.0 3.0 4.2 3.1
FXSQ50PAVE 50 2.5 2.5 3.2 3.1 4.0 3.6 4.5 3.7 4.6 3.6 4.9 3.6 5.1 3.5
FXSQ63PAVE 63 3.3 3.3 4.1 4.0 5.1 4.5 5.7 4.7 5.9 4.7 6.2 4.6 6.5 4.6
FXSQ80PAVE 80 4.1 3.9 5.3 4.8 6.6 5.5 7.3 5.7 7.5 5.6 7.9 5.6 8.3 5.5
FXSQ100PAVE 100 5.3 5.2 6.7 6.3 8.3 7.3 9.1 7.5 9.3 7.4 9.9 7.3 10.4 7.2
FXSQ125PAVE 125 6.5 6.1 8.4 7.5 10.4 8.6 11.4 8.9 11.7 8.8 12.4 8.8 13.1 8.6
FXSQ140PAVE 140 7.5 7.1 9.6 8.6 12.0 9.9 13.0 10.2 13.5 10.1 14.3 10.1 15.0 9.8
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
19
FXSQ-PAVE EDTFVN391827
9. Fan Performances
FXSQ20PAVE / FXSQ25PAVE
3D095855A
20
FXSQ-PAVE EDTFVN391827
FXSQ32PAVE
3D095856A
21
FXSQ-PAVE EDTFVN391827
FXSQ40PAVE
3D095857A
22
FXSQ-PAVE EDTFVN391827
FXSQ50PAVE
3D095858A
23
FXSQ-PAVE EDTFVN391827
FXSQ63PAVE
3D095859A
24
FXSQ-PAVE EDTFVN391827
FXSQ80PAVE
3D095860A
25
FXSQ-PAVE EDTFVN391827
FXSQ100PAVE
3D095861A
26
FXSQ-PAVE EDTFVN391827
FXSQ125PAVE
3D095862A
27
FXSQ-PAVE EDTFVN391827
FXSQ140PAVE
3D095863A
28
FXSQ-PAVE EDTFVN391827
FXSQ20PAVE / FXSQ25PAVE
3D095846A
29
FXSQ-PAVE EDTFVN391827
FXSQ32PAVE
3D095847A
30
FXSQ-PAVE EDTFVN391827
FXSQ40PAVE
3D095848A
31
FXSQ-PAVE EDTFVN391827
FXSQ50PAVE
3D095849A
32
FXSQ-PAVE EDTFVN391827
FXSQ63PAVE
3D095850A
33
FXSQ-PAVE EDTFVN391827
FXSQ80PAVE
3D095851A
34
FXSQ-PAVE EDTFVN391827
FXSQ100PAVE
3D095852A
35
FXSQ-PAVE EDTFVN391827
FXSQ125PAVE
3D095853A
36
FXSQ-PAVE EDTFVN391827
FXSQ140PAVE
3D095854A
37
FXSQ-PAVE EDTFVN391827
FXSQ20PAVE / FXSQ25PAVE
4D095804B
FXSQ32PAVE
4D095805B
38
FXSQ-PAVE EDTFVN391827
FXSQ40PAVE
4D095806B
FXSQ50PAVE
4D095807B
39
FXSQ-PAVE EDTFVN391827
FXSQ63PAVE
4D095808B
FXSQ80PAVE
4D095809B
40
FXSQ-PAVE EDTFVN391827
FXSQ100PAVE
4D095810B
FXSQ125PAVE
4D095811B
41
FXSQ-PAVE EDTFVN391827
FXSQ140PAVE
4D095812B
42
FXSQ-PAVE EDTFVN391827
Unit: mm
4D095814B
43
FXSQ-PAVE EDTFVN391827
13. Accessories
13.1 Optional Accessories (for Unit)
Model
Item
FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE
Model
Item
FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE
Model
Item
FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE
Brown KTBJ25K160T
Air discharge adapter KDAP25A140A KDAP25A160A (Note 2)
Shield plate for side plate KDBD63A160 —
3D095818E
Notes:
1. If installing high efficiency filter and long-life filter to the unit, filter chamber is required.
2. This option is a set of KDAP25A140A and KDBHP37A160.
44
FXSQ-PAVE EDTFVN391827
Model
Item
FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE
Cooling Only BRC4C66 (Note 4)
Remote Wireless
controller Heat Pump BRC4C65 (Note 4)
Wired BRC1C62 (Note 4)
Navigation remote controller BRC1E62 (Note 4, 5)
(Wired remote controller)
Simplified remote
BRC2C51
controller (Exposed type)
Remote controller for hotel use BRC3A61
(Concealed type)
Adaptor for wiring KRP1C64
Wiring adaptor for KRP2A61
electrical appendices (1)
Wiring adaptor for KRP4AA51
electrical appendices (2)
Remote sensor
KRCS01-4B
(for indoor temperature)
Installation box for adaptor KRP4A98 (Note 2, 3)
printed circuit board
External control adaptor DTA104A61
for outdoor unit
Adaptor for multi tenant DTA114A61
Model
Item
FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE
Cooling Only BRC4C66 (Note 4)
Remote Wireless
Heat Pump BRC4C65 (Note 4)
controller
Wired BRC1C62 (Note 4)
Navigation remote controller
BRC1E62 (Note 4, 5)
(Wired remote controller)
Simplified remote BRC2C51
controller (Exposed type)
Remote controller for hotel BRC3A61
use (Concealed type)
Adaptor for wiring KRP1C64
Wiring adaptor for KRP2A61
electrical appendices (1)
Wiring adaptor for KRP4AA51
electrical appendices (2)
Remote sensor KRCS01-4B
(for indoor temperature)
Installation box for adaptor
KRP4A98 (Note 2, 3)
printed circuit board
External control adaptor DTA104A61
for outdoor unit
Adaptor for multi tenant DTA114A61
C: 3D095822D
Notes:
1. Installation box is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Wireless remote controller does not have AUTO fan mode.
Use wired remote controller to select AUTO fan mode.
5. Auto airflow rate can be set only via wired remote controller BRC1E62. Cannot be set via other remote controllers.
45
FXSQ-PAVE EDTFVN391827
CONTENTS WARNING
• Ask your local dealer or qualified personnel to carry out
1. SAFETY PRECAUTIONS .............................................. 1
installation work.
2. BEFORE INSTALLATION .............................................. 2 Improper installation may result in water leakage, electric
3. SELECTION OF INSTALLATION LOCATION ................ 4 shocks or a fire.
4. PREPARATION BEFORE INSTALLATION .................... 5 • Perform installation work in accordance with this installation
manual.
5. INSTALLATION OF INDOOR UNIT ............................... 6 Improper installation may result in water leakage, electric
6. REFRIGERANT PIPING WORK .................................... 7 shocks or a fire.
7. DRAIN PIPING WORK .................................................. 8 • Consult your local dealer regarding what to do in case of
refrigerant leakage.
8. DUCT WORK ............................................................... 11
When the air conditioner is installed in a small room, it is
9. ELECTRIC WIRING WORK ......................................... 11 necessary to take proper measures so that the amount of
10. FIELD SETTING .......................................................... 15 any leaked refrigerant does not exceed the concentration
11. TEST OPERATION ...................................................... 16 limit in the event of a leakage.
Otherwise, this may lead to an accident due to oxygen
12. WEIGHT AND DIMENSION ........................................16 deficiency.
• Be sure to use only the specified parts and accessories for
1. SAFETY PRECAUTIONS installation work.
Failure to use the specified parts may result in the air
Please read the these " SAFETY CONSIDERATIONS" conditioner falling down, water leakage, electric shocks, a
carefully before installing air conditioning unit and be sure to fire, etc.
install it correctly. After completing the installation, make sure • Install the air conditioner on a foundation that can withstand
that the unit operates properly during the start-up operation.
its mass.
Please instruct the customer on how to operate the unit and
Insufficient strength may result in the air conditioner falling
keep it maintained.
down and causing injury.
Also, inform customers that they should store this installation
In addition, it may lead to vibration of indoor units and cause
manual along with the operation manual for future reference.
unpleasant chattering noise.
This product comes under the term “appliances not accessible
• Carry out the specified installation work in consideration of
to the general public”.
strong winds, typhoons, or earthquakes.
This is a class A product. In a domestic environment this Improper installation may result in an accident such as air
product may cause radio interference in which case the user conditioner falling.
may be required to take adequate measures. • Make certain that all electrical work is carried out by qualified
personnel according to the applicable legislation (Note 1)
• This manual classifies the precautions into WARNINGS and and this installation manual, using a separate circuit.
CAUTIONS. In addition, even if the wiring is short, make sure to use a
Be sure to follow all the precautions below: They are all wiring that has sufficient length and never connect additional
important for ensuring safety. wiring to make the length sufficient.
Insufficient capacity of the power supply circuit or improper
WARNING ..............Indicates a potentially electrical construction may lead to electric shocks or a fire.
hazardous situation which,
(Note 1) applicable legislation means “All international,
if not avoided, could result in
national and local directives, laws, regulations
death or serious injury.
and/or codes which are relevant and applicable for
CAUTION ...............Indicates a potentially a certain product or domain”.
hazardous situation which, • Earth the air conditioner.
if not avoided, may result in Do not connect the earth wiring to gas or water piping,
minor or moderate injury. lightning conductor or telephone earth wiring.
It may also be used to alert Incomplete earthing may cause electric shocks or a fire.
against unsafe practices. • Be sure to install an earth leakage breaker.
• After the installation is completed, test the air conditioner Failure to do so may cause electric shocks and a fire.
and check if the air conditioner operates properly. Give the • Disconnect the power supply before touching the electric
user adequate instructions concerning the use and cleaning components.
of the indoor unit according to the Operation Manual. Ask the If you touch the live part, you may get electric shocks.
user to keep this manual and the Operation Manual together • Make sure that all wiring is secure, using the specified
in a handy place for future reference. wirings and ensuring that external forces do not act on the
terminal connections or wirings.
Incomplete connection or fixing may cause an overheat or a
fire.
3P432203-4B
46
FXSQ-PAVE EDTFVN391827
• When wiring between the indoor and outdoor units, and • Make sure to provide for adequate measures in order to prevent
wiring the power supply, form the wirings orderly so that the that the outdoor unit be used as a shelter by small animals.
control box lid can be securely fastened. Small animals making contact with electrical parts can cause
If the control box lid is not in place, overheating of the malfunctions, smoke or fire. Please instruct the customer to
terminals, electric shocks or a fire may be caused. keep the area around the unit clean.
• If refrigerant gas leaks during installation work, ventilate the • Install in a machine room that is free of moisture. The unit is
area immediately. designed for indoor use.
Toxic gas may be produced if refrigerant gas comes into • Disposal requirements
contact with a fire. Dismantling of the unit, treatment of the refrigerant, of oil and of
• After completing the installation work, check to make sure other parts must be done in accordance with relevant local and
that there is no leakage of refrigerant gas. national legislation.
Toxic gas may be produced if refrigerant gas leaks into the
room and comes into contact with a source of a fire, such as
a fan heater, stove or cooker. SPECIAL NOTICE PRODUCT
• Never directly touch any accidental leaking refrigerant. This • The refrigerant R410A requires that strict precautions be
could result in severe wounds caused by frostbite. observed for keeping the system clean, dry and tightly sealed.
• Do not allow children to climb on the outdoor unit and avoid A. Clean and dry
placing objects on the unit. Strict measures must be taken to keep impurities
Injury may result if the unit becomes loose and falls. (including SUNISO oil and other mineral oils as well as
moisture) out of the system.
CAUTION B. Tightly sealed
R410A contains no chlorine, does not destroy the ozone
• Install drain piping according to this installation manual to layer and so does not reduce the earth's protection against
ensure good drainage, and insulate the piping to prevent harmful ultraviolet radiation. R410A will contribute only slightly
condensation. to the greenhouse effect if released into the atmosphere.
Improper drain piping may cause water leakage, make the
furniture get wet. • Since design pressure is 4.0 MPa or 40 bar (for R407C units:
3.3 MPa or 33 bar), the thickness of pipes must be greater
• Install the air conditioner, power supply wiring, remote
than previously. Since R410A is a mixed refrigerant, the
controller wiring and transmission wiring at least 1 meter
required additional refrigerant must be charged in its liquid state.
away from televisions or radios to prevent image interference
(If the system is charged with refrigerant in its gaseous state,
or noise.
due to composition change, the system will not function
(Depending on the radio waves, a distance of 1 meter may
normally). The indoor unit is designed for R410A use.
not be sufficient to eliminate the noise.)
See the catalogue for indoor unit models that can be
• Install the indoor unit as far as possible from fluorescent
connected. (Normal operation is not possible when connecting
lamps.
units that are originally designed for other refrigerants.)
If a wireless remote controller kit is installed, the transmission
distance may be shorter in a room where an electronic lighting
type (inverter or rapid start type) fluorescent lamp is installed.
• Do not install the air conditioner in places such as the 2. BEFORE INSTALLATION
following: When unpacking the indoor unit or moving the unit after
1. Where there is mist of oil, oil spray or vapour for example unpacked, hold the hangers (4 places) and do not apply
a kitchen. force to other parts (particularly refrigerant piping, drain
Resin parts may deteriorate, and fall out or water may piping).
leak. • Make sure to check in advance that the refrigerant to be
2. Where corrosive gas, such as sulfurous acid gas, is used for installation work is R410A.
produced. (The air conditioner will not properly operate if a wrong
Corrosion of copper pipings or brazed parts may cause refrigerant is used.)
the refrigerant to leak. • For installation of the outdoor unit, refer to the installation
3. Where there is machinery which emits electromagnetic manual attached to the outdoor unit.
waves. • Do not throw away the accessories until the installation work
Electromagnetic waves may disturb the control system, is completed.
and cause malfunction of the equipment. • After the indoor unit is carried into the room, to avoid the
4. Where gases may leak, where carbon indoor unit from getting damaged, take measures to protect
or ignitable dust is suspended in the air or where volatile the indoor unit with packing materials.
such as thinner or gasoline, are handled. (1) Determine the route to carry the unit into the room.
If the gas should leak and remain around the air condi- (2) Do not unpack the unit until it is carried to the installa-
tioner, it may cause ignition. tion location.
• The air conditioner is not intended for use in a potentially Where unpacking is unavoidable, use a sling of soft
explosive atmosphere. material or protective plates together with a rope when
• Pay careful attention when transporting the product. lifting, to avoid damage or scratches to the indoor unit.
Carry the product by the handle sections indicated on the
• Have the customer actually operate the air conditioner while
packaging material.
looking at the operation manual.
Do not hold the PP band since the PP band can become
Instruct the customer how to operate the air conditioner
loose and may result in danger.
(particularly cleaning of the air filters, operation procedures,
• Do not touch the heat exchanger fins.
and temperature adjustment).
Inadvertently touching the fins can cause injury.
3P432203-4B
47
FXSQ-PAVE EDTFVN391827
• Do not use the air conditioner in a salty atmosphere such as CARRY OUT THE WORK GIVING CAUTION
coastal areas, vehicles, vessels or where voltage fluctuation
is frequent such as factories.
TO THE FOLLOWING ITEMS AND AFTER THE
• Take off static electricity from the body when carrying out WORK IS COMPLETED CHECK THESE AGAIN.
wiring and the control box lid is removed.
The electric parts may be damaged. (1) Items to be checked after the installation work is
completed
2-1 ACCESSORIES
Check if the following accessories are attached to the Items to be checked In case of defective Check column
indoor unit. Are the indoor and outdoor Drop · vibration ·
(1) Metal (3) Duct flange connection units rigidly fixed? noise
Name (2) Drain hose Are the installation works of
clamp screw Does not operate ·
the outdoor and indoor units
Quantity 1 pc. 1 pc. See below burnout
completed?
20·25·32 Have you carried out a leakage
6 pcs.
class test with the test pressure Does not cool / Does
40 specified in the outdoor unit not heat
10 pcs.
class installation manual?
50·63·80 Is the insulation of refrigerant
Shape 18 pcs.
class piping and drain piping Water leakage
100·125 completely carried out?
30 pcs.
class Does the drain flow out
Water leakage
140 smoothly?
34 pcs.
class Is the power supply voltage
identical to that stated in the Does not operate ·
Joint insulating (6) Sealing (7) Sealing manufacturer’s label on the burnout
Name (8) Clamp air conditioner?
material material material
Are you sure that there is no
Quantity 1 each 1 sheet 2 sheets 9 pcs. Does not operate ·
wrong wiring or piping or no
burnout
loose wiring?
Thin
Danger in case of
(4) For liquid Is earthing completed?
leakage
piping Are the sizes of electric
Shape Does not operate ·
wiring according to the
Large Medium burnout
Thick specification?
(Dark gray) (Dark gray)
(5) For gas Are any of air outlets or inlets
piping of the indoor and outdoor
units blocked with obstacles? Does not cool /
(It may lead to capacity drop Does not heat
(9) Washer (10) Wire (11) Washer due to fan speed drop or
Name Others
clamp sealing material for hanger malfunction of equipment.)
Quantity 4 pcs. 2 sheets 8 pcs. • Operation Is the external static Does not cool /
manual pressure set correctly? Does not heat
Shape Small • Installation
manual Have you recorded the
(Gray) refrigerant piping length Refrigerant charge
and the refrigerant charge amount is not clear
2-2 OPTIONAL ACCESSORIES amount added?
• A remote controller is required for the indoor unit. Make sure to recheck the items of “SAFETY PRECAUTIONS”.
• There are 2 kinds of remote controller; wired type and
wireless type. (2) Items to be checked at delivery
Install the remote controller to the place where the customer
has given consent. Items to be checked Check column
Refer to the catalog for the applicable model.
Have you carried out field setting? (if necessary)
(Refer to the installation manual attached to the remote
controller for how to install.) Are the control box lid, the air filter and the suction
• The indoor unit can be switched to lower suction. grille attached?
(Refer to 4. PREPARATION BEFORE INSTALLATION.) Does the cool air discharge during the cooling
The side cover plate (KDBD63A160) is required in the case operation and the warm air discharge during the
heating operation? Does the indoor unit makes
of wiring from the bottom surface at bottom suction.
unpleasant sound of air discharge?
For installation work, refer to the instruction sheet provided
Have you explained how to operate the air
with the side cover plate. <Except for 140 class>
conditioner showing the operation manual to the
customer?
Have you explained the description of cooling,
heating, program dry and automatic (cooling/
heating) given in the operation manual to the
customer?
3P432203-4B
48
FXSQ-PAVE EDTFVN391827
If you set the fan speed at thermostat OFF, did you [ Required installation space ]
explain the set fan speed to the customer. Figures indicate the minimum required installation space.
Have you handed the operation manual and the
installation manual to the customer?
Have you checked that there is no generation
of abnormal noise (i.e., noise resulting from
contamination or missing parts)?
Is the printed circuit board switch not on the
emergency (EMG.) side?
The switch is factory set to the normal (NORM.) side.
If an optional accessory is in use, did you check the
operation of the optional accessory and make field
or more
settings as needed?
450mm
Maintenance Maintenance
space for
Is the remote controller icon displayed? Is the space for
electrical
drain pan
remote controller connected to the master unit if the components
system is in simultaneous multi operation? Secure the maintenance
Have you explained failure examples of space for the drain pan and
3. SELECTION OF INSTALLATION LOCATION? electrical components.
Fig. 1
Points of the operation explanation
or more
20mm
In addition to the general usage, since the items in the
operation manual with the WARNING and
CAUTION marks are likely to result in human bodily
H1=245mm*
H2 or more*
injuries and property damages, it is necessary not only
to explain these items to the customer but also to have
the customer read them.
Furthermore, it is necessary to have the customer read
through the troubleshooting items while explaining the
2500mm
or more
above items.
Ceiling
3P432203-4B
49
FXSQ-PAVE EDTFVN391827
20 or more
of the indoor unit and, if necessary, hang the indoor unit
with bolts after it is reinforced by beams etc.
Ceiling
200mm
(Indoor unit size
or less
1. Inspection ports 1 and 2 (450 × 450) (Fig. 3-1) and + 300 or more)
a minimum space of 300 mm at the bottom of the
D=B+300 or more
product (Fig. 3).
2. Inspection port 1 (450 × 450) on the control box side
and inspection port 2 on the bottom of the product. Control box
(Fig. 4, arrow A-1)
B
3. Inspection port 3 on the bottom of the product and on
the bottom side of the control box. (Fig. 4, arrow A-2) Inspection port 2
800 800 Control box
Control box
(Indoor unit
300 or more
Fig. 4
Table 1 (unit [mm])
Model B C D
Ceiling Inspection port 20·25·32 class 550 588 850
40 class 700 738 1000
< In the case of (1)-1 >
50·63·80 class 1000 1038 1300
Fig. 3
100·125 class 1400 1438 1700
800 140 class 1550 1588 1850
Inspection port 1
630 (450×450)
(Hanging bolt pitch)
(2) Mount canvas ducts to the air outlet and inlet so that
200 or less
Hanging bolts (× 4)
the vibration of the indoor unit will not be transmit-
ted to the ducts or ceiling. Furthermore, attach sound
Control box
absorbing material (thermal insulation material) to the
duct inner walls and anti-vibration rubber to the hang-
ing bolts (refer to 8. DUCT WORK).
500
Air outlet standard set value, the remote controller may be used to
make on-site setting change in the external static pres-
Bottom of Air inlet
Inspection port 2* indoor unit
sure.
(450×450) Refer to 10. FIELD SETTING.
(For drain pan
removal and * Inspection port 2 is not required
(4) Open installation holes
component replacement) if the bottom space under the product (in the case of installation onto the existing ceiling).
is accessible for work. • Open the installation holes on the ceiling of the instal-
Fig. 3-1 lation location, and work on the refrigerant piping, drain
piping, remote controller wiring (unless a wireless re-
mote controller is used), and wiring between the indoor
and outdoor units to the piping connection port and
wiring connection port of the indoor unit (refer to each
piping and wiring procedure items).
• Ceiling framework reinforcement may be required in
order to keep the ceiling horizontal and prevent ceiling
vibration after opening the ceiling holes. For details,
consult your building and upholstery work contractors.
(5) Install the hanging bolts.
• Use M8 or M10 bolts for hanging the indoor unit.
Use hole-in-anchors for the existing bolts and embed-
ded inserts or foundation bolts for new bolts, and the
indoor unit to the building so that it may withstand
the mass of the unit.
3P432203-4B
50
FXSQ-PAVE EDTFVN391827
In addition, adjust clearance (50 - 100 mm) from the ceil- 5. INSTALLATION OF INDOOR UNIT
ing in advance.
Depending on the optional parts, it may be easier to attach
them before installing the indoor unit. Refer to also the
<Installation examples> installation manual attached to the optional parts.
For installation, use the attached installation parts and
Ceiling slab
specified parts.
Foundation bolt (1) Install the indoor unit temporarily.
Long nut or • Fix the hanger to the hanging bolt.
Indoor turnbuckle Make sure to securely the hanger with the nut and the
unit washer for hanger (11) from the upper and lower side.
Hanging bolt
(Refer to Fig. 6)
Note) Components shown in the figure above are If the washer clamp (9) is used, the upper side washer
all local procurement. for hanger (11) may be protected from falling off.
(Refer to Fig. 7)
(6) In the case of changing the preset suction to bottom [ Fix the hanger ]
side suction, replace the chamber cover and the suc- Field supply
tion (Refer to Fig. 5)
1. Remove the suction and chamber cover.
2. Replace the suction and the chamber cover. Washer for
hanger (11)
CAUTION (accessory)
• Secure a maintenance space for the drain pan
and electrical components before installing the indoor
unit.
Tighten
• Secure a maintenance space for the
(double nut)
chamber, and peripheral components before installing the
indoor unit. Fig. 6
Replacement
Chamber cover Fig. 7
<140 class> • Keep the air outlet covered with a protective sheet to prevent
Suction flange weld spatter and other foreign materials from entering the
indoor unit and damaging the resin drain pan.
(If holes or cracks are generated in the resin drain pan, water
can leak.)
(2) Adjust so that the unit is properly positioned.
(3) Check the level of the unit. (Refer to Fig. 8)
(4) Remove the washer clamp (9) used for preventing the
washer for hanger (11) from dropping and tighten the up-
Chamber cover Replacement per side nut.
Hanger
Note)
1. Be sure to remove chamber cover one side by
one side.
2. For this model, maintenance of the control box
through side is only available. Bottom of
Maintenance through bottom is not available. Level product
Fig. 5 Vinyl tube
Feed water into the tube and
set the indoor unit to the water
levels on the left and right.
[Maintaining horizontality]
Fig. 8
3P432203-4B
51
FXSQ-PAVE EDTFVN391827
Torque wrench
CAUTION
• Install the indoor unit leveled.
If the indoor unit is inclined and the drain piping side gets Spanner
high, it may cause malfunction of switch and result in
water leakage.
• Attach nuts on the upper and lower side of hanger. Flare nut
If there is no upper nut and the lower nut is over-tightened,
the hanger and the top plate will deform and cause abnormal
sound.
• Do not insert materials other than that into Union joint
the clearance between the hanger and the washer for Fig. 9
hanger (11).
Unless the washers are properly attached, the hanging Coat the flared inner surface
bolts may come off from the hanger. only with ether oil or ester oil
WARNING
The indoor unit must be securely installed on a place
that can withstand the mass. Fig. 10
If the strength is the indoor unit may fall down Table 2
and cause injuries. Piping Tightening Dimension for
size torque processing flare Flare shape
(mm) (N·m) A (mm)
6. REFRIGERANT PIPING WORK φ 6.4 15.7 ± 1.5 8.9 ± 0.2
2°
• For the outdoor unit refrigerant piping, refer to the installation
°±
manual attached to the outdoor unit.
45
φ 9.5 36.3 ± 3.6 13.0 ± 0.2 R0.4-0.8
• Carry out insulation of both gas and liquid refrigerant piping
90°±2°
securely. If not insulated, it may cause water leakage. For φ 12.7 54.9 ± 5.4 16.4 ± 0.2
A
gas piping, use insulation material of which heat resistant
temperature is not less than 120°C. φ 15.9 68.6 ± 6.8 19.5 ± 0.2
For use under high humidity, strengthen the insulation
material for refrigerant piping. If not strengthened, the
surface of insulation material may sweat. CAUTION
• Before installation work, make sure that the refrigerant
Do not have oil adhere to the screw part of resin
is R410A. (Unless the refrigerant is R410A, the normal
parts.
operation cannot be expected.)
If oil adheres, it may weaken the strength of screwed part.
CAUTION Do not tighten nuts too tight.
If a flare nut cracks, the refrigerant may leak.
This air conditioner is a dedicated model for new re-
frigerant R410A. Make sure to meet the requirements • If there is no torque wrench, use Table 3 as a rule of
shown below and carry out installation work. thumb.
• Use dedicated piping cutters and tools for When tightening a nut with a spanner harder and
R410A. harder, there is a point where the tightening torque sud-
• When making a connection, coat the inner denly increases.
surface only with ether oil or ester oil. From that position, tighten the nut additionally at the angle
• Use only the nuts attached to the air conditioner. shown in Table 3.
If other nuts are used, it may cause refrigerant After the work is check securely that there is no
leakage. gas leak.
• To prevent contamination or moisture from getting If the nut is not tightened as instructed, it may cause slow
into the piping, take measures such as pinching or refrigerant leak and result in malfunction (such as does
taping the pipings. not cool or heat).
Do not mix substance other than the refriger- Table 3
ant such as air into the refrigeration circuit. Piping size Tightening Recommended arm length of
If the refrigerant leaks during the work, ventilate the (mm) angle tool used
room. φ 6.4 60° - 90° approx. 150 mm
• The refrigerant is pre-charged in the outdoor unit. φ 9.5 60° - 90° approx. 200 mm
• When connecting the pipings to the air conditioner, make φ 12.7 30° - 60° approx. 250 mm
sure to use a spanner and a torque wrench as shown in φ 15.9 30° - 60° approx. 300 mm
Fig. 9.
• For the dimension of part and the tightening torque, CAUTION
refer to the Table 2. Insulation of piping must be carried out up to the
• When making a connection, coat the inner connection inside the casing.
surface only with ether oil or ester oil. If the piping is exposed to the atmosphere, it may cause
(Refer to Fig. 10) sweating, burn due to touching the piping, electric shocks or
Then, turn the nut 3 to 4 times with your hand and a fire due to the wiring touching the piping.
screw in the nut.
3P432203-4B
52
FXSQ-PAVE EDTFVN391827
• After leak test, referring to Fig. 11, insulate both the gas • Before brazing refrigerant piping, have nitrogen
and liquid piping connection with the attached joint in- through the refrigerant piping and substitute air with nitro-
sulating material (4) and (5) to prevent the pipings from gen (NOTE 1) (Refer to Fig. 12). Then, carry out brazing
getting exposed. (NOTE 2).
Then, tighten both the ends of insulating material with the After all the brazing works are carry out
clamp (8). connection with the indoor unit. (Refer to Fig. 11)
• Wrap the sealing material (Medium) (7) around the joint
insulating material (4) and (5) nut section), both the Pressure reducing valve
gas and liquid piping. Taping
• Make sure to bring the seam of joint insulating material (4) Brazing place
and (5) to the top.
Gas side piping insulating method Nitrogen
Joint insulating
material (5) Refrigerant piping Stop valve
(accessory) Nitrogen
Flare nut Piping insulating Fig. 12
connection material (main unit) Wind around the
piping until top of the
Bring the flare nut connection,
NOTE
seam Do not leave beginning at the base. 1. The proper pressure for having nitrogen through the
to the top. clearance. piping is approximately 0.02 MPa, a pressure that makes
one feel like slight breeze and can be obtained through a
pressure reducing valve.
Indoor unit
2. Do not use when brazing refrigerant piping.
Clamp (8) Use phosphor copper brazing metal (BCuP-2: JIS Z
Piping (accessory) Sealing material 3264/B-Cu93P-710/795: ISO 3677) that does not require
insulating
Tighten the portion (7) Medium
material
where overlapped by (accessory)
(field supply) (If chlorinated is used, the piping will be corroded and,
the piping insulating
material. in addition if is contained, the refrigerant oil will
Do not expose the
piping in order to be deteriorated and the refrigerant circuit will be affected
prevent the vapor badly.)
condensation. 3. When carrying out leakage test of refrigerant piping and
the indoor unit after the installation of indoor unit is -
ished, the connecting outdoor unit installation
manual for test pressure.
Refer to also the outdoor unit installation manual or techni-
cal document for refrigerant piping.
4. In case of refrigerant shortage due to forgetting additional
refrigerant charge etc., it will result in malfunction such as
Gas piping does not cool or does not heat.
Refer to the outdoor unit installation manual or technical
Liquid piping document for refrigerant piping.
Fig. 11
3P432203-4B
53
FXSQ-PAVE EDTFVN391827
approx. 90°
inclination of
1/100 or more
Good Vinyl tape
Wrong
<In case of bending the tip>
Fig. 13
Tightened part
CAUTION
approx. 90°
If drain stagnates in the drain piping, the piping may be
clogged.
(850 or less)
• Do not tighten the metal clamp (1) with the torque more
than the value.
Adjustable
The drain hose (2), the socket or the metal clamp (1) may
(675 or less)
be damaged.
Upward drain piping
• Wrap the vinyl tape around the end of the metal clamp Metal clamp (1)
(Field supply)
(1) so that the sealing material (Large) (6) to be used at (accessory)
the next process may not be damaged with the clamp Drain hose (2)
end or bend the tip of the metal clamp (1) inward as (accessory)
shown. (Refer to Fig. 15)
Level or upward
inclination
Keep the drain hose level or make a slight up-grade so
that air may not stagnate in the drain hose.
If air stagnates, the drain may flow oppositely when
the drain pump stops and generate abnormal sound.
Fig. 16
3P432203-4B
54
FXSQ-PAVE EDTFVN391827
10
3P432203-4B
55
FXSQ-PAVE EDTFVN391827
11
3P432203-4B
56
FXSQ-PAVE EDTFVN391827
FXSQ125PAVE WARNING
FXSQ140PAVE • When wiring, form the wirings orderly so that the control box
lid can be securely fastened. If the control box lid is not in
The lengths of remote controller wiring are as follows:
place, the wirings may come out or be sandwiched by the
Remote controller wiring (indoor unit - remote controller) ....Max. 500 m
box and the lid and cause electric shocks or a fire.
NOTE
1. Shows only in case of protected piping. Use H07RN-F in (1) Remove the control box lid.
case of no protection. (Do not lighter than 60245 IEC 57.)
2. Vinyl cord with sheath or cable (Insulated thickness : 1 mm
or more)
3. This size is based on IEC 60335-1 (Table 11), and this size
must comply with local codes.
Screws
(2 points)
9-4 WIRING CONNECTION METHOD
CAUTION FOR WIRING
Fig. 23
• For connection to the terminal block, use ring type crimp
style terminals with insulation sleeve or insulate the wirings
properly.
Wiring
Insulation sleeve
12
3P432203-4B
57
FXSQ-PAVE EDTFVN391827
(2) Connect the wiring into the control box through the (5) Securely each wire with the provided clamp mate-
wiring intake beside the control box. rial (8).
Wiring intake Wiring intake Clamp (8)
(low voltage) (high voltage) (accessory)
Remote controller Power supply
wiring wiring
Transmission Earth wiring
wiring
Power supply wiring,
Remote controller wiring and earth wiring
Transmission wiring
Fig. 27
Terminal block (X1M) < No. 1 system: When 1 remote controller is used for 1
for power supply wiring, indoor unit. >
and earth wiring
Power supply
1~
220-240 V
Connection method 50 Hz
for power supply wiring,
X1M or
and earth wiring
1~
220 V Outdoor
Securely fix the wiring to 60 Hz unit
the provided wiring fixture L N
IN/D OUT/D
with the clamp (8). F1 F2 F1 F2
(4) Mount the control box lid and wrap the wire sealing
material (small) (10) so that the wiring through hole
will be covered by the sealing material.
• Seal the clearance around the wirings with putty or insu-
lating material supply).
(If insects and small animals get into the indoor unit,
short-circuiting may occur inside the control box.)
Wiring through
hole Wire sealing material (small) (10)
(accessory)
Power supply wiring,
earth wiring, remote
controller wiring, or
transmission wiring
Wiring fixture
Fig. 26
13
3P432203-4B
58
FXSQ-PAVE EDTFVN391827
< No. 3 system: When BS unit is used > Remote Crossover Remote
controller 1 wiring (Remote controller 2
Outdoor unit BS unit (Main) controller) (Sub)
Power supply L N
IN/D OUT/D OUT/D IN/D
Fig. 28
1~ F1 F2 F1 F2 F1 F2 F1 F2
14
3P432203-4B
59
FXSQ-PAVE EDTFVN391827
10. FIELD SETTING Return to the “Basic screen” (“Normal mode” if a wireless
remote controller is used), and press the ON/OFF button.
CAUTION The operation lamp is lit, and the indoor unit will go into fan
operation for air volume automatic adjustments (at which
Before carrying out field setting, check the items mentioned in time, do not adjust the opening of the air outlet or inlet).
(1) Items to be checked after the installation work is The air volume adjustments will automatically terminate
completed on page 3. approximately 1 to 15 minutes after the indoor unit comes
• Check if all the installation and piping works for the air into operation, and the operation lamp will be OFF and the
conditioner are completed. indoor unit will come to a stop.
• Check that the outside panel and piping cover of the indoor Table 7
and outdoor units are closed. FIRST SECOND CODE No.
Setting
Mode No. CODE
content 01 02 03
< FIELD SETTING > No.
After turning on the power supply, carry out field setting Air volume
Air volume Air volume
adjust-
from the remote controller according to the installation 11 (21) 7 adjust- OFF adjust-
ment
state. ment ment start
completion
• Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.”
and “SECOND CODE No.”. (4) After the air conditioner comes to a stop, be sure to check
The settings shown by in the following tables indicate with Mode No. [21] per indoor unit that the above SECOND
those when shipped from the factory. CODE No. is “02”. If the operation of the air conditioner
• The method of setting procedure and operation is shown in does not stop automatically or the SECOND CODE No. is
the installation manual attached to the remote controller. not set to “02”, repeat the setting procedure from (3).
(Note) Though setting of “Mode No.” is carried out as a group, CAUTION
if you intend to carry out individual setting by each
indoor unit or confirmation after setting, carry out • If airflow pathway changes, such as duct and air outlet
setting with the Mode No. shown in the parenthesis ( ). changes, are made after air volume adjustments, be sure to
• Ask your customer to keep the manual attached to the remote make “Air volume automatic adjustment” again.
controller together with the operation manual. • If airflow pathway changes, such as duct and air outlet
• Do not carry out settings other than those shown in the table. changes, are made after 11. TEST OPERATION or air
• Settings are performed by selecting “Mode No.”, “FIRST conditioner relocation, contact your dealer.
CODE No.”, and “SECOND CODE No.”. (b) Select external static pressure with the remote controller.
Check with Mode No. [21] per indoor unit that the SECOND CODE
10-1 Settings for external static pressure No. for the above “Air volume adjustment” is set to “01” (OFF).
• Make settings in either method (a) or method (b). (The SECOND CODE No. is factory set to “01” (OFF).)
(a) Make settings with Air volume automatic adjustment Change the SECOND CODE No. by referring to the table below
function. according to the external static pressure of the duct to be
“Air volume automatic adjustment” function: The air volume connected.
is adjusted to the rated air volume automatically. Table 8
In case of 20-125 class
CAUTION FIRST SECOND
External static
Mode No.
• Be sure to check that the external static pressure is within pressure CODE No. CODE No.
the specification range before making settings. The external 30Pa (*1) 03
static pressure will not be automatically adjusted and air 40Pa (*1) 04
volume insufficiency or water leakage may result if the 50Pa 05
external static pressure is outside the range. (Refer to the 60Pa 06
technical document for the setting range of external static 70Pa 07
pressure.) 80Pa 08
90Pa 13(23) 6 09
(1) Check that the electrical wiring and duct work have been
100Pa 10
completed.
110Pa 11
(If the closing damper is set midway, be sure to check that
120Pa 12
the damper is opened. Furthermore, check that the air
passage on the suction side is provided with an air filter 130Pa 13
(field supply)). 140Pa 14
150Pa 15
(2) If air conditioner has more than one air outlet and air inlet,
(*1) The FXSQ50-125 class cannot be set to 30Pa or 40Pa.
be sure to make adjustments so that the air volume ratio of
each air outlet and the corresponding air inlet will conform In case of 140 class
to the designed air volume ratio. External static FIRST SECOND
Mode No.
pressure CODE No. CODE No.
In that case, set the operating mode to “Fan”. (In the case
of changing the air volume, press the fan speed button on 50Pa 05
the remote controller and change the current selection to 60Pa 06
“High”, “Medium”, or “Low”.) 70Pa 07
80Pa 08
(3) Make settings to adjust the air volume automatically.
After setting the operating mode to “Fan”, set the air con- 90Pa 09
13(23) 6
ditioner to setting mode with the operation of the air 100Pa 10
conditioner stopped. Select Mode No. [21] (11 in the case 110Pa 11
of batch settings), select FIRST CODE No. “7”, and set the 120Pa 12
SECOND CODE No. to “03”. 130Pa 13
140Pa 14
15
3P432203-4B
60
FXSQ-PAVE EDTFVN391827
16
3P432203-4B
61
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
●Specifications, designs and other content appearing in this brochure are current as of March 2018 but subject to change without notice.