You are on page 1of 40

EDMT341410B

FXSQ-P
Middle Static Pressure
Ceiling Mounted Duct Type

1. Specifications ......................................................................................182
2. Dimensions .........................................................................................185
3. Piping Diagrams..................................................................................191
4. Wiring Diagrams..................................................................................192
5. Electric Characteristics........................................................................193
6. Safety Devices Setting ........................................................................194
7. Capacity Tables ..................................................................................195
7.1 Cooling Capacity for Te: 6°C................................................................195
7.2 Cooling Capacity for Te: 9°C................................................................195
8. Fan Performances...............................................................................196
10
9. Airflow Auto Adjustment Characteristics .............................................205
10.Sound Levels ......................................................................................214
11.Centre of Gravity .................................................................................219
12.Accessories.........................................................................................220
12.1 Optional Accessories (for Unit).............................................................220
12.2 Optional Accessories (for Controls)......................................................220

FXSQ-P 181
Specifications EDMT341410B

1. Specifications
Middle static pressure ceiling mounted duct type
Model FXSQ20PVE FXSQ25PVE FXSQ32PVE
Power supply 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz
kcal/h 1,900 2,400 3,100
1 2 Cooling capacity Btu/h 7,500 9,600 12,300
kW 2.2 2.8 3.6
6
Cooling kW 0.058 0.058 0.066
Power input
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 245×550×800 245×550×800 245×550×800
Model — — —
Type Sirocco fan Sirocco fan Sirocco fan
Motor output × W 78×1 78×1 78×1
Number of units
Fan m³/min 9/7.5/6.5 9/7.5/6.5 9.5/8/7
Airflow rate (H/M/L) l/s 150/125/108 150/125/108 158/133/116
cfm 318/265/230 318/265/230 335/282/247
External static pressure Pa Rated 50 (150-30 3) Rated 50 (150-30 3) Rated 50 (150-30 3)
Drive Direct drive Direct drive Direct drive
Microprocessor thermostat for Microprocessor thermostat for Microprocessor thermostat for
Temperature control
cooling and heating cooling and heating cooling and heating
Air filter — 4 — 4 — 4
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
Piping
connections VP25 VP25 VP25
Drain pipe mm External dia. 32 External dia. 32
( Internal dia. 25 ) ( Internal dia. 25 ) ( External dia. 32
Internal dia. 25 )
Mass kg 25 25 25
5 Sound pressure level (H/M/L) dB(A) 33/30/28 33/30/28 34/32/30
Fuse, Fuse, Fuse,
Safety devices
Fan driver overload protector Fan driver overload protector Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Operation manual, Installation manual, Operation manual, Installation manual,
Drain hose, Sealing material, Clamps, Drain hose, Sealing material, Clamps, Drain hose, Sealing material, Clamps,
Standard accessories Washers, Screws, Thermal insulation, Washers, Screws, Thermal insulation, Washers, Screws, Thermal insulation,
Hose band, Air discharge flange, Air Hose band, Air discharge flange, Air Hose band, Air discharge flange, Air
suction flange suction flange suction flange
Specification C: 3D095816A C: 3D095816A C: 3D095816A
Drawing No.
Sound level C: 4D095804A C: 4D095804A C: 4D095805A

Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
kcal/h=kW×860
3. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class) by remote controller. Btu/h=kW×3412
4. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity l/s=m³/min×1000/60
method) 50% or more. cfm=m³/min×35.3
5. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
6. Power input values are based on conditions of rated external static pressure.
7. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external static pressure.

182 FXSQ-P
EDMT341410B Specifications

Middle static pressure ceiling mounted duct type


Model FXSQ40PVE FXSQ50PVE FXSQ63PVE FXSQ80PVE
1 phase, 220-240/220V, 1 phase, 220-240/220V, 1 phase, 220-240/220V, 1 phase, 220-240/220V,
Power supply
50/60Hz 50/60Hz 50/60Hz 50/60Hz
kcal/h 3,900 4,800 6,100 7,700
1 2 Cooling capacity Btu/h 15,400 19,100 24,200 30,700
kW 4.5 5.6 7.1 9.0
6
Cooling kW 0.101 0.075 0.106 0.126
Power input
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 245×700×800 245×1,000×800 245×1,000×800 245×1,000×800
Model — — — —
Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan
Motor output ×
W 130×1 230×1 230×1 230×1
Number of units
Fan m³/min 15/12.5/10.5 17/14.5/11.5 21/17.5/14.5 23/19.5/16
Airflow rate (H/M/L) l/s 250/208/175 283/242/192 350/292/242 383/325/267
cfm 530/441/371 600/512/406 741/618/512 812/688/565
External static pressure Pa Rated 50 (150-30 3) Rated 50 (150-50 3) Rated 50 (150-50 3) Rated 50 (150-50 3)
Drive Direct drive Direct drive Direct drive Direct drive
Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat
Temperature control for cooling and heating for cooling and heating for cooling and heating for cooling and heating
Air filter — 4 — 4 — 4 — 4
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection)
Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection)
Piping
connections VP25 VP25 VP25 VP25
Drain pipe mm
( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 )
10
Mass kg 27 35 35 37
5 Sound pressure level (H/M/L) dB(A) 36/33/30 34/32/29 36/32/29 37.5/34/30
Fuse, Fuse, Fuse, Fuse,
Safety devices Fan driver overload Fan driver overload Fan driver overload Fan driver overload
protector protector protector protector
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual, Operation manual, Operation manual, Operation manual,
Installation manual, Drain Installation manual, Drain Installation manual, Drain Installation manual, Drain
hose, Sealing material, hose, Sealing material, hose, Sealing material, hose, Sealing material,
Standard accessories Clamps, Washers, Screws, Clamps, Washers, Screws, Clamps, Washers, Screws, Clamps, Washers, Screws,
Thermal insulation, Hose Thermal insulation, Hose Thermal insulation, Hose Thermal insulation, Hose
band, Air discharge flange, band, Air discharge flange, band, Air discharge flange, band, Air discharge flange,
Air suction flange Air suction flange Air suction flange Air suction flange
Specification C: 3D095816A C: 3D095816A C: 3D095816A C: 3D095816A
Drawing No.
Sound level C: 4D095806A C: 4D095807A C: 4D095808A C: 4D095809A

Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
kcal/h=kW×860
3. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class) by remote controller. Btu/h=kW×3412
4. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity l/s=m³/min×1000/60
method) 50% or more. cfm=m³/min×35.3
5. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
6. Power input values are based on conditions of rated external static pressure.
7. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external static pressure.

FXSQ-P 183
Specifications EDMT341410B

Middle static pressure ceiling mounted duct type


Model FXSQ100PVE FXSQ125PVE FXSQ140PVE
Power supply 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz
kcal/h 9,600 12,000 13,800
1 2 Cooling capacity Btu/h 38,200 47,800 54,600
kW 11.2 14.0 16.0
6
Cooling kW 0.151 0.206 0.222
Power input
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 245×1,400×800 245×1,400×800 245×1,550×800
Model — — —
Type Sirocco fan Sirocco fan Sirocco fan
Motor output ×
Number of units W 300×1 300×1 350×1

Fan m³/min 32/27/22.5 37/31.5/26 39/33.5/28


Airflow rate (H/M/L) l/s 533/450/375 617/525/433 650/558/467
cfm 1130/953/794 1306/1112/918 1377/1183/988
External static pressure Pa Rated 50 (150-50 3) Rated 50 (150-50 3) Rated 50 (140-50 3)
Drive Direct drive Direct drive Direct drive
Microprocessor thermostat for cooling Microprocessor thermostat for cooling Microprocessor thermostat for cooling
Temperature control
and heating and heating and heating
Air filter — 4 — 4 — 4
Liquid pipes mm φ9.5 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection)
Gas pipes mm φ15.9 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection)
Piping
connections VP25 VP25 VP25
Drain pipe mm External dia. 32 External dia. 32
( Internal dia. 25 ) ( Internal dia. 25 ) ( External dia. 32
Internal dia. 25 )
Mass kg 46 47 52
5 Sound pressure level (H/M/L) dB(A) 39/35/32 42/38.5/35 43/40/36
Fuse, Fuse, Fuse,
Safety devices
Fan driver overload protector Fan driver overload protector Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Operation manual, Installation manual, Operation manual, Installation manual,
Drain hose, Sealing material, Clamps, Drain hose, Sealing material, Clamps, Drain hose, Sealing material, Clamps,
Standard accessories Washers, Screws, Thermal insulation, Washers, Screws, Thermal insulation, Washers, Screws, Thermal insulation,
Hose band, Air discharge flange, Air Hose band, Air discharge flange, Air Hose band, Air discharge flange, Air
suction flange suction flange suction flange
Specification C: 3D095816A C: 3D095816A C: 3D095816A
Drawing No.
Sound level C: 4D095810A C: 4D095811A C: 4D095812A

Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
kcal/h=kW×860
3. External static pressure is changeable in 13 stages (20-40 class), 11 stages (50-125 class), 10 stages (140 class) by remote controller. Btu/h=kW×3412
4. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity l/s=m³/min×1000/60
method) 50% or more. cfm=m³/min×35.3
5. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
6. Power input values are based on conditions of rated external static pressure.
7. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external static pressure.

184 FXSQ-P
EDMT341410B Dimensions

2. Dimensions
FXSQ20PVE / FXSQ25PVE / FXSQ32PVE
Unit: mm

3D095725A
10

FXSQ-P 185
Dimensions EDMT341410B

FXSQ40PVE
Unit: mm

3D095726A

186 FXSQ-P
EDMT341410B Dimensions

FXSQ50PVE
Unit: mm

3D096164A
10

FXSQ-P 187
Dimensions EDMT341410B

FXSQ63PVE / FXSQ80PVE
Unit: mm

3D095426B

188 FXSQ-P
EDMT341410B Dimensions

FXSQ100PVE / FXSQ125PVE
Unit: mm

3D095427B
10

FXSQ-P 189
Dimensions EDMT341410B

FXSQ140PVE
Unit: mm

3D095727B

190 FXSQ-P
EDMT341410B Piping Diagrams

3. Piping Diagrams
FXSQ20PVE / FXSQ25PVE / FXSQ32PVE / FXSQ40PVE / FXSQ50PVE / FXSQ63PVE / FXSQ80PVE /
FXSQ100PVE / FXSQ125PVE / FXSQ140PVE

10

4D034245M

„ Refrigerant pipe connection port diameters


(mm)
Model Gas Liquid
FXSQ20PVE / FXSQ25PVE / FXSQ32PVE / FXSQ40PVE / FXSQ50PVE φ12.7 φ6.4
FXSQ63PVE / FXSQ80PVE / FXSQ100PVE / FXSQ125PVE / FXSQ140PVE φ15.9 φ9.5

FXSQ-P 191
Wiring Diagrams EDMT341410B

4. Wiring Diagrams
FXSQ20PVE / FXSQ25PVE / FXSQ32PVE / FXSQ40PVE / FXSQ50PVE / FXSQ63PVE / FXSQ80PVE /
FXSQ100PVE / FXSQ125PVE / FXSQ140PVE

C: 3D092752B

192 FXSQ-P
EDMT341410B Electric Characteristics

5. Electric Characteristics
FXSQ20PVE / FXSQ25PVE / FXSQ32PVE / FXSQ40PVE / FXSQ50PVE / FXSQ63PVE / FXSQ80PVE /
FXSQ100PVE / FXSQ125PVE / FXSQ140PVE

10

4D096947A

FXSQ-P 193
Safety Devices Setting EDMT341410B

6. Safety Devices Setting

Model FXSQ20PVE FXSQ25PVE FXSQ32PVE FXSQ40PVE FXSQ50PVE FXSQ63PVE FXSQ80PVE FXSQ100PVE FXSQ125PVE FXSQ140PVE
Printed circuit board fuse 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A
Printed circuit board fuse 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A
(Fan driver)
Drain pump thermal fuse °C — — — — — — — — — —
C: 3D034597M

194 FXSQ-P
EDMT341410B Capacity Tables

7. Capacity Tables
7.1 Cooling Capacity for Te: 6°C
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXSQ20PVE 20 1.5 1.5 1.8 1.7 2.1 1.8 2.2 1.8 2.2 1.8 2.3 1.7 2.3 1.7
FXSQ25PVE 25 1.9 1.8 2.3 1.9 2.6 2.1 2.8 2.2 2.8 2.1 2.9 2.0 3.0 2.0
FXSQ32PVE 32 2.4 2.0 2.9 2.3 3.4 2.6 3.6 2.7 3.6 2.6 3.7 2.5 3.8 2.5
FXSQ40PVE 40 3.0 2.8 3.6 3.2 4.2 3.6 4.5 3.7 4.6 3.6 4.7 3.4 4.8 3.4
FXSQ50PVE 50 3.8 3.3 4.5 3.8 5.2 4.2 5.6 4.3 5.7 4.2 5.8 4.1 5.9 3.9
FXSQ63PVE 63 4.8 4.2 5.7 4.8 6.6 5.3 7.1 5.4 7.2 5.4 7.4 5.2 7.5 5.1
FXSQ80PVE 80 6.1 5.0 7.2 5.7 8.4 6.4 9.0 6.5 9.1 6.4 9.3 6.2 9.5 6.0
FXSQ100PVE 100 7.6 6.5 9.0 7.5 10.5 8.4 11.2 8.5 11.3 8.4 11.6 8.1 11.9 7.9
FXSQ125PVE 125 9.4 7.7 11.3 8.9 13.1 9.9 14.0 10.1 14.2 10.0 14.5 9.7 14.9 9.4
FXSQ140PVE 140 10.8 8.8 12.9 10.1 15.0 11.3 16.0 11.6 16.2 11.4 16.6 11.1 17.0 10.7

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
10
7.2 Cooling Capacity for Te: 9°C
When a mixed combination of VRV and
residential indoor units is connected

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXSQ20PVE 20 1.0 1.0 1.3 1.3 1.7 1.6 1.8 1.6 1.8 1.6 1.9 1.5 2.0 1.5
FXSQ25PVE 25 1.3 1.3 1.7 1.6 2.0 1.8 2.3 1.9 2.3 1.8 2.5 1.8 2.6 1.8
FXSQ32PVE 32 1.7 1.6 2.2 1.9 2.7 2.3 2.9 2.4 3.0 2.3 3.2 2.3 3.3 2.3
FXSQ40PVE 40 2.1 2.1 2.6 2.6 3.3 3.1 3.6 3.2 3.8 3.2 4.0 3.0 4.2 3.1
FXSQ50PVE 50 2.5 2.5 3.2 3.1 4.0 3.6 4.5 3.7 4.6 3.6 4.9 3.6 5.1 3.5
FXSQ63PVE 63 3.3 3.3 4.1 4.0 5.1 4.5 5.7 4.7 5.9 4.7 6.2 4.6 6.5 4.6
FXSQ80PVE 80 4.1 3.9 5.3 4.8 6.6 5.5 7.3 5.7 7.5 5.6 7.9 5.6 8.3 5.5
FXSQ100PVE 100 5.3 5.2 6.7 6.3 8.3 7.3 9.1 7.5 9.3 7.4 9.9 7.3 10.4 7.2
FXSQ125PVE 125 6.5 6.1 8.4 7.5 10.4 8.6 11.4 8.9 11.7 8.8 12.4 8.8 13.1 8.6
FXSQ140PVE 140 7.5 7.1 9.6 8.6 12.0 9.9 13.0 10.2 13.5 10.1 14.3 10.1 15.0 9.8

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.

FXSQ-P 195
Fan Performances EDMT341410B

8. Fan Performances
FXSQ20PVE / FXSQ25PVE

3D095855A

196 FXSQ-P
EDMT341410B Fan Performances

FXSQ32PVE

3D095856A
10

FXSQ-P 197
Fan Performances EDMT341410B

FXSQ40PVE

3D095857A

198 FXSQ-P
EDMT341410B Fan Performances

FXSQ50PVE

3D095858A
10

FXSQ-P 199
Fan Performances EDMT341410B

FXSQ63PVE

3D095859A

200 FXSQ-P
EDMT341410B Fan Performances

FXSQ80PVE

3D095860A
10

FXSQ-P 201
Fan Performances EDMT341410B

FXSQ100PVE

3D095861A

202 FXSQ-P
EDMT341410B Fan Performances

FXSQ125PVE

3D095862A
10

FXSQ-P 203
Fan Performances EDMT341410B

FXSQ140PVE

3D095863A

204 FXSQ-P
EDMT341410B Airflow Auto Adjustment Characteristics

9. Airflow Auto Adjustment Characteristics


FXSQ20PVE / FXSQ25PVE

3D095846A
10

FXSQ-P 205
Airflow Auto Adjustment Characteristics EDMT341410B

FXSQ32PVE

3D095847A

206 FXSQ-P
EDMT341410B Airflow Auto Adjustment Characteristics

FXSQ40PVE

3D095848A
10

FXSQ-P 207
Airflow Auto Adjustment Characteristics EDMT341410B

FXSQ50PVE

3D095849A

208 FXSQ-P
EDMT341410B Airflow Auto Adjustment Characteristics

FXSQ63PVE

3D095850A
10

FXSQ-P 209
Airflow Auto Adjustment Characteristics EDMT341410B

FXSQ80PVE

3D095851A

210 FXSQ-P
EDMT341410B Airflow Auto Adjustment Characteristics

FXSQ100PVE

3D095852A
10

FXSQ-P 211
Airflow Auto Adjustment Characteristics EDMT341410B

FXSQ125PVE

3D095853A

212 FXSQ-P
EDMT341410B Airflow Auto Adjustment Characteristics

FXSQ140PVE

3D095854A
10

FXSQ-P 213
Sound Levels EDMT341410B

10. Sound Levels


FXSQ20PVE / FXSQ25PVE

4D095804A
FXSQ32PVE

4D095805A

214 FXSQ-P
EDMT341410B Sound Levels

FXSQ40PVE

4D095806A
10

FXSQ50PVE

4D095807A

FXSQ-P 215
Sound Levels EDMT341410B

FXSQ63PVE

4D095808A
FXSQ80PVE

4D095809A

216 FXSQ-P
EDMT341410B Sound Levels

FXSQ100PVE

4D095810A
10

FXSQ125PVE

4D095811A

FXSQ-P 217
Sound Levels EDMT341410B

FXSQ140PVE

4D095812A

218 FXSQ-P
EDMT341410B Centre of Gravity

11. Centre of Gravity


FXSQ20PVE / FXSQ25PVE / FXSQ32PVE / FXSQ40PVE / FXSQ50PVE / FXSQ63PVE / FXSQ80PVE /
FXSQ100PVE / FXSQ125PVE / FXSQ140PVE
Unit: mm

10

4D095814B

FXSQ-P 219
Accessories EDMT341410B

12. Accessories
12.1 Optional Accessories (for Unit)
Model
Item
FXSQ20PVE FXSQ25PVE FXSQ32PVE FXSQ40PVE FXSQ50PVE FXSQ63PVE FXSQ80PVE FXSQ100PVE FXSQ125PVE FXSQ140PVE

High efficiency filter 65% KAFP632B36 KAFP632B56 KAFP632B80 KAFP632B160 KAF632B160B


(Note 1) 90% KAFP633B36 KAFP633B56 KAFP633B80 KAFP633B160 KAF633B160B
Filter chamber (for rear suction) KDDFP63B36 KDDFP63B56 KDDFP63B80 KDDFP63B160 KDDF63B160B
(Note 1)
Long life filter (Note 1) KAFP631B36 KAFP631B56 KAFP631B80 KAFP631B160 KAF631B160B
White KTBJ25K36W KTBJ25K56W KTBJ25K80W KTBJ25K160W
Service panel Fresh white KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F
Brown KTBJ25K36T KTBJ25K56T KTBJ25K80T KTBJ25K160T

Air discharge adapter KDAP25A36A KDAP25A160A


KDAP25A56A KDAP25A71A KDAP25A140A
(Note 2)
Shield plate for side plate KDBD63A160 —
C: 3D095818C

Notes:
1. If installing high efficiency filter and long-life filter to the unit, filter chamber is required.
2. This option is a set of KDAP25A140A and KDBHP37A160.

12.2 Optional Accessories (for Controls)


Refer to page 822.

220 FXSQ-P