Professional Documents
Culture Documents
FXMQ-M
Ceiling Mounted Duct Type
AMERICAS
EDUS39-600-F4
FXMQ-M
Ceiling Mounted Duct Type
1. Features ......................................................................................................2
2. Specifications ..............................................................................................3
3. Dimensions .................................................................................................4
4. Piping Diagrams..........................................................................................6
5. Wiring Diagrams..........................................................................................7
6. Electric Characteristics................................................................................8
7. Capacity Tables ..........................................................................................9
7.1 Cooling Capacity .......................................................................................... 9
7.2 Heating Capacity ........................................................................................ 10
8. Fan Performances.....................................................................................11
9. Sound Levels ............................................................................................12
10.Installation .................................................................................................13
11.Accessories...............................................................................................25
FXMQ-M 1
Features EDUS39-600-F4
1. Features
The Ceiling-Mounted Duct Type is a new addition to the VRV indoor units lineup that
provides greater flexibility to satisfy individual air-conditioning needs even in a broad
area.
Increased allowable external static pressure accommodates greater flexibility in duct design and application.
Ceiling-Mounted Duct Type
FXMQ30M
FXMQ36M
FXMQ48M
2 FXMQ-M
EDUS39-600-F4 Specifications
2. Specifications
Ceiling Mounted Duct Type
Model FXMQ30MVJU FXMQ36MVJU FXMQ48MVJU
Cooling Capacity1 Btu/h 30,000 36,000 48,000
Heating Capacity2 Btu/h 34,000 40,000 54,000
Casing / Color Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
15-3/8 × 28-3/8 × 27-1/8” 15-3/8 × 43-3/4 × 27-1/8” 15-3/8 × 43-3/4 × 27-1/8”
Dimensions: (H × W × D) in (mm)
( 390.5 x 720.7 x 689 mm) ( 390.5 x 1111.2 x 689 mm) ( 390.5 x 1111.2 x 689 mm)
Coil (Cross Rows × Stages × FPI 3 × 16 × 13 3 ×16 ×13 3 ×16 ×13
Fin Coil) Face Area ft² 1.95 3.43 3.43
Model D11/2D3AA1VE 2D11/2D3AG1VE 2D11/2D3AF1VE
Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output kW 0.15 0.27 0.43
Fan
Air Flow Rate (H/L) cfm 690/565 1,020/810 1,270/1,020
External Static Pressure4 in. Wg 0.66-0.43 0.71-0.43 1.0-0.72
Drive Direct Drive Direct Drive Direct Drive
Temperature Control Microprocessor Thermostat for Cooling Microprocessor Thermostat for Cooling Microprocessor Thermostat for Cooling
and Heating and Heating and Heating
Sound Absorbing Thermal Insulation Material Glass Fiber Glass Fiber Glass Fiber
Air Filter5 See Note 5 See Note 5 See Note 5
Liquid Pipes in / mm φ3/8” / 9.5 mm (Flare Connection) φ3/8” / 9.5 mm (Flare Connection) φ3/8” / 9.5 mm (Flare Connection)
Piping Gas Pipes in / mm φ5/8” / 15.8 mm (Flare Connection) φ5/8” / 15.8 mm (Flare Connection) φ5/8” / 15.8 mm (Flare Connection)
Connections VP25 VP25 VP25
Drain Pipe in / mm External Dia. 1-1/4 External Dia. 1-1/4
( Internal Dia. 1 ) ( Internal Dia. 1 ) ( External Dia. 1-1/4
Internal Dia. 1 )
Machine Weight (Mass) Lbs 99 139 144
Sound Level (H/L)6 dBA 45/41 45/41 48/45
FXMQ-M 3
Dimensions EDUS39-600-F4
3. Dimensions
FXMQ30MVJU
3D042508
4 FXMQ-M
EDUS39-600-F4 Dimensions
FXMQ36MVJU
FXMQ48MVJU
3D042512
FXMQ-M 5
Piping Diagrams EDUS39-600-F4
4. Piping Diagrams
R3T
R1T
Fan
R2T
J:DU220-602J
6 FXMQ-M
EDUS39-600-F4 Wiring Diagrams
5. Wiring Diagrams
FXMQ30M/36M/48MVJU
3D043176A
FXMQ-M 7
Electric Characteristics EDUS39-600-F4
6. Electric Characteristics
8 FXMQ-M
EDUS39-600-F4 Capacity Tables
7. Capacity Tables
7.1 Cooling Capacity
FXMQ-M
Cooling capacity
Indoor Air Temp. °FWB
Outdoor 61 64 67 70 72 75
Unit size air temp.
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
°FDB MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
75 23.7 17.6 26.8 18.8 30.0 19.6 33.2 20.2 35.1 20.2 35.7 19.0
79 23.7 17.6 26.8 18.8 30.0 19.6 33.2 20.2 34.5 20.1 35.1 18.8
83 23.7 17.6 26.8 18.8 30.0 19.6 33.2 20.2 33.9 19.8 34.5 18.7
87 23.7 17.6 26.8 18.8 30.0 19.6 33.0 20.3 33.4 19.7 34.0 18.7
30
91 23.7 17.6 26.8 18.8 30.0 19.6 32.4 20.1 32.8 19.5 33.4 18.7
95 23.7 17.6 26.8 18.8 30.0 19.6 31.8 20.1 32.2 19.3 32.9 18.7
99 23.7 17.6 26.8 18.8 30.0 19.6 31.3 19.9 31.7 19.3 32.3 18.6
103 23.7 17.6 26.8 18.8 30.0 19.6 30.7 19.6 31.1 19.3 31.7 18.4
75 28.4 23.5 32.2 25.1 36.0 26.3 39.8 27.1 42.1 27.1 42.8 25.8
79 28.4 23.5 32.2 25.1 36.0 26.3 39.8 27.1 41.4 27.0 42.1 25.4
83 28.4 23.5 32.2 25.1 36.0 26.3 39.8 27.1 40.7 26.7 41.5 25.2
87 28.4 23.5 32.2 25.1 36.0 26.3 39.5 27.1 40.0 26.4 40.8 24.9
36
91 28.4 23.5 32.2 25.1 36.0 26.3 38.9 27.1 39.4 26.2 40.1 24.7
95 28.4 23.5 32.2 25.1 36.0 26.3 38.2 27.1 38.7 25.9 39.4 24.4
99 28.4 23.5 32.2 25.1 36.0 26.3 37.5 27.0 38.0 25.7 38.8 24.2
103 28.4 23.5 32.2 25.1 36.0 26.3 26.9 26.9 37.3 25.4 38.1 24.0
75 37.9 30.6 42.9 32.7 48.0 34.4 53.1 35.6 56.1 35.6 57.1 34.0
79 37.9 30.6 42.9 32.7 48.0 34.4 53.1 35.6 55.2 35.5 56.2 33.7
83 37.9 30.6 42.9 32.7 48.0 34.4 53.1 35.6 54.3 35.2 55.3 33.4
87 37.9 30.6 42.9 32.7 48.0 34.4 52.7 35.6 53.4 34.7 54.4 33.1
48
91 37.9 30.6 42.9 32.7 48.0 34.4 51.8 35.2 52.5 34.4 53.5 32.6
95 37.9 30.6 42.9 32.7 48.0 34.4 50.8 35.1 51.6 34.0 52.6 32.3
99 37.9 30.6 42.9 32.7 48.0 34.4 50.0 35.0 50.7 33.7 51.7 32.0
103 37.9 30.6 42.9 32.7 48.0 34.4 49.1 34.6 49.8 33.4 50.8 31.7
TC : Total capacity ; kW
SHC : Sensible heat capacity ; kW
Refer to Outdoor Unit Capacity Tables for the actual performance data of each indoor and outdoor unit combination.
FXMQ-M 9
Capacity Tables EDUS39-600-F4
FXMQ-M
Heating Capacity
Indoor Air Temp. °FDB
Outdoor Air Temp. 62 65 68 70 72 75
Indoor unit
TC TC TC TC TC TC
°FDB °FWB MBh MBh MBh MBh MBh MBh
22.0 20.0 29.2 29.1 29.1 29.0 29.0 28.9
26.0 24.0 30.6 30.5 30.5 30.4 30.4 30.3
30.0 28.0 32.0 31.9 31.9 31.8 31.8 30.6
35.0 32.0 33.3 33.3 33.2 33.2 32.5 30.6
39.0 36.0 34.7 34.7 34.6 34.0 32.5 30.6
30 44.0 40.0 36.1 36.1 35.0 34.0 32.5 30.6
47.0 43.0 37.2 36.9 35.0 34.0 32.5 30.6
51.0 47.0 38.6 36.9 35.0 34.0 32.5 30.6
54.0 50.0 38.7 36.9 35.0 34.0 32.5 30.6
57.0 53.0 38.7 36.9 35.0 34.0 32.5 30.6
60.0 56.0 38.7 36.9 35.0 34.0 32.5 30.6
22.0 20.0 35.0 35.0 34.9 34.8 34.8 34.7
26.0 24.0 36.7 36.6 36.6 36.5 36.5 36.4
30.0 28.0 38.4 38.3 38.2 38.2 38.1 36.8
35.0 32.0 40.0 40.0 39.9 39.8 39.0 36.8
39.0 36.0 41.7 41.6 41.6 40.0 39.0 36.8
36 44.0 40.0 43.4 43.3 42.0 40.0 39.0 36.8
47.0 43.0 44.6 44.2 42.0 40.0 39.0 36.8
51.0 47.0 46.3 44.2 42.0 40.0 39.0 36.8
54.0 50.0 46.5 44.2 42.0 40.0 39.0 36.8
57.0 53.0 46.5 44.2 42.0 40.0 39.0 36.8
60.0 56.0 46.5 44.2 42.0 40.0 39.0 36.8
22.0 20.0 46.7 46.6 46.5 46.5 46.4 46.3
26.0 24.0 48.9 48.8 48.7 48.7 48.6 48.5
30.0 28.0 51.1 51.1 51.0 50.9 50.8 49.0
35.0 32.0 53.4 53.3 53.2 53.1 52.0 49.0
39.0 36.0 55.6 55.5 53.2 54.0 52.0 49.0
48 44.0 40.0 57.8 57.7 56.0 54.0 52.0 49.0
47.0 43.0 59.5 59.0 58.0 54.0 52.0 49.0
51.0 47.0 61.7 59.0 56.0 54.0 52.0 49.0
54.0 50.0 62.0 59.0 56.0 54.0 52.0 49.0
57.0 53.0 62.0 59.0 56.0 54.0 52.0 49.0
60.0 56.0 62.0 59.0 56.0 54.0 52.0 49.0
Refer to Outdoor Unit Capacity Tables for the actual performance data of each indoor and outdoor unit combination.
10 FXMQ-M
EDUS39-600-F4 Fan Performances
8. Fan Performances
WG WG WG
Note:
1. The remote controller can be used to switch between HIGH and LOW.
2. The airflow is set to STANDARD before leaving the factory. It is possible to switch between STANDARD ESP and
HIGH ESP by changing the terminals in the indoor unit electrical box.
FXMQ-M 11
Sound Levels EDUS39-600-F4
9. Sound Levels
Overall
dBA
Model 208~230V, 60Hz
H L
FXMQ30MVJU 45 41
FXMQ36MVJU 45 41
FXMQ48MVJU 48 45
12 FXMQ-M
EDUS39-600-F4 Installation
10. Installation
Center of Gravity
A B
FXMQ30MVJU 28-3/8 11-3/8
FXMQ36, 48MVJU 43-3/4 20-1/8
4D042517
FXMQ-M 13
Installation EDUS39-600-F4
• Install the air conditioner on a foundation strong To avoid injury wear gloves or cover the fins when working
enough to withstand the weight of the unit. around them.
A foundation of insufficient strength may result in the equip- • Use of unspecified parts can result in the unit fall-
ment falling and causing injuries. ing, leaks, and even electric shock or fire.
• Carry out the specified installation work after taking • Entrust installation to the place of purchase or a
into account strong winds, typhoons or earth- qualified serviceman.
quakes. Improper installation can lead to result in leaks and even
Improper installation work may result in the equipment fall- electric shock or fire.
ing and causing accidents. • Do not allow children to play on or around the unit as
• Make sure that a separate power supply circuit is they could be injured.
provided for this unit and that all electrical work is • Placing a flower vase or other containers with water
carried out by qualified personnel according to local or other liquids can result in a shock hazard or fire if
laws and regulations and this installation manual. a spill occurs.
An insufficient power supply capacity or improper electrical • Do not remove the front panel because some parts
construction may lead to electric shocks or fire. are dangerous to touch. In addition, some parts may
• Make sure that all wiring is secured, the specified be damaged. For checking and adjusting internal parts,
wires and used, and no external forces act on the ter- contact your dealer.
minal connections or wires. • Do not put a finger or other objects into the air inlet
Improper connections or installation may result in fire. or air outlet. The fan is rotating at high speed and
• When wiring the power supply and connecting the injury can result.
remote controller wiring and transmission wiring, Do not let the indoor unit get wet as it may cause an
position the wires so that the electric parts box lid electric shock or fire.
can be securely fastened. • Refrigerant pipes may be very hot or very cold dur-
Improper positioning of the electric parts box lid may result ing or immediately after operation.
in electric shocks, fire or the terminals overheating. • Touching them can result in burns or frostbite. To avoid
• Before touching electrical parts, turn off the unit. injury give the pipes time to return to normal temperature
• Check the unit stand for damage on a continuous or, if you must touch them, be sure to wear proper gloves.
basis, especially if it has been used for a long time.
CAUTION
If left in a damaged condition, the unit may fall and cause
injury. • While following the instructions in this installation man-
• Do not touch the air outlet or the horizontal flaps ual, install drain piping in order to ensure proper drainage
while the swing flap is in operation as fingers may and insulate piping in order to prevent condensation.
get caught and injured. Improper drain piping may result in water leakage and
• Be sure to establish a ground. property damage.
Do not ground the unit to a utility pipe, arrester, or tele- • Be very careful about product transportation.
phone ground. Some products use PP bands for packaging. Do not use
Incomplete ground may cause electrical shock, or fire. any PP bands for a means of transportation. It is danger-
A high surge current from lightning or other sources may ous.
cause damage to the air conditioner. • Safely dispose of the packing materials.
• Do not touch the switch with wet fingers. Packing materials, such as nails and other metal or wooden
Touching a switch with wet fingers can cause electric parts, may cause stabs or other injuries.
shock. • Tear apart and throw away plastic packaging bags so that
• Be sure to install a ground leakage breaker. children will not play with them and risk suffocation. Do not
Failure to install a ground leakage breaker may result in turn off the power immediately after stopping opera-
electric shocks, or fire. tion.
• Do not install the air conditioner in the following Do Always wait at least five minutes before turning off the
not install the air conditioner in the following loca- power or water leakage and other problems may occur.
tions: • Take adequate measures to prevent the outdoor
(a) Where a mineral oil mist or oil spray or vapor is pro- unit from being used as a shelter by small animals.
duced, for example, in a kitchen. Small animals making contact with electrical parts can
Plastic parts may deteriorate and fall off or result in cause malfunctions, smoke or fire. Please instruct the cus-
water leakage. tomer to keep the area around the unit clean.
(b) Where corrosive gas, such as sulfurous acid gas, is
produced. NOTE
Corroding copper pipes or soldered parts may result in • Install the indoor and outdoor units, power supply wir-
refrigerant leakage. ing, and connecting wires at least 3.5 ft. away from tele-
(c) Near machinery emitting electromagnetic waves visions or radios in order to prevent image interference
Electromagnetic waves may disturb the operation of the or noise.
control system and result in a malfunction of the equip- Depending on the radio waves, a distance of 3.5 ft. may not
ment. be sufficient to eliminate the noise.
• Heat exchanger fins are sharp enough to cut.
14 FXMQ-M
EDUS39-600-F4 Installation
NOTE
• Be sure to read this manual before installing the indoor unit.
• Be sure to procure an air filter in the field and mount it in the
suction air passage to prevent water leaks or other prob-
lems.
FXMQ-M 15
Installation EDUS39-600-F4
Mid
for liquid pipe 3. SELECTING INSTALLATION SITE
Name Clamp Screws for duct flanges Please attach additional thermal insulation material to the unit
(Other) body when it is believed that the relative humidity in the ceiling
Quantity 6 pcs. As described in table below
• Operation exceeds 80%. Use glass wool, polyethylene foam, or similar
manual with a thickness of 3/8”. or more as thermal insulation material.
• Installa-
tion manual (1) Select and installation site that meets your customer’s
• Washers approval and where the following conditions are fulfilled:
Shape
for hanger • The upper space (including the back of the ceiling) of
FXMQ30MVJU 16 bracket the indoor unit has no possibility of dripping of water
·
FXMQ36 48MVJU 28 (8 pcs.)
from the refrigerant pipe, drain pipe, water pipe, etc.
• Optimum air distribution can be ensured.
• Nothing blocks air passage.
2-2 OPTIONAL ACCESSORIES • Condensate can be properly drained.
Table 1 • In the upper space (including the back of the ceiling) of
Remote controller the indoor unit where there is no possible dripping of
Wired type BRD1C71 water from the refrigerant pipe, drain pipe, water pipe, etc.
TAKE SPECIAL CARE DURING CONSTRUCTION • False ceiling is not noticeably on an incline.
AND AFTER INSTALLATION IS COMPLETED, • Sufficient clearance for maintenance and service can
CAREFULLY CHECK THE FOLLOWING ITEMS: be ensured.
• Piping between indoor and outdoor units is possible
a. Items to be checked after completion of work within the allowable limit. (Refer to the installation man-
The following problems may
ual for the outdoor unit.)
Items to be checked Check
occur If not properly done:
DANGER
Are the indoor and outdoor Units may drop, vibrate, or
unit fixed firmly? make noise. • Do not install unit in an area where flammable materials are
May result in insufficient present due to the risk of explosion resulting in serious
Is the gas leak test finished? injury or death.
cooling.
Is the unit fully insulated? Condensate water may drip. • If the supporting structural members are not strong
enough to withstand the unit’s weight, the unit can fall
Does drainage flow out of place and cause serious injury.
Condensate water may drip.
smoothly?
Does the power supply volt-
Unit may malfunction or the
NOTE
age correspond to that
components burn out. • Install the indoor and outdoor units, power supply wiring
shown on the name plate?
and connecting wires at least 3.5 feet away from televi-
Are wiring and piping cor- Unit may malfunction or the
rect? components burn out.
sions or radios in order to prevent image interference or
noise.
Danger of electrical leak- Depending on the radio waves, a distance of 3.5 feet may
Is the unit safely grounded?
age. not be enough to eliminate the noise.
Is wiring size according to Unit may malfunction or the
specifications? components burn out.
Is something blocking the
air outlet or inlet of either the Insufficient cooling.
indoor or outdoor units?
Are refrigerant piping length
The refrigerant charge in
and additional refrigerant
the system is not clear.
charge noted down?
16 FXMQ-M
EDUS39-600-F4 Installation
(2) Use suspension bolts for installation. Check to make (3) Install suspension bolts.
sure the ceiling is strong enough to support the Use bolts of 3/8” diameter.
weight of the unit . If there is a risk, reinforce the ceil- • Install the equipment where supporting structures are
ing before installing the unit. strong enough to bear the equipment’s weight. Use
embedded inserts or anchor bolts with new buildings
FXMQ30 · 36 · 48MVJU and hole-in-anchors with old buildings.
Min. 17 11/16
Installation example
Ceiling slab
Anchor
Long nut or turn-buckle
Suspension bolt
Indoor unit
Model A
FXMQ30MVJU 29 1/2 Note) All the above parts are field supplied.
A
FXMQ36MVJU 43 5/16
48MVJU
5. INDOOR UNIT INSTALLATION
Min. 27 9/16 (service space) Installing optional accessories before installing the
indoor unit is easier.
Fig. 1 (length: in.)
Use only the provided specific accessories and parts desig-
nated by Daikin AC.
4. PREPARATIONS BEFORE INSTALLATION (1) Fix the hanger bracket to the suspension bolt. Use wash-
(1) Relative positions of indoor unit and suspension bolt. ers to firmly tighten both upper and lower nuts. .
(Refer to Fig. 2) Part to be procured in the field
FXMQ30 · 36 · 48MVJU Washer (accessory)
Suspension bolt (× 4)
Hanger bracket
FXMQ-M 17
Installation EDUS39-600-F4
• To prevent flare nut cracking and gas leaks, be sure to use 6-3 Piping insulation
both a spanner and torque wrench together, as shown in • Execute heat insulation work completely on both sides of
the drawing below, when connecting or disconnecting the gas piping and the liquid piping or a water leakage may
pipes to/from the unit. result .
Torque wrench • When using a heat pump, the temperature of the gas piping
can reach up to approximately 250°F, so use sufficiently
resistant insulation.
• Also, in cases where the temperature and humidity of the
Spanner refrigerant piping sections might exceed 86°F or RH80%,
reinforce the refrigerant insulation. (13/16” or thicker) Conden-
Piping union sation may form on the surface of the insulating material.
• Check the pipe connector for gas leaks, then insulate it as
Flare nut shown in the drawing below.
• Refer to Table 2 for the dimensions of flare nut spaces. • Make absolutely sure to execute heat insulation works on
• Refer toTable 2 to determine the proper tightening torque. the pipe-connecting section after checking gas leakage by
Table 2 thoroughly studying the following figure and using the
Tightening Flare
attached heat insulating materials for fitting. Fasten both
Pipe ends with the accessory clamps.
torque dimensions Flare shape (in.)
size
(ft.lbf) A (in.) • Wrap the accessory sealing pad only around the insulation
for the joints on the gas piping side.
φ 1/4” 10.4 – 12.7 0.342-0.358
R0.016-
45˚±2˚
Clamp (× 4)
φ 3/8” 0.031
90˚±2˚
Gas pipe
Liquid pipe
18 FXMQ-M
EDUS39-600-F4 Installation
CAUTION
7. DRAIN PIPING WORK
Install the drain pipe as shown below and take measures
• Be sure to insulate any field piping all the way to the piping against condensation. Improperly rigged piping could
connection inside the unit. Any exposed piping may cause lead to leaks on furniture and belongings.
condensation or burns if touched. Insulate the drain piping inside the building.
6-4 Brazing refrigerant piping (1) Install drain piping as shown in the following figure:
• Before brazing local refrigerant piping, nitrogen gas must
be blown through the piping to expel air from the piping. Attached drain hose
If your brazing is done without nitrogen gas blowing, a large
amount of oxide film develops inside the piping, and could Bottom of unit
cause system malfunction.
• When brazing the refrigerant piping, only begin brazing
or more
1 15/16
after having carried out nitrogen substitution or while
inserting nitrogen into the refrigerant piping. Once this is
done, connect the indoor unit with a flared or a flanged con-
or more
1 15/16
nection.
• Nitrogen should be set to 2.9psi. with a pressure-reducing
valve if brazing while inserting nitrogen into the piping.
FXMQ-M 19
Installation EDUS39-600-F4
(2) After piping work is finished, check that drainage flows 8-3 SPECIFICATIONS FOR FIELD SUPPLIED
smoothly. FUSES AND WIRE
• Add approximately 61in3 of water slowly from the air
inlet and check drainage flow. Remote controller
wiring
Power supply wiring
NOTE Transmission wir-
Model ing
• Drain piping connections Field fuses
Do not connect the drain piping directly to sewage pipes that Size Wire Size
smell of ammonia. The ammonia in the sewage might enter
the indoor unit through the drain pipes and corrode the heat FXMQ30MVJU Wire size
Sheathed
must com- AWG
exchanger. FXMQ36MVJU 15A wire
ply with local 18-16
(2 wire)
FXMQ48MVJU codes.
8. ELECTRIC WIRING WORK NOTE
8-1 GENERAL INSTRUCTIONS • Allowable length of transmission wiring between indoor/
• All field supplied parts, materials, and electrical works outdoor units and between the indoor unit and the remote
must conform to local codes. controller is as follows.
• Use copper wire only. (1) Outdoor unit – Indoor unit:
Max. 3280 ft. (1000 m); Total wiring length: 6560 ft.
• For electric wiring work, refer to also “Wiring diagram label”
(2000 m)
attached to the electric parts box lid.
(2) Indoor unit – Remote controller:
• For remote controller wiring details, refer to the installation
Max. 1640 ft. (500 m)
manual attached to the remote controller.
• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each 9. WIRING EXAMPLE AND HOW TO SET
indoor unit as unit A, unit B, and so forth, and be sure the
terminal board wiring to the outdoor unit and BS unit are
THE REMOTE CONTROLLER
properly matched. If controls wiring and piping between the 9-1 HOW TO CONNECT WIRINGS
outdoor and indoor units are mismatched, a communica-
Remove the electric parts box lid and wire as shown in the fol-
tions malfunction is likely.
lowing figure: FXMQ30 - 36 - 48MVJU
• A circuit breaker capable of shutting down power supply to
the entire system must be installed. FXMQ30 · 36 · 48MVJU
• Refer to the installation manual attached to the outdoor unit
for the size of its power supply, the capacity of the circuit Conduit
breaker and switch, and wiring instructions. Lock
• Be sure to ground the air conditioner. nut
Electric
DANGER parts Ground wiring
box lid Power supply wiring
• Do not ground units to water pipes, telephone wires, or
lightning rods because incomplete grounding can cause a (Field wiring)
severe shock hazard resulting in severe injury or death. Do
not ground units to gas pipes because a gas leak could Transmission
result in an explosion which could lead to severe injury or wiring
death. (Field wiring)
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (W); FLA: Full Load Amps (A)
20 FXMQ-M
EDUS39-600-F4 Installation
Power NOTE
supply Power supply
terminal X1M wiring, 1. Use round crimp-style terminals for connecting wires to
block ground wiring the power supply terminal block.
If unavailable, observe the following points when wiring.
L1 L2
• Do not connect wires of a different gauge to the same
power supply terminal because looseness
Conduit in the connection may cause overheating.
Field
supply • Use the specified electrical wire. and connect it
wire securely to the terminal. Lock the wire down without
P1 P2 F1 F2 T1 T2
REMOTE TRANSMISSION FORCED
OFF
Transmission
wiring applying excessive force to the terminal. (Tightening
WIRING
Terminal
block for Remote
remote controller Attach insulation sleeve
controller X2M wiring
FXMQ-M 21
Installation EDUS39-600-F4
9-2 WIRING EXAMPLE 2. Example of group control or use with 2 remote con-
• Fit the power supply wiring of each unit with a switch and trollers:
fuse as shown in the following drawing.
Note: It is not necessary to designate indoor unit address when
COMPLETE SYSTEM EXAMPLE using group control.
The address is automatically set when power is activated.
Power supply Power supply wiring Power supply Power supply Power supply Power supply
208-230V Outdoor unit 208-230V 208-230V 208-230V
Main Transmission wiring 60Hz~ Control box 60Hz~ 60Hz~ 60Hz~
IN/D OUT/D
switch Switch L1 L2 F1 F2 F1 F2
L1 L2 L1 L2 L1 L2
No. 2
Fuse System
Most
downstream
indoor unit
L1 L2 P1 P2 F1 F2 T1 T2 L1 L2 P1 P2 F1 F2 T1 T2 L1 L2 P1 P2 F1 F2 T1 T2 L1 L2 P1 P2 F1 F2 T1 T2
Lower part of
remote controller
22 FXMQ-M
EDUS39-600-F4 Installation
F2 T1 T2
10. FIELD SETTING
FORCED Make sure the terminal box lids are closed on the indoor
OFF
and outdoor units.
Input A Field setting must be made from the remote controller in
accordance with the installation condition.
• Setting can be made by changing the MODE NO., FIRST
CODE NO., and SECOND CODE NO.
Wire specification 2-conductor, stranded, non-shielded cop- • For setting and operation, refer to the FIELD SETTING in
per cable / PVC or vinyl jacket the installation manual of the remote controller.
Gauge AWG 18
Length Max. 328ft.
Contact that can ensure the minimum appli-
External terminal
cable load of 15 V DC, 10 mA.
(2) Actuation
• The following table explains FORCED OFF and ON/
OFF OPERATIONS in response to Input A. The T1-T2 • Set the remote controller to the field set mode. For details,
terminals are standard on all Daikin indoor units and refer to the section HOW TO SET IN THE FIELD in the
allow for remote starting and stopping of equipment. REMOTE CONTROLLER MANUAL.
Individual indoor units can be field prgrammed at the • When in the field set mode, select the MODE NO. to [12]
remote controller to change the T1-T2 sequence of and set the FIRST CODE SWITCH (switch) No. to [1]. Then
operation of the equipment based upon the application set the SECOND CODE NO. (position) to [01] for FORCED
OFF and [02] for ON/OFF OPERATION. FORCED OFF is
factory setting.
FXMQ-M 23
Installation EDUS39-600-F4
24 FXMQ-M
EDUS39-600-F4 Accessories
11. Accessories
Standard Accessories
Metal Drain Insulation for
Name Sealing pad Clamp Screws for duct flanges
clamp hose fitting
Quantity 1 pc. 1 pc. 1 each. 1 each. 6 pcs. As described in table below (Other)
• Operation
manual
• Installation
Shape for liquid pipe Large manual
FXMQ30MVJU 16 • Washers
·
FXMQ36 48MVJU 28 (8 pcs.)
3P086156-9T
FXMQ-M 25
EDUS 39 - 600 - F2
FXDQ-M
Slim Ceiling Mounted Duct Type
AMERICAS
1645 Wallace Drive, Suite 110
Carrollton, TX75006
info@daikinac.com
www.daikinac.com
May 2007
EDUS39-600-F4 AMERICAS
Printed in U.S.A. 05/2007