You are on page 1of 60

EDMT391710

FXMQ20-140PAVE
Ceiling Mounted Duct Type
50 / 60 Hz
EDMT391710

FXMQ-PAVE
Ceiling Mounted Duct Type

1. Specifications ..........................................................................................2
2. Dimensions .............................................................................................5
3. Piping Diagrams....................................................................................10
4. Wiring Diagrams....................................................................................11
5. Electric Characteristics..........................................................................12
6. Safety Devices Setting ..........................................................................13
7. Capacity Tables ....................................................................................14
7.1 Cooling Capacity for Te: Auto ................................................................14
7.2 Cooling Capacity for Te: 6°C..................................................................14
7.3 Cooling Capacity for Te: 9°C..................................................................15
7.4 Heating Capacity ....................................................................................15
8. Fan Performances.................................................................................16
9. Airflow Auto Adjustment Characteristics ...............................................25
10.Sound Levels ........................................................................................33
11.Accessories...........................................................................................38
11.1 Optional Accessories (for Unit)...............................................................38
11.2 Optional Accessories (for Controls)........................................................38
12.Centre of Gravity ...................................................................................39
13.Installation Manual ................................................................................40

FXMQ-PAVE 1
Specifications EDMT391710

1. Specifications
Ceiling mounted duct type
Model FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE
Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 1,900 2,400 3,100
1 3 Cooling capacity Btu/h 7,500 9,600 12,300
kW 2.2 2.8 3.6
kcal/h 2,200 2,800 3,400
2 3 Heating capacity Btu/h 8,500 10,900 13,600
kW 2.5 3.2 4.0
50 Hz kW 0.056 0.056 0.060
Cooling
7 60 Hz kW 0.056 0.056 0.059
Power input 50 Hz kW 0.044 0.044 0.048
Heating
60 Hz kW 0.044 0.044 0.048
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 300×550×700 300×550×700 300×550×700
Model — — —
Type Sirocco fan Sirocco fan Sirocco fan
Motor output ×
W 90×1 90×1 90×1
Number of units
Fan m3/min 9/7.5/6.5 9/7.5/6.5 9.5/8/7
Airflow rate (HH/H/L) l/s 150/125/108 150/125/108 158/133/116
cfm 318/265/230 318/265/230 335/282/247
External static pressure Pa Rated 50 (100-30 4) Rated 50 (100-30 4) Rated 50 (100-30 4)
Drive Direct drive Direct drive Direct drive

Temperature control Microprocessor thermostat for Microprocessor thermostat for Microprocessor thermostat for
cooling and heating cooling and heating cooling and heating
Air filter — 5 — 5 — 5
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
Piping
connections VP25 VP25 VP25
Drain pipe mm
( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 ) ( External
Internal dia. 25 )
dia. 32

Mass kg 25 25 25
6 Sound pressure level (HH/H/L) dB(A) 33/31/29 33/31/29 34/32/30
Sound power level (H) dB 51 51 52

Safety devices Fuse, Fuse, Fuse,


Fan driver overload protector Fan driver overload protector Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Operation manual, Installation manual, Operation manual, Installation manual,
Drain hose, Sealing pads, Clamps, Drain hose, Sealing pads, Clamps, Drain hose, Sealing pads, Clamps,
Standard accessories Washers, Screws, Insulation for fitting, Washers, Screws, Insulation for fitting, Washers, Screws, Insulation for fitting,
Clamp metal, Air discharge flange, Air Clamp metal, Air discharge flange, Air Clamp metal, Air discharge flange, Air
suction flange suction flange suction flange
Specification C: 3D105230A C: 3D105230A C: 3D105230A
Drawing No.
Sound level C: 4D062535A C: 4D062535A C: 4D062536A

Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping length: 7.5 m, level difference: Conversion formulae
0 m.
kcal/h=kW×860
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: 7.5 m, level difference: Btu/h=kW×3412
0 m. l/s=m3/min×1000/60
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m3/min×35.3
4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity
method) 50% or more.
6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external static pressure.

2 FXMQ-PAVE
EDMT391710 Specifications

Ceiling mounted duct type


Model FXMQ40PAVE FXMQ50PAVE FXMQ63PAVE FXMQ80PAVE
1 phase, 220-240/220 V, 1 phase, 220-240/220 V, 1 phase, 220-240/220 V, 1 phase, 220-240/220 V,
Power supply
50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
kcal/h 3,900 4,800 6,100 7,700
1 3 Cooling capacity Btu/h 15,400 19,100 24,200 30,700
kW 4.5 5.6 7.1 9.0
kcal/h 4,300 5,400 6,900 8,600
2 3 Heating capacity Btu/h 17,100 21,500 27,300 34,100
kW 5.0 6.3 8.0 10.0
50 Hz kW 0.151 0.128 0.138 0.185
Cooling
7 60 Hz kW 0.150 0.127 0.138 0.184
Power input 50 Hz kW 0.139 0.116 0.127 0.173
Heating
60 Hz kW 0.139 0.116 0.127 0.173
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 300×700×700 300×1,000×700 300×1,000×700 300×1,000×700
Model — — — —
Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan
Motor output ×
Number of units W 140×1 350×1 350×1 350×1

m3/min 16/13/11 18/16.5/15 19.5/17.5/16 25/22.5/20


Fan
Airflow rate (HH/H/L) l/s 267/216/183 300/275/250 325/292/267 417/375/333
cfm 565/459/388 635/582/530 688/618/565 883/794/706
External static
Pa Rated 100 (160-30 4) Rated 100 (200-50 4) Rated 100 (200-50 4) Rated 100 (200-50 4)
pressure
Drive Direct drive Direct drive Direct drive Direct drive
Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat
Temperature control
for cooling and heating for cooling and heating for cooling and heating for cooling and heating
Air filter — 5 — 5 — 5 — 5
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection)

Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection)
connections VP25 VP25 VP25 VP25
Drain pipe mm
( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 ) ( External
Internal dia. 25 )
dia. 32

Mass kg 27 35 35 35
6 Sound pressure level (HH/H/L) dB(A) 39/37/35 41/39/37 42/40/38 43/41/39
Sound power level (H) dB 57 59 60 61
Fuse, Fuse, Fuse, Fuse,
Safety devices Fan driver overload Fan driver overload Fan driver overload Fan driver overload
protector protector protector protector
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual, Operation manual, Operation manual, Operation manual,
Installation manual, Drain Installation manual, Drain Installation manual, Drain Installation manual, Drain
hose, Sealing pads, hose, Sealing pads, hose, Sealing pads, hose, Sealing pads,
Standard accessories Clamps, Washers, Screws, Clamps, Washers, Screws, Clamps, Washers, Screws, Clamps, Washers, Screws,
Insulation for fitting, Clamp Insulation for fitting, Clamp Insulation for fitting, Clamp Insulation for fitting, Clamp
metal, Air discharge flange, metal, Air discharge flange, metal, Air discharge flange, metal, Air discharge flange,
Air suction flange Air suction flange Air suction flange Air suction flange
Specification C: 3D105230A C: 3D105230A C: 3D105230A C: 3D105230A
Drawing No.
Sound level C: 4D060446C C: 4D060428C C: 4D060447C C: 4D060429C

Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping length: 7.5 m, level difference: Conversion formulae
0 m.
kcal/h=kW×860
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: 7.5 m, level difference: Btu/h=kW×3412
0 m. l/s=m3/min×1000/60
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m3/min×35.3
4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity
method) 50% or more.
6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external static pressure.

FXMQ-PAVE 3
Specifications EDMT391710

Ceiling mounted duct type


Model FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 9,600 12,000 13,800
1 3 Cooling capacity Btu/h 38,200 47,800 54,600
kW 11.2 14.0 16.0
kcal/h 10,800 13,800 15,500
2 3 Heating capacity Btu/h 42,700 54,600 61,400
kW 12.5 16.0 18.0
50 Hz kW 0.215 0.284 0.405
Cooling
7 60 Hz kW 0.214 0.283 0.404
Power input 50 Hz kW 0.203 0.272 0.380
Heating
60 Hz kW 0.203 0.272 0.380
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 300×1,400×700 300×1,400×700 300×1,400×700
Model — — —
Type Sirocco fan Sirocco fan Sirocco fan
Motor output ×
W 350×1 350×1 350×1
Number of units
m3/min 32/27/23 39/33/28 46/39/32
Fan
Airflow rate (HH/H/L) l/s 533/450/383 650/550/466 767/650/533
cfm 1,130/953/812 1,377/1,165/988 1,624/1,377/1,130
External static
Pa Rated 100 (200-50 4) Rated 100 (200-50 4) Rated 100 (140-50 4)
pressure
Drive Direct drive Direct drive Direct drive
Microprocessor thermostat for cooling Microprocessor thermostat for cooling Microprocessor thermostat for cooling
Temperature control
and heating and heating and heating
Air filter — 5 — 5 — 5
Liquid pipes mm φ9.5 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection)
Gas pipes mm φ15.9 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection)
Piping
connections VP25 VP25 VP25
Drain pipe mm
( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 )
Mass kg 45 45 46
6 Sound pressure level (HH/H/L) dB(A) 43/41/39 44/42/40 46/45/43
Sound power level (H) dB 61 62 64
Fuse, Fuse, Fuse,
Safety devices
Fan driver overload protector Fan driver overload protector Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Operation manual, Installation manual, Operation manual, Installation manual,
Drain hose, Sealing pads, Clamps, Drain hose, Sealing pads, Clamps, Drain hose, Sealing pads, Clamps,
Standard accessories Washers, Screws, Insulation for fitting, Washers, Screws, Insulation for fitting, Washers, Screws, Insulation for fitting,
Clamp metal, Air discharge flange, Air Clamp metal, Air discharge flange, Air Clamp metal, Air discharge flange, Air
suction flange suction flange suction flange
Specification C: 3D105230A C: 3D105230A C: 3D105230A
Drawing No.
Sound level C: 4D060448C C: 4D060449C C: 4D063786A

Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping length: 7.5 m, level difference: Conversion formulae
0 m.
kcal/h=kW×860
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Rated external static pressure / Equivalent piping length: 7.5 m, level difference: Btu/h=kW×3412
0 m. l/s=m3/min×1000/60
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m3/min×35.3
4. External static pressure is changeable in 7 stages (FXMQ20/25/32PAVE), 13 stages (FXMQ40PAVE), 14 stages
(FXMQ50/63/80/100/125PAVE), 10 stages (FXMQ140PAVE) by remote controller.
5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity
method) 50% or more.
6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external static pressure.

4 FXMQ-PAVE
EDMT391710 Dimensions

2. Dimensions
FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE

3D105236
Unit: mm

FXMQ-PAVE 5
Dimensions EDMT391710

FXMQ40PAVE

3D105231
Unit: mm

6 FXMQ-PAVE
EDMT391710 Dimensions

FXMQ50PAVE

3D105232
Unit: mm

FXMQ-PAVE 7
Dimensions EDMT391710

FXMQ63PAVE / FXMQ80PAVE

3D105233
Unit: mm

8 FXMQ-PAVE
EDMT391710 Dimensions

FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE

3D105235
Unit: mm

FXMQ-PAVE 9
Piping Diagrams EDMT391710

3. Piping Diagrams
FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE / FXMQ40PAVE / FXMQ50PAVE / FXMQ63PAVE /
FXMQ80PAVE / FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE

4D104913

 Refrigerant pipe connection port diameters


Unit: mm
Model Gas Liquid
FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE / FXMQ40PAVE / FXMQ50PAVE φ12.7 φ6.4
FXMQ63PAVE / FXMQ80PAVE / FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE φ15.9 φ9.5

10 FXMQ-PAVE
EDMT391710 Wiring Diagrams

4. Wiring Diagrams
FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE / FXMQ40PAVE / FXMQ50PAVE / FXMQ63PAVE /
FXMQ80PAVE / FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE

3D103336

FXMQ-PAVE 11
Electric Characteristics EDMT391710

5. Electric Characteristics
FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE / FXMQ40PAVE / FXMQ50PAVE / FXMQ63PAVE /
FXMQ80PAVE / FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE

4D104911

12 FXMQ-PAVE
EDMT391710 Safety Devices Setting

6. Safety Devices Setting

Model FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE FXMQ50PAVE FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse
250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A
(Fan driver)
Drain pump thermal fuse °C — — — — — — — — — —
C: 3D104897

FXMQ-PAVE 13
Capacity Tables EDMT391710

7. Capacity Tables
7.1 Cooling Capacity for Te: Auto
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXMQ20PAVE 20 1.9 1.9 2.1 2.1 2.2 2.0 2.2 1.9 2.2 1.9 2.3 1.8 2.3 1.8
FXMQ25PAVE 25 2.5 2.2 2.6 2.3 2.8 2.5 2.8 2.3 2.8 2.2 2.9 2.1 3.0 2.2
FXMQ32PAVE 32 3.2 2.6 3.4 2.7 3.5 2.9 3.6 2.8 3.6 2.7 3.7 2.7 3.8 2.6
FXMQ40PAVE 40 4.0 3.7 4.2 4.0 4.4 4.2 4.5 3.8 4.6 3.7 4.7 3.5 4.8 3.6
FXMQ50PAVE 50 4.9 4.3 5.3 4.7 5.5 5.0 5.6 4.6 5.7 4.5 5.8 4.3 5.9 3.6
FXMQ63PAVE 63 6.3 5.1 6.7 5.5 7.0 5.8 7.1 5.5 7.2 5.4 7.3 5.3 7.5 5.2
FXMQ80PAVE 80 7.9 6.5 8.5 7.0 8.8 7.4 9.0 7.0 9.1 6.9 9.3 6.6 9.5 6.6
FXMQ100PAVE 100 9.9 8.2 10.5 8.8 11.0 9.1 11.2 8.5 11.3 8.4 11.6 8.1 11.8 7.8
FXMQ125PAVE 125 12.3 10.2 13.2 10.9 13.8 11.3 14.0 10.5 14.2 10.4 14.5 10.1 14.8 9.6
FXMQ140PAVE 140 14.1 11.8 15.0 12.5 15.7 12.8 16.0 12.0 16.2 11.9 16.5 11.5 16.9 11.2

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.

7.2 Cooling Capacity for Te: 6°C


Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXMQ20PAVE 20 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.2 1.9 2.3 1.8 2.3 1.8
FXMQ25PAVE 25 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 2.8 2.2 2.9 2.1 3.0 2.2
FXMQ32PAVE 32 2.4 2.1 2.9 2.4 3.4 2.7 3.6 2.8 3.6 2.7 3.7 2.7 3.8 2.6
FXMQ40PAVE 40 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.6 3.7 4.7 3.5 4.8 3.6
FXMQ50PAVE 50 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 5.7 4.5 5.8 4.3 5.9 3.6
FXMQ63PAVE 63 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.2 5.4 7.4 5.3 7.5 5.2
FXMQ80PAVE 80 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.1 6.9 9.3 6.6 9.5 6.6
FXMQ100PAVE 100 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.3 8.4 11.6 8.1 11.9 7.8
FXMQ125PAVE 125 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.2 10.4 14.5 10.1 14.9 9.7
FXMQ140PAVE 140 10.8 9.0 12.9 10.4 15.0 11.7 16.0 12.0 16.2 11.9 16.6 11.5 17.0 11.3

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.

14 FXMQ-PAVE
EDMT391710 Capacity Tables

7.3 Cooling Capacity for Te: 9°C


For VRV indoor units only at Te: 9°C /
mixed combination of VRV and residential indoor units

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXMQ20PAVE 20 1.0 1.0 1.3 1.3 1.6 1.6 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.6
FXMQ25PAVE 25 1.3 1.3 1.6 1.6 2.0 1.9 2.2 2.0 2.3 1.9 2.4 1.8 2.6 2.0
FXMQ32PAVE 32 1.6 1.6 2.0 2.0 2.6 2.3 2.9 2.4 2.9 2.3 3.1 2.4 3.3 2.4
FXMQ40PAVE 40 2.1 2.1 2.6 2.6 3.3 3.3 3.6 3.3 3.8 3.2 3.9 3.1 4.1 3.3
FXMQ50PAVE 50 2.6 2.6 3.2 3.2 4.0 3.8 4.4 3.9 4.6 3.9 4.9 3.8 5.1 3.3
FXMQ63PAVE 63 3.2 3.2 4.0 4.0 5.1 4.6 5.6 4.7 5.8 4.7 6.2 4.7 6.5 4.7
FXMQ80PAVE 80 4.2 4.1 5.1 5.0 6.5 5.9 7.2 6.0 7.4 6.0 7.8 5.8 8.2 6.0
FXMQ100PAVE 100 5.2 5.0 6.4 6.0 8.0 7.0 8.9 7.3 9.2 7.3 9.7 7.1 10.2 7.1
FXMQ125PAVE 125 6.5 6.2 8.0 7.5 10.1 8.8 11.2 9.1 11.6 9.0 12.2 8.9 12.8 8.8
FXMQ140PAVE 140 7.5 7.0 9.2 8.6 11.7 10.0 12.8 10.4 13.2 10.4 13.9 10.1 14.6 10.3

TC: Total capacity: kW


SHC: Sensible heat capacity: kW
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.

7.4 Heating Capacity


Indoor air temp.
Model Capacity 16°CDB 18°CDB 20°CDB 21°CDB 22°CDB 24°CDB
indication
kW kW kW kW kW kW
FXMQ20PAVE 20 2.6 2.6 2.5 2.4 2.3 2.2
FXMQ25PAVE 25 3.4 3.4 3.2 3.1 3.0 2.8
FXMQ32PAVE 32 4.2 4.2 4.0 3.9 3.7 3.5
FXMQ40PAVE 40 5.2 5.2 5.0 4.8 4.7 4.4
FXMQ50PAVE 50 6.6 6.6 6.3 6.1 5.9 5.5
FXMQ63PAVE 63 8.4 8.4 8.0 7.7 7.5 7.0
FXMQ80PAVE 80 10.5 10.5 10.0 9.7 9.4 8.7
FXMQ100PAVE 100 13.1 13.1 12.5 12.1 11.7 10.9
FXMQ125PAVE 125 16.8 16.8 16.0 15.5 15.0 13.9
FXMQ140PAVE 140 18.9 18.9 18.0 17.4 16.8 15.7

Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.

FXMQ-PAVE 15
Fan Performances EDMT391710

8. Fan Performances
FXMQ20PAVE / FXMQ25PAVE

3D062537B

16 FXMQ-PAVE
EDMT391710 Fan Performances

FXMQ32PAVE

3D062538B

FXMQ-PAVE 17
Fan Performances EDMT391710

FXMQ40PAVE

3D060456D

18 FXMQ-PAVE
EDMT391710 Fan Performances

FXMQ50PAVE

3D060457E

FXMQ-PAVE 19
Fan Performances EDMT391710

FXMQ63PAVE

3D060458D

20 FXMQ-PAVE
EDMT391710 Fan Performances

FXMQ80PAVE

3D060459C

FXMQ-PAVE 21
Fan Performances EDMT391710

FXMQ100PAVE

3D060460D

22 FXMQ-PAVE
EDMT391710 Fan Performances

FXMQ125PAVE

3D060461D

FXMQ-PAVE 23
Fan Performances EDMT391710

FXMQ140PAVE

3D063787A

24 FXMQ-PAVE
EDMT391710 Airflow Auto Adjustment Characteristics

9. Airflow Auto Adjustment Characteristics


FXMQ20PAVE / FXMQ25PAVE

3D062539B

FXMQ-PAVE 25
Airflow Auto Adjustment Characteristics EDMT391710

FXMQ32PAVE

3D062540B

26 FXMQ-PAVE
EDMT391710 Airflow Auto Adjustment Characteristics

FXMQ40PAVE

3D060577E

FXMQ-PAVE 27
Airflow Auto Adjustment Characteristics EDMT391710

FXMQ50PAVE

3D060578E

28 FXMQ-PAVE
EDMT391710 Airflow Auto Adjustment Characteristics

FXMQ63PAVE

3D060579E

FXMQ-PAVE 29
Airflow Auto Adjustment Characteristics EDMT391710

FXMQ80PAVE

3D060580E

30 FXMQ-PAVE
EDMT391710 Airflow Auto Adjustment Characteristics

FXMQ100PAVE

3D060581E

FXMQ-PAVE 31
Airflow Auto Adjustment Characteristics EDMT391710

FXMQ125PAVE

3D060582E

32 FXMQ-PAVE
EDMT391710 Sound Levels

10. Sound Levels


FXMQ20PAVE / FXMQ25PAVE

4D062535A
FXMQ32PAVE

4D062536A

FXMQ-PAVE 33
Sound Levels EDMT391710

FXMQ40PAVE

4D060446C
FXMQ50PAVE

4D060428C

34 FXMQ-PAVE
EDMT391710 Sound Levels

FXMQ63PAVE

4D060447C
FXMQ80PAVE

4D060429C

FXMQ-PAVE 35
Sound Levels EDMT391710

FXMQ100PAVE

4D060448C
FXMQ125PAVE

4D060449C

36 FXMQ-PAVE
EDMT391710 Sound Levels

FXMQ140PAVE

4D063786A

FXMQ-PAVE 37
Accessories EDMT391710

11. Accessories
11.1 Optional Accessories (for Unit)
Model
Item
FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE FXMQ50PAVE FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
65% KAF372AA36 KAF372AA56 KAF372AA80 KAF372AA160
High efficiency filter
90% KAF373AA36 KAF373AA56 KAF373AA80 KAF373AA160
Filter chamber KDDF37AA36 KDDF37AA56 KDDF37AA80 KDDF37AA160
Long life replacement filter KAF371AA36 KAF371AA56 KAF371AA80 KAF371AA160
Long life filter chamber kit KAF375AA36 KAF375AA56 KAF375AA80 KAF375AA160
White KTBJ25K36W KTBJ25K56W KTBJ25K80W KTBJ25K160W
Service panel Fresh white KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F
Brown KTBJ25K36T KTBJ25K56T KTBJ25K80T KTBJ25K160T
Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A
C: 3D104914

11.2 Optional Accessories (for Controls)


Model
Item
FXMQ20PAVE FXMQ25PAVE FXMQ32PAVE FXMQ40PAVE FXMQ50PAVE FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
For Cooling only BRC4C66 (Note 4)
Remote Wireless
For Heat pump BRC4C65 (Note 4)
controller
Wired BRC1C62 (Note 4)
Navigation remote controller BRC1E62 (Notes 4, 5)
(Wired remote controller)
Wired remote controller with weekly
BRC1D61
schedule timer
Simplified remote controller BRC2C51
Remote controller for hotel use BRC3A61
Adaptor for wiring KRP1C64
Wiring adaptor for electrical appendices (1) KRP2A61
Wiring adaptor for electrical appendices (2) KRP4AA51
Remote sensor KRCS01-4B
Mounting plate for adaptor printed
circuit board KRP4A97 (Notes 2, 3)

External control adaptor for outdoor unit DTA104A61


(Must be installed on indoor units)
Adaptor for multi tenant DTA114A61
C: 3D104915A

Notes:
1. Mounting plate is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each mounting plate.
3. Only one mounting plate can be installed for each indoor unit.
4. Wireless remote controller does not have AUTO fan mode.
Use wired remote controller to select AUTO fan mode.
5. Individual airflow direction, auto airflow rate and sensing sensor control can be set only via wired remote controller
BRC1E62. Cannot be set via other remote controllers. Available functions depend on the type of indoor unit.

38 FXMQ-PAVE
EDMT391710 Centre of Gravity

12. Centre of Gravity


FXMQ20PAVE / FXMQ25PAVE / FXMQ32PAVE / FXMQ40PAVE / FXMQ50PAVE / FXMQ63PAVE /
FXMQ80PAVE / FXMQ100PAVE / FXMQ125PAVE / FXMQ140PAVE
Unit: mm

4D104912

FXMQ-PAVE 39
Installation Manual EDMT391710

13. Installation Manual

3P432203-1B

40 FXMQ-PAVE
EDMT391710 Installation Manual

3P432203-1B

FXMQ-PAVE 41
Installation Manual EDMT391710

3P432203-1B

42 FXMQ-PAVE
EDMT391710 Installation Manual

3P432203-1B

FXMQ-PAVE 43
Installation Manual EDMT391710

3P432203-1B

44 FXMQ-PAVE
EDMT391710 Installation Manual

3P432203-1B

FXMQ-PAVE 45
Installation Manual EDMT391710

3P432203-1B

46 FXMQ-PAVE
EDMT391710 Installation Manual

3P432203-1B

FXMQ-PAVE 47
Installation Manual EDMT391710

3P432203-1B

48 FXMQ-PAVE
EDMT391710 Installation Manual

3P432203-1B

FXMQ-PAVE 49
Installation Manual EDMT391710

3P432203-1B

50 FXMQ-PAVE
EDMT391710 Installation Manual

3P432203-1B

FXMQ-PAVE 51
Installation Manual EDMT391710

3P432203-1B

52 FXMQ-PAVE
EDMT391710 Installation Manual

3P432203-1B

FXMQ-PAVE 53
Installation Manual EDMT391710

3P432203-1B

54 FXMQ-PAVE
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Specifications, designs and other content appearing in this brochure are current as of May 2017 but subject to change without notice.

All rights reserved 05/17 FS

You might also like