You are on page 1of 23

FCOB Cabinet Site Solutions

Overview
Tero Kemila
Product Manager,BTS Site Arch.& Electr.

November 24 , 2015

1 09/02/2017 © Nokia 2014


Confidential
Content of the FCOB Cabinet Site Solution
Content

1. FCOB cabinet main use cases


2. FCOB installation options
3. FCOB installation with system module and with 1 HU unit - example rectifier
4. FCOB summary

2 09/02/2017 © Nokia 2014


Confidential
FCOB Flexi outdoor cabinet - Compact
• FCOB provides aluminum alloy frame for Flexi installation outdoors.
• Provides IP55 protection for IP20 products inside of FCOB
• Operating environment temperature range: -40°C~45°C with solar
radiation
• 4U internal space
• Size (WxHxD): 600mm x 600 mm x 380mm (137 Liter)
• Weight 29kg
• Power distribution for interior equipments
• Installation options:
– Horizontal and vertical
– Pole/wall/floor and stand alone installations
– Stackable of horizontal installation
– Stackable with Flexi modules (Top or bottom of Flexi)
• The cabinet has the following functions:
– protection against external damage and foreign objects
– The FCOB provides earthquake protection for internal modules

473240A FCOB Flexi Cabinet Outdoor - Compact


3 09/02/2017 © Nokia 2014
Confidential
FCOB cabinet with closed doors

•FCOB maximum power consumption:


•Maximum 1.5kW power consumption

4 09/02/2017 © Nokia 2014


Confidential
FCOB cabinet details
Height 600mm
Width 380mm
Depth 600mm
Weight Max 29 kg without site bag,
(Site bag 9Kg)
Ingress Protection IP55
Operating Temperature -40°C - +45°C using full
capacity
Installation Temperature -20°C - +45°C
Airflow Direction Front side to back side,
Cold start ~2h from -40°C to -5°C
Nominal supply voltage -40.5 … -57 V DC
Input voltage range Extended Service Voltage
Range supported -36Vdc .. -
60Vdc Floating
Handle 2piecse included in site bag
for vertical installation
Volume 136.8L
Mass capacity Support Max 25Kg module
inside
Internal mechanical 19inch rack,
interface Height:4U(Maximum) *
350mm(Depth)

FCOB cabinet X11 with opened door

5 09/02/2017 © Nokia 2014


Confidential
System modules installed into FCOB

The maximum supported heat load is 1500W.

• 350mm depth is supported for 4U equipment


•400mm depth can be supported for 3U equipment

6 09/02/2017 © Nokia 2014


Confidential
System modules installed into FCOB

7 09/02/2017 © Nokia 2014


Confidential
Content of the FCOB Cabinet Site Solution
Content

1. FCOB cabinet main use cases


2. FCOB installation options
3. FCOB installation with system module and with 1 HU unit - example rectifier
4. FCOB summary

8 09/02/2017 © Nokia 2014


Confidential
FCOB installation on floor vertically and horizontally

9 09/02/2017 © Nokia 2014


Confidential
FCOB installation on pole and wall

(Installation also possible on the left side wall of FCOB)

10 09/02/2017 © Nokia 2014


Confidential
FCOB installation two pieces stacked in horizontal direction

11 09/02/2017 © Nokia 2014


Confidential
FCOB installation in horizontal direction with 3x Flexi modules with 3U casing
stacked on top

12 09/02/2017 © Nokia 2014


Confidential
FCOB with FSIH installed in horizontal and vertical direction

13 09/02/2017 © Nokia 2014


Confidential
FCOB with FSM4.0 ID installed: maintenance of internal and external fans

14 09/02/2017 © Nokia 2014


Confidential
Content of the FCOB Cabinet Site Solution
Content

1. FCOB cabinet main use cases


2. FCOB installation options
3. FCOB installation with system module and with 1 HU unit - example rectifier
4. FCOB summary

15 09/02/2017 © Nokia 2014


Confidential
Slotpack power solution installation FCOB
Nokia FCOB OD cabinet

• Complete 19-wide power solution


• Slotpack power output: 3x1,8kW = 5,4kW
• Battery connection: 1x80A
• Battery LVD as a default
• Smartpack S Controller as a default
• Applications:
48VDC power feed for FCOB (Nokia OD cabinet for FSM4)
Power system modernization cases

Contro Rectifi Batt. Load


ller ers dist. dist.

16 09/02/2017 © Nokia 2014


Confidential
Building blocks, Flatpack S 48V 1800W rectifier module introduction

• Wide AC input range

• High Efficiency rectifier module -> Efficiency: 95,7%


Save OPEX

• AirFlow direction: Back to Front

• One fan -> Less noisy solution

17 09/02/2017 © Nokia 2014


Confidential
Building blocks, Smartpack S Controller Unit Introduction

• Same front size, handle and locking mechanisms as the rectifier


• 6 x potential free alarm contacts
• 2 x LVD control
• Ethernet -> Remote monitoring via WEB
• 1x Fan control
• Genset charge/discharge function
• Li-Ion battery support via RS-485 interface:
- SAFT Li-Ion Evolion
- Fiamm Sonic
• Communication with Energy Meters

18 09/02/2017 © Nokia 2014


Confidential
Additional 1U DC-Distribution Introduction
• 19’’-mounted, Height: 1U, Depth:160mm deep
• Front access connections (4mm2) with rear cable
entry
• Load breaker qty: 12 pcs
Default Load Breakers: 2x30A, 2x20A, 2x15A. 4x10A, 2x5A
• Single feed DC-feed, interconnection cables from
Power Core to Distribution are included into BOM of
1U DC-Distribution

19 09/02/2017 © Nokia 2014


Confidential
Optional Kits
Kit: 2m Battery Cables Kit: AC SPD 3ph400Vac TN
• +/- cables for one battery string, black and blue color • AC Surge Protection Device assembled on a DIN rail
• 25sqmm / 2m lenght / M8 lugs • ~1,2m long cabling from SPD to AC terminals in Power
Core

20 09/02/2017 © Nokia 2014


Confidential
Content of the FCOB Cabinet Site Solution
Content

1. FCOB cabinet main use cases


2. FCOB installation options
3. FCOB installation with system module and with 1 HU unit - example rectifier
4. FCOB summary

21 09/02/2017 © Nokia 2014


Confidential
Cabinet Summary

FCOB cabinets can be used in a variety of applications:

Main target is to support installation of Flexi Indoor System


Module to outdoor environment. The application case need be
checked for product which will be installed in FCOB,

1U space to support FYGE&FYGG, Rectifier, Routers and other


3rd party units

The FCOB unit consists of mechanical parts:


•Cabinet
•External Fan assembly/ Internal Fan assembly(replaceable)
•PDU Box(replaceable)

22 09/02/2017 © Nokia 2014


Confidential
23 09/02/2017 © Nokia 2014
Confidential