COVER SERIES: Motors & Drives

4 Types of Enclosures for


Large Motors
Consider advantages and disadvantages for enclosures of
motors at 3,000 horsepower or higher.
JUNE 2021 REPRINT
DANIEL JEON, JAY PARK & HAMED TONEKABONI | TMEIC

Electric motors are considered one of the


main components of large pump systems
due to their percentage of the total system
The enclosure is one of the main
cost and their role in the entire pump
system’s reliability. When pump OEMs factors in determining motor frame size,
specify motors for a request for quotation
(RFQ), specifications such as the rated
which may impact the motor cost and
power, rated voltage/frequency and each the pump system design.
application’s speed range are generally
clearly indicated. However, additional
critical issues arise when choosing the
appropriate motor enclosure. review four major enclosure options mounted enclosure to cool the whole motor
First, the enclosure protects the motor (ODP, WPII, TEWAC and TEAAC) for large- body, including rotor and stator windings.
windings, a critical component, from and medium-size electric motors (3,000 Motor cooling is achieved by rotating
harmful contaminants in the outside horsepower [hp] or larger) and a guide interior fan blades radially installed on
environment like water, dust and high for selecting proper motor enclosure the shaft end(s), creating a slight pressure
temperature while efficiently cooling difference between the rotating blades’ two
types while considering cooling methods,
and reducing motor noise. It also sides, pulling cooler outside air into the
pros/cons, motor size, cost, reliability and
protects personnel from heat and high motor housing.
site environments.
noise generated by the motor. The The air intake side of the fan blades
Here are the essential things to consider is exposed to the outside air through the
enclosure is one of the main factors in
determining motor frame size, which when choosing enclosure types for large- enclosure’s embedded channels. The
may impact the motor cost and the pump and medium-size motors. discharge side of the fan blades forces
system design. fresh air into the motor. Main parts of the
Most users select motor enclosure motor’s internal structure like rotor, stator
types without considering the surrounding and windings are exposed to cooling air. The
environments or ambient conditions and moving air absorbs the generated heat and
with little understanding of each enclosure is directed to the discharge channel.
type’s advantages or disadvantages. Image 1 shows the path of the cooling
Proper selection of motor enclosures air. The air intake path (blue arrows) is
will benefit users with lower cost, higher drawn from the outside, and after absorbing
reliability and improved efficiency. the heat from internal parts (red arrows),
In contrast, improper choices can it is directed to the outside channels and
cause frequent downtimes, increased leaves the motor. The volume of the air that
motor repairs and additional and often enters the motor depends on motor speed
nonbudgeted maintenance costs. IMAGE 1: Open drip-proof enclosure and fan blade design.
When it comes to motor enclosures, (Images courtesy of TMEIC) Alternatively, an independent external
there are many options. National Electrical blower motor could be mounted on the
Manufacturers Association (NEMA) standard main motor enclosure to fulfill the cooling
Enclosure Types

1
MG1-2016 defines several different types air circulation requirement. This type is
of common motor enclosures but most ODP (Open Drip Proof, IC01, IP12) protected against dripping water that may
of them are cast frames for small motors Cooling method: The surrounding have up to a 15-degree angle from the
with limited rated power. This article will outside air is drawn into the motor top- vertical line and will not enter the motor.

1 PUMPS & SYSTEMS REPRINTED FROM JUNE 2021


COVER SERIES: Motors & Drives

Advantages: ODP enclosures are considered


the least expensive, simplest structures
among top-hat-type enclosures. Stators
enclosure’s air-inlet side force fresh air to
change direction while moving from inside
to outside. The airflow pathway encounters
3 TEWAC (Totally Enclosed Water
to Air Cooled, IC81W, IP54/56)
Cooling method: A TEWAC enclosure uses
and rotor windings are cooled by outside three 90-degree turns, reducing the the high heat absorption property of liquids
air, keeping the frame size relatively small. opportunity for water droplets and dust to for motor cooling. In this type of enclosure,
enter the motor. the internal circulating hot air passes
Disadvantages: The open enclosure design through dedicated air pathways designed
results in a high noise level compared to Advantages: The WPII enclosure is and embedded in the heat exchanger. The
other enclosure types. It is also difficult to designed for outdoor use. However, it is also heat exchanger is mounted on the motor
apply noise abatement techniques because suitable in a well-ventilated indoor location. body and has channels and tubes where
the noise from the internal shaft-mounted The footprint is relatively small, and the liquid can pass through without leaking
fans reaches the outside. This type is not structure is simple, like ODP. The cost is into the motor body. On the other side, the
applicable for Division 1 hazardous areas. slightly higher than an ODP enclosure cooling fluid such as freshwater or a glycol
but still less expensive than other totally mixture flows through heat exchanger
Possible problems and solutions: If an air enclosed types. tubes to remove heat from hot air that is
filter is not installed, insects and rodents continuously circulating inside the motor.
can easily enter the motor enclosure Disadvantages: Like an ODP enclosure, To effectively design the motor and its
through air openings and block the airflow. the high noise can be an issue. If used TEWAC cooling system, the end users
Air filters could become clogged by dust or in a dusty area, the filter can clog easily, need to provide essential data regarding
particles. Thus, air filters and differential causing the motor to trip. This type is not the proposed cooling liquid’s quality to be
pressure instruments are recommended. applicable for Division 1 areas. deployed in the cooling system and heat
Due to exposure to the surrounding air, exchanger. This enables manufacturers to
the internal parts are at risk of rusting Possible problems and solutions: Air filters offer the best economic and engineered
and corrosion. Proper primary painting is could become clogged by dust or particles. solution. Information regarding maximum
recommended, especially for the stator and Thus, air filters and differential pressure inlet liquid/water temperature and liquid/
rotor and internal frame. instruments are recommended. Due to water type are required.
exposure to the surrounding air, the internal
Recommendations: Recommend ODP for parts are at risk of rusting and corrosion. Advantages: This type of enclosure has the
clean and well-ventilated indoor areas Proper primary painting is recommended, best cooling efficiency and lowest noise
only. Not suitable for outdoor or corrosive/ especially for the stator and rotor and compared with other types of enclosures.
dust areas. internal frame. Noise reduction is easy to apply, and
large-capacity motors up to 30 megawatts
Recommendations: A WPII enclosure is (MW) for induction motors and up to 100
suitable for use in relatively clean and MW synchronous motors are available.
less-dusty outdoor areas. Also, it could be A TEWAC configuration is considered the
a reasonable substitute when cooling water most reliable option and suitable for use
is not available at the site. Please note that in dusty/dirty areas, indoor/outdoor and
a stainless steel washable air filter (90% of Division 1/Division 2 hazardous areas if
particles ≥ 10 microns) is recommended for properly designed.
this enclosure, and regular maintenance,
cleaning or filter replacement is necessary. Disadvantages: Capex/opex cost is the
highest among top-hat-type enclosures.
Cooling water is always required for a
TEWAC enclosure. A closed-loop cooling
system is an option when fresh cooling
IMAGE 2: Weather-protected Type II enclosure water is not available; however, the
additional cost adds up and cooling

2
efficiency can drop. Users should have a
WPII (Weather Protected Type II, water cooling system that maintains the
IC01, IP23/24) quality and inlet temperature of the
Cooling method: The cooling method cooling water.
is similar to ODP. However, WP II offers
better protection against external dust, Possible problems and solutions: Water
IMAGE 3: Totally enclosed water-to-air
water and objects. Baffles on the top-hat cooled enclosure leakage is a potential problem, so a water

2 PUMPS & SYSTEMS REPRINTED FROM JUNE 2021


COVER SERIES: Motors & Drives

leakage detector is recommended. A double is expensive and is not suitable for an It can be challenging to determine what
tube heat exchanger or redundant cooler is extremely large-capacity motor since the type of motor enclosure is the best for the
an available option to increase reliability. windings are not well cooled, particularly if driven equipment. Therefore, understanding
the motor is operating in a variable and low- the basic concepts, pros, cons and
Recommendations: A TEWAC design is speed application for a long period of time. recommendations of each enclosure type
the best option for large motors when the In that case, the chance of overheating will help users select the most efficient and
maximum ambient temperature is high and exists, which could damage the motor’s cost-effective enclosure for pump systems.
cooling water is available. It is best for use insulation and reduce the motor’s operating Getting familiar with motor standards
in a corrosive and dusty area and is suitable life. such as NEMA MG-1, International
Advantages: A TEAAC Electrotechnical Commission (IEC) and
enclosure does not American Petroleum Institute (API)
require cooling water at 541/547 is a good starting point to learn
the site. As the frame about basic motor requirements, including
is totally enclosed, this enclosure types and cooling methods.
option is suitable for Another good practice is to consult with
dusty /corrosive/humid/ motor experts to receive professional advice
salty areas. The noise and recommendations. By selecting the
abatement technique is best enclosure type, the motor is more
easy to apply. likely to achieve the designed motor life
cycle and simultaneously increase motor
Disadvantages: This performance and reliability.
enclosure’s frame size is
usually one or two sizes References
IMAGE 4: Totally enclosed air-to-air cooled enclosure
larger than TEWAC or WPII 1. NEMA MG-1 2016
when the other specs are 2. TMEIC MV Induction Motors 21-L Series
the same. The initial cost Catalog_2012
for Division 1/Division 2 hazardous areas is the highest, and there is some limit in the
when properly designed. rated power range. Noise level is higher than
  a TEWAC.

4 TEAAC (Totally Enclosed Air to


Air Cooled, IC611, IP54/56)
Cooling method: A TEAAC enclosure is
Possible problems and solutions: When
the noise level is too high, a noise absorber
Daniel Jeon is a senior sales application engineer
based in Houston, Texas, for TMEIC. He has more
than 15 years of experience in medium voltage
equipped with an external fan that blows is highly recommended, especially for electric motors and the VFD industry. Jeon holds
a Master’s of Science in industrial and systems
surrounding ambient air into the motor large high-speed motors. Windings are
engineer from Virginia Tech. He may be reached at
frame’s heat exchanger tubes. The motor not well-cooled for large motors, so one or daniel.jeon@tmeic.com.
heat exchanger is designed to efficiently two external blowers are needed for better
Jay Park is a sales applications engineer for medium
transfer internal motor heat to the cooling. voltage motors and drives at the TMEIC office in
surrounding air. Houston, Texas. Park received his bachelor’s degree
Internal motor sealed forced air is Recommendations: A TEAAC enclosure is in mechanical engineering at the University of Idaho
in 2010. Park may be reached at jay.park@tmeic.com.
circulated by internal fan(s) blades recommended when the maximum ambient
mounted on shaft end(s). If the rotor is temperature is not high and cooling water is Hamed Tonekaboni is a sales application engineer
not available at the site. A TEAAC is a good at TMEIC Canada corporation. He holds a master’s
rotating, shaft-mounted blades are also degree from Tabriz University and a bachelor’s degree
turning. This causes internal motor-sealed fit for on/offshore applications. It is not from Iran University of Science and Technology—both
hot air to continuously circulate and pass recommended for use in an extremely in electrical engineering. He may be reached at
hamed.tonekaboni@tmeic.com. For more information,
through heat exchanger tubes. The volume high ambient temperature and cooling
visit tmeic.com.
of sealed air circulated internally directly water is available. When choosing the best
corresponds to the motor rotor’s speed. enclosure type, there are many things © Copyright 2021 Cahaba Media Group,
The rotor’s higher speed results in a to consider in selecting proper motor Inc. All rights reserved. Permission granted
higher chance of exposure of internal hot enclosures. The factors to be investigated by publisher to TMEIC to reproduce and
air to the heat exchanger. Heat exchanger are based on users’ needs or site conditions distribute this excerpt in any medium
tubes play a key role in efficiently such as environmental circumstances, and on multiple occasions, provided that
transferring heat from motor internal hot hazardous environment requirements, water this copyright statement appears on the
air to external air. This enclosure type availability, etc. reproduced materials.