MAINTENANCE MANUAL AS532MK1

Fire extinguishing - Inspection / Check


602 Percussion head cartridges check - Extinguisher - Weighing
A. References
24-00-00-301 ................................. General instructions
26-00-00-301 ................................. General instructions
26-21-00-401 ................................. Extinguisher bottle (PRE MOD 0726050): "painted steel"
bottle Removal - Installation
26-21-00-402 ................................. Extinguisher bottle (POST MOD 0726050): stainless steel
bottle Removal - Installation
20-07-02-211 MTC
20-08-05-101 MTC
B. Special Tools

ICO 90.50.00.08.50 ...................... test set, Squib


or
Not listed in the ICO ..................... milliohmmeter
ICO 90.50.00.11.50 ...................... selector, Squib, Fire

C. Consumable Materials

None

D. Routine Replacement Parts


None

E. Cartridges check

(1) - Check that cartridge service life has not expired (see MSM).
- Check cartridge resistance.

THE CURRENT FLOWING THROUGH THE


CARTRIDGES MUST NOT EXCEED 45 mA

26-21-00-602 Page 601


2013.07.18
MAINTENANCE MANUAL AS532MK1

COMPLY WITH THE GENERAL INSTRUCTIONS


BEFORE PERFORMING ANY WORK:
- ON THE ELECTRICAL CIRCUIT, AS PER
24-00-00-301.
- ON THE FIRE PROTECTION SYSTEM, AS
PER 26-00-00-301.
- A PYROTECHNIC DEVICE, AS PER
20-07-02-211 MTC.
NO ELECTRICAL TEST IS PERMITTED DURING
THE PYROTECHNIC TEST.

(a) Using the test set

Connect test set, Squib [ ICO 90.50.00.08.50] cables and carry out tests as per the
following table :
1 Painted steel bottle (PRE MOD 0726050)

Cable No. Cartridge Termin. Extinguish. Resistance to Selector, Squib,


reference : be obtained Fire
(X)
34 three AC 0.29 ± 0.21 3
861.345 ABG SEMCA
bayonet-type BC Ohm 2
connectors
36 three screw- 1-3 0.29 ± 0.21 6
861.355 ABG SEMCA
type connectors 2-3 Ohm 5

2 Stainless steel bottle (POST MOD 0726050)

Cable No. Cartridge Termin. Extinguish. Resistance to Selector, Squib,


reference : be obtained Fire
(X)
34 three AC 3
863080-00 ABG SEMCA 0.85 ± 0.2 Ohm
bayonet-type BC 2
connectors
36 three screw- 1-3 6
863085-00 ABG SEMCA 0.85 ± 0.2 Ohm
type connectors 2-3 5

NOTE

For each measurement, hold the test set, Squib [


ICO 90.50.00.08.50] button for three seconds.

(b) Using the squib-testing milliohmmeter

Connect the milliohmmeter [ Not listed in the ICO] directly to cartridge. For the same
cartridge reference and same terminals, the values to be obtained are identical to

26-21-00-602 Page 602


2013.07.18
MAINTENANCE MANUAL AS532MK1

those given in table above. Disregard cable numbers and selector, Squib, Fire [ ICO
90.50.00.11.50] positions.

F. Extinguisher weighing

NOTE

1. Extinguisher is weighed with percussion heads


and frangible disc installed without protective
plug or electric firing cartridge.
2. The Manufacturer original weight is indicated on
the FM (log card).

(1) Carry out weighing.

(2) Make sure that the weight of the bottle does not differ by more than ± 20 grams from the
Manufacturer original weight indicated on the FM (log card).
(3) Replace the bottle if the weight is out of tolerance.

(4) mark the weighing date on the follow-up label.

(5) Check the overall condition of the bottle.


(6) See assembly of cartridge and installation of extinguisher (26-21-00-401 PRE MOD
0726050 or 26-21-00-402 POST MOD 0726050).

26-21-00-602 Page 603


END OF MODULE 2013.07.18
26-21-00-602 Page 604