Professional Documents
Culture Documents
SUN2000 65KTL M0 - Deratingcurve
SUN2000 65KTL M0 - Deratingcurve
SUN2000-65KTL-M0 (480Vac)
80
70
Output Power(kW)
60
50
40
30
20
10
0
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60
Ambient Temperature(℃)
120%
110% 110% 110% 110%
100%
90%
80% 80%
Pout/Prated
70%
60% 60%
50%
40%
30%
26%
20%
15%
10%
0%
0 100 200 300 400 500 600 700 800 900 1000
DC Input Voltage(V)
Note: The PV input voltage de-rating curve works under condition that PF=1.0.
DC Input
200 445 545 720 850 950 1000
Voltage (V)
Pout/Prated 26% 60% 110% 110% 110% 80% 15%
3. PQ Curve of SUN2000-65KTL-M0 @ 1.0 p.u. voltage (480Vac)
P(kW)
80
72 Un=1.0,1.1 PU
70
64.8
60
Un=0.9 PU
50
40
30
20
10
43.2 43.2
Qind 50 40 30 20 10 0 10 20 30 40 50 Qcap(kVar)
Note:
When SUN2000-65KTL-M0 is in the condition that it operates at rated and 1.1 rated output voltage,
it can output 72kW (when PF=1) or 72kVA at most.
When SUN2000-65KTL-M0 is in the condition that it operates at 0.9 rated output voltage, it can
output 64.8kW (when PF=1) or 64.8kVA at most.
1200
1100 1100 1100 1100
1000 1000 1000
Max. PV Input Voltage(Vdc)
900
870
800
740
700
600
500
400
300
200
100
0
0 1000 2000 3000 4000 5000 6000
Altitude(m)
Note:
SUN2000 inverter design safety distance in accordance with running at the altitude of 4000m and
below to avoid power de-rating. As altitude increases above 4000m, DC voltage de-rating of
SUN2000 should be taken into consideration and DC voltage drop in accordance with 13V/100m.
For SUN2000 inverter, the rated AC voltage will not be affected by the altitude.
60
50 50 50
Max. Working Temperature
44
at Rated Power(℃)
40
38
32
30
26
20
10
0
0 1000 2000 3000 4000 5000 6000
Altitude(m)
Note:
The maximum working temperature is the ambient temperature below which SUN2000 can output
rated power without de-rating.
When the altitude rises, the cooling capacity of the inverters de-rates. So the internal temperature of
inverters in the high altitude area will be higher and severer than that in the low altitude area.
When altitude > 2000m, the maximum working temperature of SUN2000 should de-rate by altitude,
and it de-rates in accordance with 6℃/1000m.