Isolator amplifier 4-channel with display

Isolator amplifier

Features Description
■ 4-channel 4 NAMUR sensors, optocouplers, mechanical
■ For NAMUR sensors DIN EN 60947-5-6 contacts or other operating elements can be
■ For mechanical contacts connected to the isolator amplifier in an
intrinsically safe way.
■ Galvanic isolation DIN EN 60079-11
The intrinsically safe inputs are safely galvanically
■ LED displays isolated from the supply voltage and the outputs
■ Ex ia, ib in accordance with DIN EN 60079-11. Open- and
■ Active transistor outputs short-circuits of the sensor lines are detected and
signaled via an additional transistor output as
■ Additional group fault signal output group fault signal. LEDs display the output states.
■ Standard or inverted

Dimensions/mounting positions Technical data


Construction
Clip-on enclosure for TH 35 rail
Enclosure material
High-quality thermoplastics
Protection class
Module IP 66/IEC 60529
Terminals IP 20/IEC 60529
Module width: 75 mm Terminals with cover IP 30/IEC 60529
Terminals
2.5 mm², fine stranded
Wiring diagram/terminal assignment
Mounting rail
TH 35 x 15 (7.5) DIN EN 60715
Terminal designation
written marking labels
Storage temperature
-40 °C to +60 °C
03-0330-0128/C-11/08-BAT-A127171

Ambient temperature
-20 °C to +50 °C
Weight
0.640 kg

144
Isolator amplifier 4-channel with display

■ Electrical data Displays


LED’s for all outputs
Supply voltage
DC 20 V to DC 30 V Line monitoring
always active, separate fault signal output
Power consumption
max. 580 mA Guidelines/norms/certifications
Directive 2004/108/EG
Power dissipation
Directive 94/9/EG
P V = max. 2.4 W
Galvanic isolation
Inputs//power supply, outputs
■ Input data
Voltage Explosion protection
U a = 8.2 V Ex protection type
Switching thresholds II 2(1)G Ex de [ia] IIC
open circuit < 0.26 mA Certification
damped < 1.2 mA PTB 97 ATEX 1068 U
undamped > 2.1 mA TÜV 97 ATEX 1211 X
short circuit > 7.4 mA
Installation
■ Output data Isolator amplifier 4-channel
Type 17-5521-4.../....
Transistor outputs U m = 253 V
output current channel max. 100 mA I 0 = 30 mA
signal level 1 - signal = Ub - 1 V U 0 = 11.55 V
0 - signal = 0.9 V P 0 = 86.4 mW
switching frequency 1.5 kHz

Notes
■ Observe the terminal assignment
■ Transistor output is not short-circuit proof
■ For open/short-circuit monitoring with contact call-up, use 1 kΩ/10 kΩ resistive coupling link;
Type 17-9Z62-0002

Status chart

Input B/S Out B/S Out B/S Out

damped 0 1 0 0 1 1

un-
damped 0 0 0 1 1 0

open
1 1 1 0 0 1
circuit
short
1 0 1 1 0 0
circuit
Code no. 12 22 32

Complete order no. 07-7311-97MT/BA


Please insert correct code.