You are on page 1of 15

Energy & Buildings 257 (2022) 111788

Contents lists available at ScienceDirect

Energy & Buildings


journal homepage: www.elsevier.com/locate/enb

The operational performance of net zero energy wooden structure


building in the severe cold zone: A case study in Hailar of China
Shenyang Ni, Neng Zhu ⇑, Zhiyuan Zhang, Yingzhen Hou, Siqi Li
School of Environmental Science and Engineering, Tianjin University, Tianjin 300350, China

a r t i c l e i n f o a b s t r a c t

Article history: At present, there is no lack of research on net zero energy buildings (nZEB) in China, and most of the
Received 2 July 2021 research on ‘‘nZEB” focuses on buildings using traditional building materials like rebar concrete, brick,
Revised 29 November 2021 etc. In this paper, we take a wooden structure residential building in the severe cold zone as the research
Accepted 14 December 2021
object, design a new type of water-passing wooden structure wall, and explore how to achieve net zero
Available online 17 December 2021
energy consumption through appropriate methods in the design stage. During the operation of the woo-
den structure building throughout the year, the solar photovoltaic (PV) system provides electricity to the
Keywords:
building. In the heating season, we will supply groundwater or shallow geothermal water into the water
Net zero energy consumption
Severe cold zone
pipes in the wall, and the solar thermal system provides hot water for heating. According to the whole
Wooden structure building year operation of the wooden structure building, the indoor environment meets the requirements of
Water-passing wall comfort standards, and the designed envelope structure of the wooden structure building has an excel-
Solar photovoltaic system lent thermal performance. The energy consumption was reduced by 62.9% compared with energy-saving
Energy criteria buildings without water-passing walls. The electricity generation capacity of the solar PV system is more
Economy than the actual electricity consumption of the building, the energy criteria are met the relevant require-
ments of the net zero energy building, and its economy is also evaluated.
Ó 2021 Published by Elsevier B.V.

1. Introduction and American countries, and the indoor environment was less
comfortable[6]. In developed countries, buildings consume 30%-
The current energy structure in China is still dominated by fossil 40% of primary energy each year, and in the United States, build-
energy; however, the burning of fossil energy can contribute to ings account for about 40% of primary energy consumption[7]. In
global warming and pollutant emissions. According to the statisti- the severe cold zone, the proportion of building energy consump-
cal bulletin of national economic and social development of China tion in primary energy is even more pronounced.
in 2020, the total energy consumption was 4.98 billion tons of In recent years, some concepts of energy-saving buildings like
standard coal, an increase of 2.2% over the previous year[1], the ‘‘ultra-low energy building”, ‘‘near zero energy building” and ‘‘net
building sector accounts for the majority proportion of the energy zero energy building” (‘‘nZEB”) have been proposed in turn to meet
consumption[2]. The total energy consumption in Hailar was 3.05 energy and carbon emission reduction targets[8]. The ‘‘ultra-low
million tons of standard coal, and its energy structure is dominated energy building” refers to a building that uses passive energy-
by raw coal (94.3%), supplemented by electricity (5.6%) and crude saving technology; it can significantly reduce the heating and cool-
oil (0.1%)[3]. In China, the energy consumed by buildings repre- ing loads of buildings, and improve the efficiency of energy sys-
sents approximately 28% of the nation’s total energy consumption; tems and facilities, and provide a comfortable indoor
still, the effective use of energy by buildings was insufficient; the environment with less energy consumption. The ‘‘near-zero energy
utilization rate is only 30%[4,5]. According to sampling statistics, building” is a building that uses renewable energy based on ultra-
compared with European and American countries with similar cli- low energy buildings; it can optimize the operation of the energy
matic conditions, only 4.3% of building energy consumption in system and provide a comfortable indoor environment with mini-
China was up to standard. The same heating area of residential mal energy consumption. The ‘‘net zero energy building” is a build-
buildings usually consumed 2–3 times more energy than European ing that generates energy is equal to its energy consumption over
some time, and the yearly energy supply from renewable energy is
greater than or equal to the building’s total energy consumption
⇑ Corresponding author. throughout the year[9]. In net zero energy buildings, reducing
E-mail address: nzhu@tju.edu.cn (N. Zhu). energy demand as much as possible, making full use of the renew-

https://doi.org/10.1016/j.enbuild.2021.111788
0378-7788/Ó 2021 Published by Elsevier B.V.
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

able energy of the building itself and its surroundings, and supply- stone[25]. According to the results of our on-site investigation,
ing the remaining energy demand by utilizing on-site renewable the walls of traditional buildings in Hailar are mainly made of con-
energy resources[10]. crete and bricks. Therefore, in this study, we take a wooden struc-
A lot of studies had been conducted to reduce the energy ture residential building in Hailar as the research object, design a
demand of the building around the world, including optimizing new type of water-passing wooden structure wall, and explore
building orientation and shape, using high-performance envelope how to achieve net zero energy consumption through appropriate
structure[11–13], and adopting high efficient heating, ventilation, methods in the design stage. The main research is as follows:
and air-conditioning (HVAC) facilities[14–22], etc. The most
important of these is to reduce the heat transfer through the envel- (1) According to the annual energy simulation results, a solar PV
ope structure of the building[23]. Therefore, the selection of mate- system has been designed and installed on the building.
rial for the building envelope is significant. At present, the Then the electricity generation of the solar PV system is sim-
materials used in the building envelope structure are mainly rebar ulated to determine whether the electricity generated can
concrete, brick, stone, and wood. And the common walls are con- meet the needs of the building.
crete walls, brick walls, and stone walls[24], but the wooden struc- (2) We studied the performance of a new water-passing wall.
ture walls have gradually been adopted in recent years. In China, (3) We evaluated the wooden structure building’s energy crite-
wooden structure building was developed thousands of years ago ria and calculated the economy of ‘‘nZEB”.
and has already entered the stage of modern light wooden struc-
ture from the traditional heavy wooden structure building[25]. 2. Methodology
Compared with buildings made of other materials, the light woo-
den structure building has many distinct advantages: (1) Raw 2.1. Energy simulation
materials were renewable; (2) Superior performance of insulation
and energy-saving; (3) The design was more flexible, and the ren- At the design stage, building energy simulation is often con-
ovation was convenient; (4) Excellent performance of fire resis- ducted to determine ways for achieving net zero energy consump-
tance, that can be comparable to concrete materials buildings; tion. The energy consumption of the preliminary design building
(5) The period of construction was short and had less environmen- was simulated by EnergyPlus software. The annual energy con-
tal pollution; (6) Superior performance of seismic performance sumption can be calculated dynamically according to various
[26–29]. parameters, such as meteorological parameters, the composition
Multiple technologies are utilized in the buildings in the severe of the envelope structure, building shape, ventilation mode, form
cold zone to pursue net zero energy consumption. The adoption of energy systems, occupant’s behaviors, lighting, equipment, etc.
rate of active technologies in the United States (US) and the Euro- During the simulation, it is assumed that the wooden structure
pean Union (EU) is higher than in passive technologies; in contrast, building model is designed and operated under standard condi-
the situation in China is the opposite. In the use of renewable tions; therefore, in selecting relevant parameters in the process
energy, the EU and China allow on-site renewable energy or nearby of building design and modeling, we refer to the results of on-
to offset on-site use. Still, except for utilization on-site and nearby site investigation and relevant national standards of China. How-
renewable energy, the US also allows the purchase of renewable ever, this simulation has some limitations; in the actual operating
energy[30]. At present, the technologies for achieving net zero of the building system, each occupant has a different behavior pat-
energy consumption, including utilization technology of solar PV tern, which can cause some gaps between the actual operating
[31], thermal storage technology[32], thermoelectric technology results and the simulation results. Although it has certain limita-
[33], reverse charging technology of electric vehicle[34], and tions, it provides theoretical support for our subsequent construc-
advanced technology of HVAC system[35], etc. Renewable energy tion and in-depth study of net zero energy wooden structure
plays an essential role in achieving net zero energy consumption; buildings in the severe cold area.
renewable energy includes solar photovoltaic (PV), wind power, Due to EnergyPlus software using a thermal balance model, the
geothermal energy, and biomass energy[36]. The building- thermal state of the thermal zone can be obtained by solving the
integrated PV system has been developed rapidly in the past ten thermal balance equations of indoor air, internal and external
years; compared to solar power accessibility and easy integration walls, roofs, and floors. The thermal balance equation includes
with existing building systems, the intermittent nature of wind the unsteady heat transfer through the envelope structure and
energy has restricted its comprehensive implementation[37]. the outdoor meteorological parameters. The variation of outdoor
China has a vast territory and complex terrain; due to the differ- meteorological parameters also affects the temperature field vari-
ent geographical latitudes, topography, and other conditions, the ation of the building envelope. Therefore, in the process of model-
climate varies significantly from place to place. Therefore, different ing the wooden structure building, the temperature field was
areas have different energy-saving designs on buildings. According mainly considered. The indoor and outdoor boundary conditions
to different climatic conditions, China is divided into five thermal are as follows: the air temperature near the internal and external
climate zones: severe cold zone, cold zone, hot summer and cold surfaces of the envelope structure, and the surface heat transfer
winter zone, hot summer and warm winter zone, and moderate coefficient between the air and internal and external surfaces of
zone. The population distribution on these thermal climate zones the envelope structure are known. According to Chinese design
is 11.1%, 31%, 41.3%, 11.9%, and 4.7%, respectively (see Fig. 1)[38]. code for heating ventilation and air conditioning of civil building,
In the severe cold zone, winter takes a long time of the year, and in this simulation, the indoor design temperature in winter is
the outdoor temperature is lower, which can reach 40 ℃; the Chi- 22℃, and the indoor design temperature in summer is 26℃.
nese standard on building envelope in this zone is far from the
requirements of ‘‘nZEB”. According to statistics, ‘‘nZEB” in severe 2.1.1. Design standards and principles of building
cold zone of China contribute 10% of the total national ‘‘nZEB” In order to achieve net zero energy consumption, wooden struc-
number[39]. Therefore, whether ‘‘nZEB” can be achieved in the sev- ture buildings need to make full use of the renewable energy of the
ere cold zone, it’s of great significance to promoting and imple- building itself. Generally speaking, solar energy utilization equip-
menting zero energy buildings in China. ment is mainly placed on the roof of the building; therefore, it is
Most existing studies on ‘‘nZEB” focus on buildings in China necessary to consider the areas and form of the building roof at
using traditional building materials like rebar concrete, brick, and the design stage. According to related standards of China, to max-
2
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

Fig. 1. The climate zones of China.

imize the use of solar energy and protect the walls of wooden refer to the living room, toilets and other auxiliary rooms on the
structure buildings, the roof of prefabricated wooden structure first floor, bedroom, toilets and other auxiliary rooms on the sec-
building should adopt slope roof, the roof slope should be 1:3– ond floor, respectively.
1:4, and overhanging eaves should be set around the eaves[40].
When the solar thermal system and solar PV system were installed 2.1.3. Location and climate
on the building, the sunlight standard of the building shall not be The building in this study is located in the pastoral area of Hai-
reduced[41]. lar District, Hulunbuir City, Inner Mongolia Autonomous Region,
When designing the wooden structure building, it should be China, in the northeast of Inner Mongolia (longitude: 119.75°E; lat-
considered that the building shape, size, window-to-wall area itude: 49.6°N) (Fig. 1). The climate zone is the severe cold zone
ratio, and shape coefficient. The shape coefficient of the building (1A); it takes a long time in winter, and the climate is cold. There-
refers to the ratio of the external surface area to the volume of fore, the living conditions of herders cannot meet the requirement
the building. The standard limits of building shape coefficient of comfortable. According to historical meteorological data from
and window-wall area ratio in severe cold areas are shown in China Meteorological Administration, the outdoor maximum dry-
Table1. In this study, the building’s slope of the roof is set to 1:4, bulb temperature for summer in Hailar is 30.1℃, the average
with overhanging eaves on all sides. The window-wall ratio in each dry-bulb temperature is 20.6℃, and the average wind speed was
direction and shape coefficient of the building are shown in Table1. 4.2 m/s, the hottest month was July. The lowest outdoor dry-bulb
temperature for winter is 35.1℃, the average dry-bulb tempera-
ture is 24.2 ℃, and the average wind speed is 1.6 m/s; the coldest
2.1.2. Building models
month is January. Fig. 3 shows the monthly average dry-bulb tem-
According to our preliminary literature research and on-site
perature, relative humidity, and wind speed of ambient air in
investigation, and combined with economic benefits, the pastoral
Hailar.
area of Hailar can adopt the following two forms of light wooden
structure buildings: (1) prefabricated two-story modular building
with a building area of about 100 m2; (2) movable small single- 2.1.4. Internal gain
story building with a building area of 20–30 m2. The mainly internal heat source in this wooden structure build-
This study uses prefabricated two-story light wooden structure ing are occupants, lighting, and indoor equipment. According to the
buildings as a base-case model to study net zero energy consump- functions of different thermal zones and actual usage habits of res-
tion. The information of the wooden structure building was as fol- idents, occupant density, lighting density, and equipment density
lows: two-story residential building with 112 m2, and height of are designed (shown in Table2). The running schedule of the main
each floor is 2.8 m (see Fig. 2 (a)). According to the function of dif- indoor equipment is shown in Table3.
ferent rooms in the building, we divide the rooms with similar
requirements for the indoor environment into the same thermal 2.2. Energy criteria
zone. This wooden structure building was divided into four ther-
mal zones (see Fig. 2 (b)), from thermal zone 1 to thermal zone 4 The energy criteria is a crucial indicator that used to evaluate
whether a building has achieved net zero energy consumption; it
includes: (1) the comprehensive value of building energy con-
Table 1
sumption; (2) the utilization rate of renewable energy; (3) the per-
Prefabricated two-story building’s shape coefficient and window-wall ratio.
formance index of building itself[42]. In the energy criteria, the
Parameters Calculated Standard limit[42] residential buildings mainly consume electricity; the scope of
Shape coefficient 0.427 0.55 (floor  3) energy consumption includes heating, ventilation, air conditioning,
Window-wall ratio South:0.24; North:0.17 South:0.45; North:0.25 lighting, domestic hot water, and elevator system. The standard
East:0.05; West:0.07 East:0.3; West:0.3
limits of energy criteria are shown in Table4; these three indicators
3
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

Fig. 2. Physical model and thermal zone of wooden structure building.

Table 3
Running schedule of People lighting and indoor equipment.

Internal heat source Thermal zone Schedule


Lighting Thermal zone1 6:00–8:00, 18:00–22:00.
Thermal zone2 6:00–22:00.
Thermal zone3 6:00–8:00, 21:00–23:00.
Thermal zone4 6:00–22:00.
Equipment Thermal zone1 7:00–22:00.
Thermal zone3 7:00–9:00, 21:00–23:00.
People Thermal zone1 7:00–22:00.
Thermal zone2 6:00–22:00
Thermal zone3 0:00–9:00, 21:00–24:00.
Thermal zone4 6:00–22:00

Table 4
The limits of energy criteria of net zero energy consumption residential buildings in
the severe cold zone[42].

Comprehensive value of building energy consumption KWh/(m2a) 55


Performance index of Yearly heat consumption for heating 18
building itself KWh/(m2a)
Air-tightness of the building (air 0.6
circulation ratio N50)
Utilization rate of renewable energy 10%

per unit area of HVAC, lighting, domestic hot water, and the elec-
tricity generation of the renewable energy system. It reflects the
building’s consumption of fossil energy and its impact on the envi-
ronment. It can be calculated by Eq. (1). The ‘‘performance index of
the building itself” refers to the energy efficiency improvement
requirements of the building envelope and energy system, except
for the utilization of renewable energy to generate electricity.
Fig. 3. The monthly average dry-bulb temperature, relative humidity, and wind The ‘‘yearly heat consumption for heating”, the ‘‘yearly cold con-
speed of ambient air in Hailar. sumption for cooling”, and the ‘‘airtightness of the building” are
used as constraint indicators for residential buildings. The renew-
need to meet standard limits simultaneously so that the building able energy utilization rate can be calculated by Eq. (2). [42]
can achieve net zero energy consumption. In the calculation, it is P P
necessary to convert the energy consumption and renewable Er;i  f i þ Erd;i  f i
E ¼ EE  ð1Þ
energy generation into standard coal equivalent. A
The ‘‘comprehensive value of building energy consumption”
P P
refers to the difference between the annual energy consumption EP h þ EP c þ EP w þ Er;i  f i þ Erd;i  f i
REP P ¼ ð2Þ
Q h þ Q c þ Q w þ El  f i þ Ee  f i
Table 2 Here: E is the comprehensive value of building energy consumption,
Interior heat of wooden structure building[42].
KWh/(m2a); EE is the comprehensive value of building energy con-
Thermal zone Occupant Lighting power Equipment power sumption excluding renewable energy power generation, KWh/
density (p/m2) density (W/m2) density (W/m2) (m2a), it can be calculated by Eq. (3); Er;i is annual electricity gen-
Thermal zone1 0.03 6 7.5 eration of renewable energy by the building itself, KWh; Erd;i is
Thermal zone2 0 6 0 annual electricity generation of renewable energy around the build-
Thermal zone3 0.03 6 6
ing, KWh; f i is energy conversion coefficient, it refers to the coeffi-
Thermal zone4 0 6 0
cient that converts energy consumption and renewable energy
4
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

generation into standard coal equivalent; A is the usable area of res- active layer of the envelope. It is necessary to prevent the water
idential buildings m2; REP P is renewable energy utilization rate, %; pipeline from freezing in winter; the water pipes are generally
EPh is renewable energy utilization of the heating system, KWh; pre-embedded in the middle of the wall or the wall near the indoor
EPc is renewable energy utilization of the cooling system, KWh; side. The water pipes were pre-embedded in the building envelope
EPw is renewable energy utilization of domestic hot water system, is also a way to reduce the building energy consumption. This
KWh; Er;i is annual electricity generation of renewable energy by water-passing wall is a new type of building envelope that the
the building itself, KWh; Erd;i is annual electricity generation of water pipes that were pre-embedded in the wall, and the circulat-
renewable energy around the building, KWh; Q h is annual heat ing water in the water pipes were used for heat transfer. This struc-
consumption of the heating system, KWh; Q c is annual cold con- ture is similar to a radiant heating/cooling system; it can
sumption of the cooling system, KWh; Q w is annual heat consump- effectively utilize low taste energy to reduce the impact of outdoor
tion of domestic hot water system, KWh; El is the annual energy climate on the indoor environment, thereby reducing building
consumption of lighting system, KWh; Ee is the annual energy con- energy consumption and improving indoor comfortable[43–55].
sumption of the elevator system, KWh. [42] The materials’ thermal performance of each layer is shown in
Table5-7. The heat transfer coefficient (U-value) of the exterior
Eh  f i þ Ec  f i þ E l  f i þ Ew  f i þ Ee  f i wall, roof, and the ground floor was calculated by Eq. (4).
EE ¼ ð3Þ
A
1
Here: Eh is the annual energy consumption of the heating system, k¼ ð4Þ
1
þ dk þ h12
KWh; Ec is the annual energy consumption of the cooling system, h1

KWh; Ew is the annual energy consumption of domestic hot water


system, KWh. Here: k is heat transfer coefficient, W/(m2K); h1 is heat transfer
coefficient of the internal surface, W/(m2K); h2 is heat transfer coef-
ficient of the external surface, W/(m2K); d is thickness, m; k is ther-
3. System description mal conductivity, W/(mK);
According to the calculation, the U-value of the exterior wall,
To achieve net zero energy consumption, the most important roof, and the ground floor is 0.085 W/(m2K), 0.113 W/(m2K),
thing is to reduce the terminal energy consumption of the building, and 0.077 W/(m2K), respectively. Exterior windows are made of
both passive and active design methods were taken into consider- plastic steel and three-layer of 5 mm glazed glass, and a low-E
ation. EnergyPlus simulated the annual energy consumption of the metal film is plated on the internal and external layer glass, the
wooden structure building in Hailar. According to the simulation cavity of glass is filled with 12 mm argon, the structure of the exte-
results of energy consumption, a solar PV system was selected to rior window is shown in Fig. 8. The U-value is 0.911 W/(m2K), the
balance the annual energy consumption and annual electricity value of solar heat gain coefficient (SHGC) is 0.279. The heat trans-
generation of the wooden structure building. Thereby, provides fer coefficient of the envelope and the window of the wooden
conditions for wooden structure buildings to achieve net zero structure building is significantly lower than the relevant national
energy consumption. standards[42] (see Table8).

3.1. High-performance envelope structure 3.2. Water-passing wall system

SIP panels were used in the exterior walls, roof, and ground The water pipes in the wall are composed of a series of elbow
floor in the small light wooden structure building. The SIP panels pipes and straight pipes. The elbow pipes are inverted S-shaped
are composed of two layers of OSB panels, and the interior is filled heating pipes with antiseptic treatment; the straight pipes also
with insulation materials such as polyurethane (Fig. 4). This struc- adopt heating pipes, the outer diameter of pipes, the thickness of
ture can realize the modularization of wooden structure building pipe wall, and the center distance between the pipes is 20 mm,
and reduce the amount of wood used. 2 mm, 46 mm, respectively. Pipe clamps and screws fix the water
The exterior wall, roof, and ground floor structure are shown in pipes, and iron sheets to keep the spacing of the pipes from defor-
Figs. 5-7; the water pipes were pre-embedded in the wall as an mation (see Fig. 9). It is connected to the water supply pipes and
return pipes with a splitter and water mixer. The water supply
pipes and return pipes adopt PE pipes, the outer diameter of the
water supply pipes and return pipes is 40 mm, and the thickness
of the pipe wall is 4 mm. The water pump is installed on the water
supply pipeline, the source of the supply water is groundwater or

Fig. 4. The structure of SIP panels. Fig. 5. Structure of the exterior wall.

5
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

Table 7
Thermal performance of main material of the ground floor.

Material Thickness Heat conductivity W/ Density Kg/


mm (mK) m3
wood 19 0.115 800
subfloor
Waterproof 2 0.17 600
OSB panel 12 0.105 593
Polyurethane 160 0.024 35
OSB panel 12 0.105 593
Air gap 150 – 1.29
Concrete 40 0.129 2240

Fig. 6. Structure of the roof.

Fig. 8. Structure of the exterior window.

Table 8
The heat transfer coefficient of the envelope and window of the wooden structure
building.

Structure U-value W/(m2K) Standard limit[42] W/(m2K)


Fig. 7. Structure of the ground floor.
Exterior wall 0.085 0.1~0.15
Roof 0.113 0.1~0.15
Ground floor 0.077 0.15~0.3
Table 5 Exterior window 0.911 1
Thermal performance of main material of the exterior wall.

Material Thickness Heat conductivity W/ Density Kg/


mm (mK) m3 shallow geothermal water, and the water pipes in each direction
Gypsum 12 0.16 800 wall are separate loops (see Fig. 10).
board A circulating pump with variable frequency and constant pres-
Air gap 40 – 1.29
sure was selected; its lift, flow rate, and power are 8 m, 4.8 m3/h,
OSB panel 12 0.105 593
Polyurethane 160 0.024 35 and 165 W, respectively. According to the literature, the tempera-
OSB panel 12 0.105 593 ture of groundwater in the northeastern part of Inner Mongolia is
XPS panel 100 0.036 50 about 10℃. Therefore, the supply water temperature is 10℃, the
Waterproof 2 0.17 600 water velocity is 0.5 m/s, and the time of supply water is from Jan-
Softwood 40 0.129 496
uary 1st to March 31st and November 1st to December 31st.

3.3. Measurement of water-passing wall thermal performance


Table 6
Thermal performance of main material of the roof.
In order to study the actual heat transfer effect of water-passing
Material Thickness Heat conductivity W/ Density Kg/ wooden structure walls in the severe cold zone, and verify the cor-
mm (mK) m3
rectness of the simulation result of the wooden structure building,
Gypsum board 12 0.16 800 we need to carry out relevant actual measurements. In the actual
OSB panel 12 0.105 593 measurement process, it is too difficult to build a full-scale build-
Polyurethane 160 0.024 35
OSB panel 12 0.105 593
ing, therefore, we conducted measurement on the water-passing
XPS panel 50 0.036 50 wooden structure wall in a cold and hot box apparatus, as shown
Waterproof 2 0.17 600 in Fig. 11. We mainly measured the temperature of the internal
Asphalt 3 0.04 1120 and external surface of the water-passing wall, and the heat flux
shingle
through the water-passing wall.
6
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

Fig. 9. Laying form of water pipes in the wall.

Fig. 10. Schematic of water inlet and outlet of water-passing wall.

The temperature and heat flux in the cold box are measured lower than the indoor temperature; we are opening windows
using an automatic temperature monitoring system. The system for ventilation, the air circulation ratio is 10 times/hour. This is
consists of 14 K-type thermocouples, heat flow sheets of the data an effective way to reduce indoor cooling load and heating load;
collector, and heat flux and temperature itinerant detector. The at this time, we stop supplying water to the wall. In the heating
models, function, and accuracy of experimental equipment are seasons, the window is closed, the air circulation ratio is 0.5
shown in Table9. The system acquisition uncertainties of the tem- times/hour.
perature and heat flux itinerant detector are that: the temperature
is less than ± 0.3℃, and the heat flux is less than 0.2% of the dis- 3.5. Renewable energy system
played value. The 14 thermocouples are arranged according to
the location of the measuring points in Fig. 12. The form of the Considering the availability of renewable energies in this study,
water-passing wooden structure wall during construction and the most suitable system for this wooden structure building was
after completion is shown in Fig. 12(a and b), respectively. solar PV and solar thermal system. Therefore, various parameters
During the experiment, the data to be measured include the of the solar PV system were tested, such as current, voltage, elec-
heat flux through the water-passing wooden structure wall, the tricity generated, and electricity consumption. Other parameters
temperature of the internal and external surface of the wall, and were also introduced, such as selecting the size and number of
the temperature of each layer inside the wall. PV panels, the generation of direct current, and the selection of
inverters. For the solar thermal system, the size and number of
3.4. Natural ventilation solar collectors, the outlet water temperature, and heat storage
temperature were introduced
Natural ventilation is also adopted in this wooden structure
building to reduce the power consumption of water pumps that 3.5.1. Solar thermal system
supply water to the wall and improve indoor comfort. During The solar thermal system of the wooden structure building con-
the transition seasons and summer, the outdoor temperature is sists of four solar collectors with a vacuum tube, heat storage
7
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

Fig. 11. Schematic diagram of cold box heat flow meter method.

Table 9 Table 10
The model and function of experimental equipment. Performance of solar collector.

Name Model Function Accuracy Name Unit Performance parameters


Cold box BC/ Provide a cold environment ±0.5% Size mm 18502000
BD252DNE Module efficiency % 85
Thermocouple TT-K-30- Measure the temperature of ±0.4%
SLE the internal and external
surface of the wall and its inner
temperature the solar thermal storage system is 45–49 ℃. It can provide 45 ℃
Heat flux sheet MX100 Measure the heat flux of the 0.001 mV of hot water to the wooden structure building, the part of the
wall hot water is directly used as domestic hot water for the occupant,
Temperature SR70B Read the temperature and heat ±0.1℃
and the other part hot water is mixed with tap water to 35 ℃ for
and heat flux flux on the internal and 0.001 mV
itinerant external surfaces of the wall heating.
detector

3.5.2. Solar PV system


The solar PV system was employed for electricity generation;
device, domestic hot water device, heating system, and circulating the generated electricity was used for lighting systems, indoor
pump. Solar thermal water as a heat source for heating. During the equipment, heating system, water-passing wall system, and other
heating season in Hailar, the amount of solar radiation is systems in the wooden structure building. The surplus electricity
0.793 MWh/m2[56], the total installed area of the solar collector is stored in the storage battery. When the electricity generated
is 14.8 m2, the performance of the solar collector is shown in by the solar photovoltaic system cannot meet the electricity
Table10. In Hailar, the temperature of hot water produced by solar demand of the building, the electricity stored in the storage battery
collectors in winter is 65 ℃, the hot water produced by the solar will be used. The schematic diagram of the system is shown in
thermal system stored in the hot water tank for building use, Fig. 13. According to the energy simulation results, we selected
and the thermal in the surplus hot water was stored in the phase the solar PV system of the wooden structure building. Considering
change material through the phase change device. When the the other electricity usage in the building, the electricity genera-
amount of hot water generated by the solar collector is insufficient, tion of solar PV systems should be about 20% higher than the elec-
the heat stored in the phase change material can release to provide tricity consumption of the building. The yearly total radiant
hot water for the building by heat exchange. The paraffin wax was intensity of solar energy in Hailar was 1.69 MWh/m2[56]. The
selected as a phase change material in the phase change device; solar PV system of the building is composed of five PV panels with
the phase change temperature of the phase change materials in monocrystalline silicon, solar charge controllers, inverters, batter-

Fig. 12. Schematic diagram of water-passing wall construction.

8
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

It can be seen from the measurement results, the temperature


of the internal surface of the wall is much higher than the temper-
ature of the external surface. Therefore, this water-passing wooden
structure wall has good thermal performance. In addition, the mea-
suring points 5, 6, 7, and 8 are located on both sides of the water
pipe layer of the wooden structure wall, according to the measure-
ment results, the average temperature of the water pipe layer
about 9 °C, so the water pipe will not freeze during the experiment.
To verify the reliability of the simulation results, we set the tem-
perature of the cold box to 25 °C and compared the experimental
results with the simulation results at this temperature. The results
are shown in Fig. 14 and Fig. 15. As can be seen from the figure that
the temperature distribution curve obtained by the simulation is
fitting well with the experimental measurements, and the changing
trend of the heat flux is also consistent. In the experiment, due to
the edge of the wooden structure wall is not completely insulated,
it can cause the part of the heat to be exchanged with the air
through the edge of the wall, which makes the experimentally mea-
Fig. 13. Schematic of solar PV power generation system. sured value of heat flux and temperature lower than the simulated
value. After comparative analysis, the errors of temperature and
ies, and pipelines; the performance of solar PV panels and inverters heat flux are both within 10%, so the simulation results have good
are shown in Table11. The total installed area of the PV panel was reliability in the research of this paper.
8.15 m2.
4.2. Influencing factors of indoor thermal comfort
3.6. Heating system
4.2.1. Water-passing wall
Hailar is located in the severe cold zone, with short and com- When water pipes are embedded in different positions in the
fortable summers; therefore, the wooden structure buildings only wall, the function of the water-passing wall may be different.
need to consider the heating system. The heating system adopts Therefore, in this section, we studied the influence on the indoor
a radiant floor system; the circulating pump with variable fre- thermal environment when water pipes are pre-embedded in dif-
quency constant pressure was selected, the lift, flow rate, and ferent positions on the wall. The result is shown in Table13 and
power of the heating pump are 8 m, 4.8 m3/h, and 165 W, respec- Fig. 16.
tively. The layout form of the heating coil in the floor is similar to When the water pipes are pre-embedded in the internal side of
the embedded pipe in the wall; the outer diameter of pipes, the the wall, the annual average indoor temperature of all thermal
thickness of the pipe wall, and the center distance between the zones in the building is approximately 10 ℃, the surface tempera-
pipes are 20 mm, 2 mm, and 150 mm, respectively. The outer ture of the indoor wall is also about 10 ℃. In this situation, the
diameter of the water supply pipes and return pipes is 40 mm, water-passing wall is similar to a radiant cooling/heating system,
and the thickness of the pipe wall is 4 mm. The temperature of the wall temperature is low, and it will inevitably cause a cold sen-
the supply water is 35℃, and the water velocity is 0.5 m/s. The sation of indoor occupants. When the water pipes are pre-
heating time in Hailar is from January 1st to April 30th and October embedded in the middle of the wall, the average indoor tempera-
1st to December 31st each year. ture of all thermal zones in the building is significantly higher than
the outdoor temperature in winter. In this situation, the water-
4. Results and discussion passing wall plays the role of isolating the outdoor cold.
Since the heat of the water in embedded pipes in the middle of
4.1. Analysis of measurement results the wall is mainly used to isolate the outdoor cold, only a small
part of the heat is used to increase the indoor temperature, and
The temperature in the cold box will affect the heat flux of the the heat of the water in embedded pipes in the inner side of the
internal and external surfaces of the wooden structure wall and the wall is mainly used to raise the indoor temperature. Therefore, in
temperature distribution of each layer in the wall. Therefore, in winter, the water pipes are pre-embedded in the middle of the
this experiment, the temperature of the cold box is set to 35℃, wall, the indoor average temperatures are less favorable than those
30℃, 25℃ and 15℃, respectively. Under these four conditions, obtained with the pre-embedded pipes in the inner side of the wall
the thermal performance of the water-passing wooden structure (see Fig. 16). The annual average indoor temperature of all thermal
wall was studied, and the temperature of each measuring point zones is higher than the average indoor temperature with an
is shown in Table12. embedded pipe in the wall near the indoor side (see Table13).
The annual energy consumption of the water-passing wall sys-
Table 11
Performance of solar PV panel and inverters. tem in the two forms are 362.69KWh and 383.47KWh, respec-
tively. Therefore, considering energy consumption and indoor
PV equipment Name Unit Performance
thermal comfort, the best position for the embedded pipes in the
parameters
middle of the wall. The water-passing walls mentioned in the fol-
Monocrystalline Size mm 1640  992  40
lowing articles are all of this form.
silicon PV panels Rate power W 300
Operating voltage V 24 Due to the doors and windows of the wooden structure building
Module efficiency % 18 being closed, there was no ventilation inside the building, and
Inverters Rate power W 3000 there were internal heat sources. When there was no water supply
Peak power W 9000 to the embedded pipes in the wall, the monthly average tempera-
Operating voltage V 24
ture of each thermal zone in the building is higher than the out-
Module efficiency % 93
door temperature (see Fig. 16). This shows that the envelope of
9
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

Table 12
The temperature and heat flux value at different cold side temperatures.

Temperature (℃) Temperature of the cold box (℃)


35 30 25 15
Measuring point 1 13.2 13.3 13.4 13.6
Measuring point 2 13.4 13.5 13.3 13.7
Measuring point 3 12.7 12.5 12.7 12.5
Measuring point 4 12.8 12.7 12.6 12.6
Measuring point 5 9.1 9.4 9.4 9.7
Measuring point 6 9.0 9.2 9.5 9.8
Measuring point 7 8.6 9.1 9.3 9.6
Measuring point 8 8.7 8.9 9.2 9.5
Measuring point 9 29.2 –22.9 19.4 10.2
Measuring point 10 29.4 –23.1 19.3 10.3
Measuring point 11 –33.3 27.9 –23.1 13.4
Measuring point 12 –33.4 28.1 –23.4 13.6
Heat flux value (W/m2) 4.95 4.39 4.12 2.88

Table 13
Annual average indoor temperature of each thermal zone.

Thermal zone When the water supply When the water supply
to the embedded pipe in to the embedded pipe in the
the middle of the wall (℃) wall near the indoor side (℃)
Thermal zone1 14.8 11.66
Thermal zone2 13.3 10.64
Thermal zone3 12.7 10.82
Thermal zone4 12.15 10.4

supplying water to the wall and open the windows for ventilation
to ensure indoor thermal comfort.

4.2.2. Natural ventilation


As described in the previous section, we can consider opening
the windows for ventilation in summer to reduce the indoor tem-
perature. From Fig. 16, we found that the indoor monthly average
temperature in May and September are 21.08℃ and 22.73℃,
Fig. 14. Comparison of simulated and experimental values of wall surface respectively (take the thermal zone3 as an example). Although
temperature. the indoor temperature is higher than the outdoor temperature,
the temperature also meets the thermal comfort standard. There-
fore, the time to open the windows is from June 1st to August
31st. The result is shown in Fig. 17.
There are noticeable changes in indoor temperature before and
after opening the windows for ventilation; the temperature
descending range is about 10 ℃, and the occupant feels more com-
fortable. Therefore, there is no need to provide cooling in summer,
saving part of the energy consumption. After ventilation, we
stopped supplying water to the embedded pipes in the wall; it
can also save part of pump power consumption.

4.2.3. Heating system


After supplying water to the embedded pipes in the wooden
structure wall, the indoor temperature in winter was still not meet
the heating standards; this wooden structure building needs heat-
ing. The indoor temperature changes before and after heating are
shown in Fig. 18. Due to the existence of the water-passing wall,
when the building is not heating in the heating season, the indoor
temperature of each thermal zone is above 0 ℃ (see Fig. 18). There-
fore, only a minor amount of energy is needed for heating, making
Fig. 15. Comparison of theoretical and experimental values of internal wall heat the occupants obtain higher thermal comfort. After heating, the
flux at different temperatures. indoor monthly average temperature is stable at about 22 ℃; it is
higher than the specified indoor temperature in winter in the rel-
evant national standards of China. Combined with natural ventila-
wooden structure building has good performance of thermal insu- tion in summer, the annual average indoor temperature of the
lation. As a result, even if water is supplied to the wall in summer, wooden structure building is 20.5 ℃, and the monthly average
the indoor temperature is still higher than the outdoor tempera- temperature of every month exceeds 16 ℃; the wooden structure
ture. Therefore, for the sake of energy saving, it can be stopped building has high thermal comfort.
10
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

Fig. 16. Comparison of the monthly average temperature of outdoor and indoor in each thermal zones before and after the water supply to the wall.

Fig. 17. Comparison of indoor and outdoor temperature changes before and after natural ventilation.

4.3. The energy consumption and cooling loads (see Table14) and the total energy consumption
(see Table15). In this building, the heating loads include heat gain
Using the building system described in section3, the wooden of people, lighting, indoor equipment, window, and opaque envel-
structure building was simulated to determine the annual heating ope structure, and the cooling loads include heat dissipation of
11
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

Fig. 18. Comparison of indoor and outdoor temperature changes before and after heating.

Table 14
Cooling and heating loads statistics of each thermal zone.

Loads Cooling load per Heating loads per


Thermal zone unit area [W/m2] unit area [W/m2]
Thermal zone1 11.46 23.56
Thermal zone2 2.15 17.58
Thermal zone3 9.19 32.78
Thermal zone4 2.45 20.04
Total 7.86 24.9

window and opaque envelope structure. The total energy con-


Fig. 19. The proportion of each energy consumption in the total energy
sumption includes the heating system energy consumption,
consumption.
water-passing wall system energy consumption, lighting system
energy consumption, and indoor equipment energy consumption.
According to calculations, the heating loads index of the wooden wooden structure building, although the existence of the water-
structure building is 24.9 W/m2, and the air conditioning cooling passing wall system can increase the power consumption of the
loads index is 7.9 W/m2, which meets the requirements of the circulating pump by 18.4%, the energy consumption of the heating
heating loads index and cooling loads index in the relevant system only accounts for 20.94%, it has obtained huge energy-
national standards of China. saving benefits.
The annual energy consumption of the wooden structure build- To determine the energy-saving rate of the wooden structure
ing was about 2080.24 KWh, the average energy consumption per building with the water-passing wall, we also simulated the energy
unit area was 18.6 KWh/m2, which the heating system was 3.9 consumption without the water-passing wall under the same con-
KWh/m2 (20.9%), the water-passing wall system was 3.4 KWh/ ditions. The basic information of the building without the water-
m2 (18.4 %), the lighting system was 4.7 KWh/m2 (25%), and the passing wall is the same as the building with the water-passing
indoor equipment was 6.6 KWh/m2 (35.7%) (See Fig. 19). In this walls in this study. According to the calculation, the energy

Table 15
Energy consumption of each system.

Month Lighting [KWh] Indoor equipment [KWh] Water-passing wall system [KWh] Heating circulating pump [KWh] Total [KWh]
1 44.1 63.01 103.33 102.85 313.29
2 39.73 56.92 79.7 79.24 255.59
3 43.75 63.01 51.02 51.4 209.18
4 42.58 60.96 0 21.29 124.83
5 44.1 63.01 0 0 107.11
6 44.27 60.96 0 0 105.23
7 44.1 63.01 0 0 107.11
8 43.89 63.01 0 0 106.9
9 42.44 60.96 0 0 103.4
10 44.1 63.01 0 32.36 139.47
11 42.39 60.96 60.93 60.51 224.79
12 43.9 63.01 88.49 87.94 283.34
Total 519.35 741.83 383.47 435.59 2080.24

12
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

Fig. 21. Comparison of electricity generation and consumption in the wooden


structure building.
Fig. 20. The electricity generation of solar PV system of the wooden structure
building.
4.5. Energy criteria of net zero energy wooden structure buildings

consumption was reduced by 62.9% compared with energy-saving According to the calculations, the ‘‘comprehensive value of
buildings without the water-passing wall. Therefore, it is an effec- building energy consumption” of the wooden structured building
tive way to realize net zero energy consumption by supplying is 37.89KWh/(m2a); this means that the building is a negative
groundwater or shallow geothermal water into the wall of the energy consumption building and can generate energy, the elec-
wooden structure building in the severe cold zone. tricity generation is more than the electricity consumption by
the building itself, it also shows that this wooden structure build-
ing in Hailar has no impact on the environment. The energy con-
4.4. Electricity generation of solar PV sumption per unit area of the building is 18.6KWh/(m2a), the
yearly heat consumption for heating is 7.3KWh/(m2a), the air-
According to the calculation, the yearly electricity generation of tightness of the building N50 is 0.5, and the utilization rate of
solar PV system in this wooden structure building is 3329.15KWh, renewable energy exceeds 100%. These values have met the
and the yearly electricity consumption is 2080.24KWh, its elec- requirements in the relevant standards of zero energy building of
tricity generation is greater than its electricity consumption. China. Therefore, it can be determined that this wooden structure
Therefore, this building achieves a balance between supply and building in Hailar has initially pursued the requirement of net zero
demand of electricity and has a surplus of electricity. Fig. 20 shows energy consumption.
the monthly change of the electricity generation of the solar PV
system. Due to Hailar is located at a higher latitude, the sun’s alti- 4.6. The economy of net zero energy wooden structure building
tude angle was reduced in winter, and the solar radiation intensity
is also decreased, which can cause the electricity generation of the The economy of net zero energy wooden structure building in
solar PV system to be lower throughout the winter. However, the the severe cold zone has aroused widespread concern. In this
solar radiation intensity is the highest in May; in this time, the study, the cost of the wooden structure building is 2410 yuan/
power generation of the solar photovoltaic system reaches its peak m2, 17% higher than that of the ordinary energy-efficient light
for the whole year. wooden structure building under the same circumstances (see
In the design stage, the electricity generation capacity of the Table16). There are three main reasons for the increase in cost:
solar PV system is 20% more than the actual electricity consump- (1) the cost of solar PV systems, including solar PV panels with
tion of the building. Theoretically, the demand of net zero energy monocrystalline silicon, inverter, and batteries, etc. (2) the cost of
consumption can be pursued by using this system; however, the the high-performance envelope structure; (3) the cost of the
monthly electricity consumption and the monthly electricity gen- water-passing wall system, including water pipes and circulating
eration of the wooden structure building could not be matched pump, etc. However, the wooden structure building in this study
well (see Fig. 21). In winter (January, February, November, and can be more energy-efficient than traditional energy-saving build-
December), electricity consumption is higher than electricity gen- ings. According to formula (5), the payback period is 9 years. In
eration. Still, in other months, electricity generation is more than order to further promote and implement net zero energy buildings
electricity consumption; there is a mismatch between electricity in Hailar pastoral areas and even the whole country, more efforts
supply and demand. Therefore, solar PV systems need to adopt are needed to put in.
methods such as using the battery to achieve ‘‘peak-shaving and
DI
valley-filling” to match the supply and demand of the electricity. N payback ¼ ð5Þ
ðQ PV;power þ Q S Þ  P P
When the electricity generation of the solar PV system is more
than the electricity consumption of the building, the surplus elec- Here: N payback is the payback period, years; DI is value of capital cost,
tricity is stored in the battery; when the electricity generation is RMB yuan, it can be calculated by Eq. (6); Q PV;power is total annual
insufficient, the electricity that stored in the battery will be sup- electricity production from photovoltaic panels, KWh; Q S is the
plied to the building, and ensuring the smooth operation of the annual energy savings, KWh/year,; P P is tariff, RMB yuan/KWh,
wooden structure building system. In this solar PV system, the PP = 0.49 yuan/KWh.
inverter and the system will also consume part of the electricity,
which consumes about 277.8KWh. DI ¼ I 0 þ I m;t ð6Þ

13
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

Table 16 (5) The electricity generation of the solar PV system of the woo-
Comparison of the construction cost of the net zero energy wooden structure building den structure building generates more electricity than the
and ordinary wooden structure building.
actual electricity consumption. However, the monthly elec-
construction cost net zero energy ordinary wooden tricity generation cannot be well-matched with the electric-
wooden structure structure building ity consumption. To address this problem, methods such as
building (RMB yuan) (RMB yuan)
batteries are used in the solar PV system to ‘‘peak-shaving
The overall structure of the 224,108 218,750 and valley-filling” to match the supply and demand of
building + doors and
windows
electricity.
Water-passing wall system 20,170 0 (6) According to calculations, the ‘‘comprehensive value of
Renewable energy 20,358 0 building energy consumption”, ‘‘utilization rate of renew-
utilization system able energy”, and the ‘‘performance index of the building
Other 5284 5284
itself” were met the requirements of the relevant standards
Total 269,920 224,034
of China for zero energy buildings. The wooden structure
building in Hailar has initially achieved net zero energy
I m;0 1 consumption.
I m;t ¼ ½1   ð7Þ
r ð1 þ r Þn (7) The biggest obstacle to implementing and promoting the
development of net zero energy buildings is the high initial
Here: I0 is the value of initial investment cost, RMB yuan; Im;t is the investment. The payback period of the construction invest-
total maintenance costs in PV, RMB yuan; Im;0 is the maintenance ment in the wooden structure building in Hailar is 9 years.
costs in PV for the first year, RMB yuan; n is the expected lifetime Therefore, it is necessary to develop appropriate technolo-
for PV; r is the discount rate, r = 8%; The yearly maintenance and gies to reduce the initial investment.
the expected lifetime was assumed to be 4% of the initial invest-
ment and 20 years, respectively[56].

5. Conclusion Declaration of Competing Interest

In this study, a wooden structure building in Hailar, China was The authors declare that they have no known competing finan-
selected as a case building to investigate the operational perfor- cial interests or personal relationships that could have appeared
mance of net zero energy wooden structure building in the severe to influence the work reported in this paper.
cold zone. By designing a new type of water-passing wooden struc-
ture wall, utilizing natural ventilation and other measures, the
energy consumption of the building is significantly reduced, and References
the thermal comfort of the building is improved. In addition, the
solar PV system is used to provide electricity to the building to [1] Statistics Bureau of the People’s Republic of China. Statistical bulletin of the
meet the electricity demand of the building. One year’s operational People’s Republic of China on 2020 national economic and social development
2020.
measurements show that the net zero energy wooden structure
[2] B.R. Hughes, H.N. Chaudhry, J.K. Calautit, Passive energy recovery from natural
building in the severe cold zone could be achieved conditionally. ventilation air streams, Applied Energy 113 (2014) 127–140.
The following conclusions are drawn: [3] Statistics Bureau of the Hailar. Statistical bulletin of the Hailar on 2020
national economic and social development 2020.
[4] X. Yuan, X. Wang, J. Zuo, Renewable energy in buildings in China—a review,
(1) The wooden structure building in Hailar has good opera- Renewable and Sustainable Energy Reviews 24 (2013) 1–8.
tional performance, its new type of water-passing wall and [5] S. Yu, J. Eom, Y. Zhou, M. Evans, L. Clarke, Scenarios of building energy demand
other envelope structure has good performance of thermal for China with a detailed regional representation, Energy 67 (2014) 284–297.
[6] China Association of Building Energy Efficiency. Building energy-saving
insulation, the U-values are also lower than the regulations technology, Modern Press Co., Ltd (2014). (in Chinese).
in relevant standards of China, and the indoor thermal com- [7] D. Crawley, S. Pless, P. Torcellini. Getting to net zero. ASHRAE J Am Soc Heat
fort level can be maintained at a high point throughout the Refrig Air Cond Eng Inc (2009).
[8] X. Li, W. Wu, C.W.F. Yu, Energy demand for hot water supply for indoor
year. After actual measurement, the error between the sim- environments: problems and perspectives, Indoor Built Environ 24 (1) (2015)
ulation result and the actual measurement result is within 5–10.
10%. [9] A. Mohamed, S. Cao, A. Hasan, K. Sirén, Selection of micro-cogeneration for net
zero energy buildings (NZEB) using weighted energy matching index, Energy
(2) The water pipes are pre-embedded in different positions of Build 80 (2014) 490–503.
the wall, the water-passing walls have different functions. [10] F. Favoino, M. Overend, Q. Jin, The optimal thermo-optical properties and
When the embedded pipes in the wall near the indoor side, energy saving potential of adaptive glazing technologies, Applied Energy 156
(2015) 1–15.
the water-passing wall was similar to a radiant cooling/heat-
[11] L. Wang, J. Gwilliam, P. Jones, Case study of zero energy house design in UK,
ing system. When the pipes are embedded in the middle of Energy Build 41 (11) (2009) 1215–1222.
the wall, the water-passing wall plays a role in isolating [12] L. Zhu, R. Hurt, D. Correa, R. Boehm, Comprehensive energy and economic
analyses on a zero energy house versus a conventional house, Energy 34 (9)
the outdoor cold.
(2009) 1043–1053.
(3) During the transitional seasons and summer, natural venti- [13] L. Zhu, R. Hurt, D. Correia, R. Boehm, Detailed energy saving performance
lation can be carried out. After natural ventilation, the analyses on thermal mass walls demonstrated in a zero energy house, Energy
annual average indoor temperature is 20.5℃, and the indoor Build 41 (3) (2009) 303–310.
[14] R.Z. Homod, H. Togun, H.J. Abd, K.S.M. Sahari, A novel hybrid modelling
environment has high thermal comfort. structure fabricated by using Takagi-Sugeno fuzzy to forecast HVAC systems
(4) Due to the water-passing wall’s effect, the heating system’s energy demand in real-time for Basra city, Sustainable Cities and Society 56
energy consumption in the wooden structure building is sig- (2020) 102091, https://doi.org/10.1016/j.scs.2020.102091.
[15] Y.u. Zhao, N. Li, C. Tao, Q. Chen, M. Jiang, A comparative study on energy
nificantly reduced. Although it can increase the electricity performance assessment for HVAC systems in high-tech fabs, Journal of
consumption of circulating pumps of the water-passing wall Building Engineering 39 (2021) 102188, https://doi.org/10.1016/j.
system, its energy-saving rate is up to 62.9%, which is com- jobe.2021.102188.
[16] I. Zlatanović, K. Gligorević, S. Ivanović, N. Rudonja, Energy-saving estimation
pared with buildings without water walls, and the energy- model for hypermarket HVAC systems applications, Energy and Buildings 43
saving benefit is obvious. (12) (2011) 3353–3359.

14
S. Ni, N. Zhu, Z. Zhang et al. Energy & Buildings 257 (2022) 111788

[17] B.A. Sun, P.B. Luh, Q.S. Jia, Z. O’Neill, F.T. Song, Building energy doctors: an SPC [38] Statistics Bureau of the People’s Republic of China. Statistical bulletin of the
and Kalman filter-based method for system level fault detection in HVAC People’s Republic of China on the 7th national census, 2020.
systems, IEEE Trans Autom Sci Eng 11 (1) (2014) 215–229. [39] Z. Liu, Q. Zhou, Z. Tian, et al., Comprehensive analysis on definitions,
[18] I. Kistelegdi, I. Haber, Building aerodynamic investigations for an energy-plus development, and policies of nearly zero energy buildings in China,
production facility in Sikonda (Hungary), Bauphysik 34 (3) (2012) 107–120. Renewable and Sustainable Energy Reviews 114 (2019) 109314.
[19] L. Wang, S. Greenberg, J. Fiegel, A. Rubalcava, S. Earni, X. Pang, R. Yin, S. [40] National standard of the People’s Republic of China. Technical standard for
Woodworth, J. Hernandez-Maldonado, Monitoring-based HVAC commissioning prefabricated wooden structure building, 2016. (in Chinese).
of an existing office building for energy efficiency, Applied Energy 102 (2013) [41] National standard of the People’s Republic of China. Design standard for
1382–1390. energy efficiency of residential buildings in severe cold and cold areas, 2018.
[20] M. Maasoumy, A. Sangiovanni-Vincentelli, Total, energy peak. Consumption (in Chinese).
minimization of building HVAC systems using model predictive control, IEEE [42] National standard of the People’s Republic of China. Technical standard for
Des Test Comput 29 (4) (2012) 26–35. nearly zero energy building, 2019. (in Chinese).
[21] Y. Su et al., Analysis of green building performance in cold coastal climates: An [43] Yang Yang, Sarula Chen, Tianxin Chang, et, al. Uncertainty and global
in-depth evaluation of green buildings in Dalian, China, Renewable and sensitivity analysis on thermal performances of pipe-embedded building
Sustainable Energy Reviews 146 (2021) 111–149. envelope in the heating season. Energy Conversion and Management, 244
[22] Y. Lu, S. Wang, K. Shan, Design optimization and optimal control of grid- (2021)114509.
connected and standalone nearly/net zero energy buildings, Applied Energy [44] M. Krajčík, M. Arıcı, et al., Review of water-based wall systems: Heating,
155 (2015) 463–477. cooling, and thermal barriers, Energy and Buildings 253 (2021) 111476.
[23] G. Feng, S. Sha, X. Xu, Analysis of the Building Envelope Influence to Building [45] Shi Guanyu, Yu Yanshun, Characteristics of the Low-temperature Hot Water
Energy Consumption in the Cold Regions, Procedia Engineering 146 (2016) Radiant Heating System with PCM Wall, Building Energy & Environment 29 (6)
244–250. (2010) 36–39.
[24] Usta, P. and B. Zengin, The Energy Impact of Building Materials in Residential [46] Baisong Ning, Youming Chen, Hongyuan Jia. A response factor method to
Buildings in Turkey. Materials, 14(11)(2021) 2793. quantify the dynamic performance for pipe-embedded radiant systems.
[25] X.u. Weitao, Development status of wooden structure building in North Energy and Buildings, 250(2021) 111311. [47] Liqun Zhou, Chaojie Li. Study
America and China, China forest products industry 45 (10) (2018) 7–16 (in on thermal and energy-saving performances of pipe-embedded wall utilizing
Chinese). low-grade energy. Applied Thermal Engineering, 176(2020) 115477.
[26] F. Benhua, L. Yan, Wooden Structure Architecture in China, China Forestry [47] Sihang Jiang, Xianting Li, Weihua Lyu, et al., Numerical investigation of the
Press, Beijing, 2011 (in Chinese). energy efficiency of a serial pipe-embedded external wall system considering
[27] AS 1720. 4-1990 Timber Structures Part 4: Fire Resistance of Structural Timber water temperature changes in the pipeline, Journal of Building Engineering 31
Members. (2020) 101435.
[28] S. Schnabl, G. Turk, I. Planinc, Buckling of Timber Columns Exposed to Fire, Fire [48] Li Zhu, Yang Yang, Numerical study on the thermal performance of pipe-
Safety Journal 46 (7) (2011) 431–439. embedded PCM building envelope in the heating season, Energy Procedia 158
[29] K. Yue, B. Liang, J. Liu, M. Li, Y. Pu, W. Lu, Z. Han, Z. Li, Fire resistance of light (2019) 2663–2670.
wood frame walls sheathed with innovative gypsum-particle composite: [49] Qiuyuan Zhu, Anbang Li, Junlong Xie, et al., Experimental validation of a semi-
Experimental investigations, Journal of Building Engineering 45 (2022) dynamic simplified model of active pipe-embedded building envelope,
103576, https://doi.org/10.1016/j.jobe.2021.103576. International Journal of Thermal Sciences 108 (2016) 70–80.
[30] R. Wang, W. Feng, L. Wang, et al., A comprehensive evaluation of zero [50] M. Krzaczek, J. Florczuk, J. Tejchman, Improved energy management technique
energy buildings in cold regions: Actual performance and key technologies in pipe-embedded wall heating/cooling system in residential buildings,
of cases from China, the US, and the European Union, Energy 215 (2021) Applied Energy 254 (2019) 113711.
118992. [51] M. Ibrahim, E. Wurtz, P.H. Biwole, et al., Transferring the south solar energy to
[31] A. Chbihi, S. Naamane, S. Boukheir, M. Mouadine, M.H. Bouhamidi, Outdoor the north façade through embedded water pipes, Energy 78 (2014) 834–845.
investigation of the performance of three PV panels technologies in Morocco, [52] D.O. Rijksen, C.J. Wisse, A.W.M. VAN Schijndel, Reducing peak requirements
Solar Energy 220 (2021) 8–17. for cooling by using thermally activated building systems, Energy Build. 42
[32] U. Stritih, V.V. Tyagi, R. Stropnik, H. Paksoy, F. Haghighat, M.M. Joybari, (2010) 298–304.
Integration of passive PCM technologies for net-zero energy buildings, [53] P. Vangtook, S. Chirarattananon, Application of radiant cooling as a passive
Sustainable Cities and Society 41 (2018) 286–295. cooling option in hot humid climate, Build. Environ 42 (2) (2007) 543–556.
[33] L. Shen, X. Pu, Y. Sun, J. Chen, A study on thermoelectric technology application [54] M.V. Albanese, B.S. Robinson, E.G. Brehob, et al., Simulated and experimrntal
in net zero energy buildings [J], Energy 113 (2016) 9–24. performance of a heat pipe assisted solar wall, Sol. Energy 86 (2012) 1552–
[34] M. Alirezaei, M. Noori, O. Tatari, Getting to net zero energy building: 1562.
Investigating the role of vehicle to home technology [J], Energy & Buildings [55] Ma. Yufeng, Li Xicang, Song Jinhua, et al., The climatological calculation of
130 (2016) 465–476. global solar radiation and its temporal and spatial distribution in Inner
[35] Y. Wang, H. Feng, X. Xi, Monitoring and autonomous control of Beijing Subway Mongolia Autonomous region [J], Journal of Meteorology and Environment 29
HVAC system for energy sustainability, Energy for Sustainable Development (6) (2013) 102–109 (in Chinese).
39 (2017) 1–12. [56] J.F. Kreider, C.J. Hoogendoorn, F. Kreith, Solar Design: Components, Systems
[36] L.i. Li, J. Lin, W.u. Nianyuan, et al., Review and outlook on the international Economics, Hemisphere Publishing Corporation, New York, 1989.
renewable energy development, Energy and Built Environment 17 (2020) 12–19.
[37] Fatima Harkouss, Farouk Fardoun, Pascal Henry Biwole. Optimal design of
renewable energy solution sets for net zero energy buildings. Energy, 179
(2019) 1155-1175.

15

You might also like