For future Egypt SS S2 SWG

-Incomer
CT Ratio (1600/1).
51 /STAGE - 1 51 /STAGE - 2 51N /STAGE - 1 51N /STAGE - 2
0.92 In = 1472
Setting 0.125 In = 200 A
A
Time
1100 ms 1100 ms
Delay

-BUSCOUPLER
CT Ratio (1600/1)
51 /STAGE - 1 51 /STAGE - 2 51N /STAGE - 1 51N /STAGE - 2
0.92 In = 1472
Setting 0.1 In = 160 A
A
Time Delay 700 ms 700 ms

-Outgoing
CT Ratio (400/1)
51N /STAGE -
51 /STAGE – 1 51 /STAGE - 2 51N /STAGE - 1
2
Setting 1 In = 400 A 4 In = 1600 A 0.15 In = 60 A 1.5 In = 600 A
Time Delay 400 ms 150 ms 350 ms 150 ms

Except Outgoing ( j1 - j22 )


CT Ratio (800/1)
51N /STAGE -
51 /STAGE – 1 51 /STAGE - 2 51N /STAGE - 1
2
Setting 1 In = 800 A 3 In = 2400 A 0.15 In = 120 A 1 In = 800 A
Time Delay 600 ms 250 ms 600 ms 250 ms