Motor Protection & Circuit Breaker Tripping Settings

Motor Details

Motor Rating 0.75 Kw 0.75 0.6


System Voltage V (L-L) 415 Volt 3 Ph
Supplay Frequency 50 Hz
Pole 4 No
Motor Spped 1000 Rpm
Locked Rotor Code B
Motor Demand Factor 1
Motor Service Factor 2
Motor Operating Temperature 30 C
Motor Starting Method Dol
Motor Starting P.F 0.6
Motor Running P.F 0.8
Motor Full Load Efficiency 100 % 1
Calculation
Motor Consumed Load 0.75 Kw
Motor Starting Current 13.04 Amp
Motor Full Load Current 1.30 Amp
Syncronus Speed(Ns) 1500 Rpm
Slip 33%
Locked Rotor Current (LRA) 2.61 Amp
Motor Protection
Maximum Size of OverLoad Perotection 1.63 Amp
Standared(On Time Delay) Fuse (Max) 3.91 Amp
On Time Delay Fuse (Max) 2.28 Amp
Instantaneous Trip C.B(Max) 10.43 Amp
Inverstime C.B(Max) 3.26 Amp
Circuit Breaker Tripping Settings
Instant.Short Circuit Tripping Setting of C.B

Voltage(L-L) 440 Volt


Voltage(L-N) 230 Volt
Instantaneous Short-Circuit Triping Set 100 Amp
Accuracy 20 %
Cable Size 3cx2.5 3 0
Cable Material Cu
Actual Length of Cable 80 Meter

Max.Length of Cable for your Tripping setting 83 Meter


Tripping Setting of C.B OK

Selection of Circuit Fuse

Circuit Wire /Cable Size 55 mm2

Circuit Fuse Size(Max) 325 Amp

Jignesh.Parmar
jiguparmar@yhaoo.com
www.electricalnotes.wordpress.com
Dol Alu AWG
Y-D Cu mm2
Hp Auto Tra.
Kw Soft
1 Ph Freq.Conv
3 Ph 3.35
A 0 3.15
B 3.15 3.55
C 3.55 4
D 4 4.5
E 4.5 5 55
F 5 5.6
G 5.6 6.3
H 6.3 7.1
J 7.1 8
K 8 9
L 9 10
M 10 11.2
N 11.2 12.5
P 12.5 14
R 14 16
S 16 18
T 18 20
U 20 24
V 24
AWG mm2 Maximum Fuse Size(Amp)
OO 70 400
OO 55 325
1 50 250
2 35 200
4 25 125
6 16 80
8 10 50
10 6 30
12 4 20
14 2.5 15
16 1.5 7.5