You are on page 1of 13

i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2

Available online at www.sciencedirect.com

w w w . i i fi i r . o r g

journal homepage: www.elsevier.com/locate/ijrefrig

Theoretical and practical comparison of two-phase ejector


refrigeration cycles including First and Second Law analysis

Neal Lawrence, Stefan Elbel*


Air Conditioning and Refrigeration Center, Department of Mechanical Science and Engineering, University of Illinois at Urbana-Champaign,
1206 West Green Street, Urbana, IL 61801, USA

article info abstract

Article history: This paper compares the standard two-phase ejector refrigeration cycle with a liquid
Received 9 September 2012 evapor separator to two alternate, less commonly considered two-phase ejector refriger-
Received in revised form ation cycles as well as to a conventional cycle with an expansion valve. An analytical
4 March 2013 comparison of the different ejector cycles’ theoretical COP’s is presented and used to show
Accepted 6 March 2013 that they have the same theoretical COP. Numerical models are used to further compare
Available online 15 March 2013 the cycles in terms of theoretical COP and availability destruction. The results show that
the standard two-phase ejector cycle has lower availability destruction and higher Second
Keywords: Law efficiency than the alternate ejector cycles despite having the same theoretical COP.
Ejector Some advantages and disadvantages of the different ejector cycles that are not accounted
Expansion work recovery for in the theoretical COP are discussed. The potential practical advantages offered by the
Throttling loss alternate ejector cycles show that these and other alternate ejector cycles may be worth
Availability additional attention in future studies.
Destruction ª 2013 Elsevier Ltd and IIR. All rights reserved.
Cycle-comparison

Comparaison théorique et pratique des cycles frigorifiques


diphasiques à éjecteur, y compris à l’aide d’analyse fondée
sur les premier et second principes
Mots clés : éjecteur ; récupération du travail de détente ; perte en charge à l’étranglement ; disponibilité ; destruction ; cycle e comparaison

1. Introduction reversed Rankine cycle with an expansion turbine. A more


desirable process would be an isentropic expansion across
The throttling of a high-pressure saturated or subcooled liquid this pressure differential, increasing the cooling capacity
to a low-pressure two-phase fluid in the vapor-compression of the cycle and allowing for the potential to recover some
refrigeration cycle is an irreversible process which limits the of the expansion work that would otherwise have been lost by
potential performance of the cycle in comparison to the the throttling process. Several methods of expansion work

* Corresponding author. Tel.: þ1 217 344 7663; fax: þ1 217 333 1942.
E-mail addresses: elbel@illinois.edu, stefanelbel@gmail.com (S. Elbel).
0140-7007/$ e see front matter ª 2013 Elsevier Ltd and IIR. All rights reserved.
http://dx.doi.org/10.1016/j.ijrefrig.2013.03.007
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2 1221

Nomenclature Subscripts
II referring to the Second Law of Thermodynamics
Abbreviations and variables Carnot referring to the Carnot COP
CFD computational fluid dynamics cond condenser
COP coefficient of performance cp compressor
COS condenser outlet split cv control volume
DOS diffuser outlet split dest destruction (of availability)
h specific enthalpy (kJ kg1) diff diffuser of the ejector
LMTD logarithmic mean temperature difference (K) evap evaporator
m_ mass flow rate (kg s1) high high-temperature evaporator
P pressure (kPa) in inlet
Q_ cooling capacity (kW) isen referring to an isentropic process
r ratio of motive to total flow () low low-temperature evaporator
s specific entropy (kJ kg1 K1) m ejector motive flow
SC subcooling mn ejector motive nozzle
SH superheat o referring to the thermodynamic dead state
T temperature (K) out outlet
V velocity (m s1) s ejector suction flow
W _ power (kW) sn ejector suction nozzle
x quality () Standard standard two-phase ejector cycle with liquid
vapor separator
Greek
total referring to the combined cooling capacity of
h efficiency ()
multiple evaporators
f specific availability (kJ kg1)
F_ total availability rate (kW)

recovery have been proposed, and among them is the two- Much of the recent work on two-phase ejectors has been
phase ejector. A two-phase ejector is a combined pump- focused on transcritical CO2 systems because of the high
expansion device that uses the expansion of a high-pressure throttling loss and high potential for improvement associated
fluid to entrain and increase the pressure of a low-pressure with the throttling of transcritical CO2 in the expansion valve
fluid. In a two-phase ejector, a high-pressure liquid (motive) cycle. Liu et al. (2002) performed one of the first numerical
stream is sent through a converging-diverging nozzle and analyses on the transcritical CO2 ejector cycle and calculated a
expanded to a high velocity and low pressure. This high ve- COP improvement of up to 14% compared to an expansion
locity motive stream is used to entrain a low-pressure vapor valve cycle. Elbel and Hrnjak (2004a) and Li and Groll (2005)
(suction) stream through momentum transfer between the both showed that the gas cooler pressure could be used
two streams. The two streams are mixed, enter a diffuser, maximize the COP of the transcritical CO2 ejector cycle, and
where they are decelerated and compressed to a pressure they calculated maximum COP improvements of 10% and
higher than the initial pressure of the suction stream, and exit 18%, respectively. Deng et al. (2007) performed a Second Law
the ejector as a two-phase fluid; the result is a pressure in- analysis of the transcritical CO2 ejector cycle. They found
crease provided to the low-pressure vapor that is being that the high-side pressure that maximized COP was the same
pumped by the high-pressure liquid. as the high-side pressure that resulted in the minimum
The concept of using a two-phase ejector to reduce throt- availability destruction; they also found that at this optimum
tling losses in a refrigeration cycle was first proposed by Gay high-side pressure, the ejector cycle resulted in a 23% reduc-
(1931). Kornhauser (1990) developed a thermodynamic model tion in the amount of availability destroyed and a 22% COP
for the combined expansion and pumping processes in the improvement compared to the expansion valve cycle. Elbel
ejector and found theoretical COP improvements for the and Hrnjak (2008) presented experimental results of a tran-
ejector cycle of 21% over the expansion valve cycle with R12 as scritical CO2 ejector cycle and achieved a simultaneous in-
the working fluid. Domanski (1995) used the model of crease in cooling capacity and COP of 8% and 7%, respectively.
Kornhauser (1990) to analyze 38 different refrigerants with the Similar experimental studies of the transcritical CO2 ejector
standard two-phase ejector cycle and found that most com- cycle were also performed by Nakagawa et al. (2011) and Lee
mon refrigerants, including R12, R22, R32, R134a, propane, et al. (2011) resulting in maximum COP improvements of
isobutane, and ammonia, offer between 10 and 30% theoret- 27% and 15%, respectively.
ical COP improvement. Initial experimental results by Harrell Several modifications to the two-phase ejector cycle of Gay
and Kornhauser (1995) showed an ejector system could ach- (1931) have been proposed. Kemper et al. (1966) proposed
ieve COP improvements of 3.9e7.6% over the expansion valve placing a liquid pump upstream of the ejector motive nozzle
cycle using R134a as the refrigerant. Disawas and Wongwises in the ejector cycle in order to increase the inlet pressure of
(2004) also used R134a with the ejector cycle and observed COP the motive stream. Bergander (2006) also used this idea of
improvements between 5% and 10%. using a pump to increase the ejector motive pressure and
1222 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2

proposed a cycle similar to the expansion valve cycle; in phase ejector cycle can be seen in Fig. 1(a), and the corre-
Bergander’s cycle, the compressor is supplemented by a pump sponding Peh diagram can be seen in Fig. 1(b).
and a two-phase ejector to further increase high-side pressure Two additional refrigeration cycles that incorporate two-
after the compressor discharge. Newton (1972a) and Newton phase ejectors are discussed here. Oshitani et al. (2005) pro-
(1972b) proposed modifications to the ejector cycle of Gay posed an ejector cycle in which the two-phase flow discharged
(1931) to allow for capacity control by adding additional from the ejector is sent through an evaporator, which leads
valves or bypass lines. It should be noted that none of the directly into the compressor. In this cycle, the ejector is used
previously mentioned modifications to the original two-phase to pump refrigerant through a second evaporator. The liquid
ejector cycle have been widely adopted, possibly because two- exiting the condenser is split into the ejector’s suction and
phase ejector cycles have not experienced large-scale motive streams; one stream of liquid directly enters the
commercialization. Several additional refrigeration cycles ejector motive nozzle as in the standard two-phase ejector
involving two-phase ejectors, different than the original two- cycle, and the other stream of liquid is throttled, evaporated in
phase ejector cycle with a liquidevapor separator, have also a second evaporator, and enters the ejector suction nozzle.
been proposed. Two of these cycles, proposed by Burk et al. Because of the pressure increase associated with the ejector,
(2006) and Oshitani et al. (2005), will be described below. there will also be a saturation temperature increase between
These two cycles differ from the cycle proposed by Gay (1931) the suction of the ejector and the diffuser, resulting in
in that they do not require a liquidevapor separator and they different evaporation temperatures in the evaporators. Note
allow for evaporation at two different temperatures. that because an evaporator is placed between the ejector and
The objective of this paper is to present a comparison of compressor, there is no need for a liquid vapor separator in
three different two-phase ejector refrigeration cycles as well this cycle. Because the liquid is split at the condenser outlet,
as a comparison to an expansion valve refrigeration cycle with this cycle will be referred to as the COS (condenser outlet split)
two evaporation temperatures. An analytical comparison of ejector cycle. A layout diagram of the COS ejector cycle can be
the theoretical COP’s of the ejector cycles will be presented. seen in Fig. 2(a), and the corresponding Peh diagram can be
Thermodynamic cycle models will also be used to compare seen in Fig. 2(b).
the theoretical COP’s of the different cycles numerically. An Burk et al. (2006) proposed a similar two-phase ejector
availability analysis of each of the cycles will be performed cycle. In this cycle, the two-phase flow at the diffuser outlet is
numerically, and the cycles will be further compared in terms split instead of the liquid at the condenser outlet, and the
of each cycle’s availability destruction and Second Law effi- ejector is again used to pump refrigerant through a second,
ciency. The implications of each cycle’s theoretical COP and low-temperature evaporator; this cycle will be referred to as
availability destruction will be discussed. Finally, the advan- the DOS (diffuser outlet split) ejector cycle. This cycle also
tages and disadvantages of each cycle that are not reflected allows for two different evaporation temperatures and
in the theoretical COP’s or Second Law efficiencies will be does not require a liquidevapor separator because there is an
discussed. evaporator placed between the ejector and compressor. A
layout diagram of the DOS ejector cycle can be seen in Fig. 3(a),
and the corresponding Peh diagram can be seen in Fig. 3(b).
2. Two-phase ejector cycles

Gay (1931) was the first to propose the use of a two-phase 3. First Law analysis of cycles
ejector for expansion work recovery in a refrigeration cycle.
This cycle, with a liquidevapor separator, has become the 3.1. Analytical performance comparison
standard cycle for two-phase ejectors and has been the focus
of the majority of two-phase ejector studies. The cycle will be It can be shown algebraically that the theoretical COP’s of the
referred to as the standard two-phase ejector cycle for the three two-phase ejector cycles mentioned above are the same.
remainder of the paper. A layout diagram of the standard two- This may be counterintuitive as one may expect the throttling

Fig. 1 e (a) Cycle layout of standard two-phase ejector cycle, (b) Pressureespecific enthalpy diagram of standard two-phase
ejector cycle.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2 1223

Fig. 2 e (a) Ejector cycle with condenser outlet split (COS) layout, (b) COS ejector cycle pressureespecific enthalpy diagram.

of the high-pressure liquid at the condenser outlet to result in h7 ¼ ð1  rÞh9 þ rh3 (4)
a larger amount of availability destruction (causing a larger
Inserting Equation (4) into Equation (2) and proceeding with
decrease in COP) than the throttling processes in the other
the algebra shows that the theoretical COP’s of the COS and
cycles; this will be discussed in detail later. The COP’s of the
DOS ejector cycles are indeed equivalent, as shown in Equa-
COS and DOS ejector cycles will be compared first. The COP of
tion (5).
the COS cycle is given in Equation (1); the state points in
Equation (1) can be seen in Fig. 2. Similarly, the COP of the DOS ðh1  h7 Þ þ ð1  rÞðh9  h3 Þ
COPDOS ¼ ¼ COPCOS (5)
cycle is given in Equation (2); the state points in Equation (2) ðh2  h1 Þ
can be seen in Fig. 3.
The expression in Equation (5) can be further simplified
Q_ high þ Q_ low ðh1  h7 Þ þ ð1  rÞðh9  h3 Þ by inserting Equation (4) into Equation (5), as shown in
COPCOS ¼ ¼ (1) Equation (6).
W_ ðh2  h1 Þ
h1  h3
Q_ high þ Q_ low rðh1  h7 Þ þ ð1  rÞðh9  h7 Þ COPDOS;COS ¼ (6)
h2  h1
COPDOS ¼ ¼ (2)
W_ rðh2  h1 Þ
This analysis can be extended to show that the COP of the
In Equation (1), the specific enthalpy at the low-temperature
COS and DOS ejector cycles is the same as the COP of the
evaporator inlet (h8) has been replaced by the specific enthalpy
standard two-phase ejector cycle. Equation (7) gives the COP
at the condenser outlet (h3) because the expansion valve is
of the standard two-phase ejector cycle; the states in Equation
assumed to operate isenthalpically; similarly, the specific
(7) can be seen in Fig. 1.
enthalpy at the low-temperature evaporator inlet (h8) has
been replaced by the specific enthalpy at the diffuser outlet Q_ ð1  rÞðh9  h8 Þ
COPStandard ¼ ¼ (7)
(h7) in Equation (2). Equations (1) and (2) have used r, the ratio W_ rðh2  h1 Þ
of the motive mass flow rate to the total mass flow rate, as
defined in Equation (3). The refrigerant flow rates in terms of r From the definition of the quality of a two-phase fluid, a
are shown in Figs. 2 and 3 as well. relation for the specific enthalpy at the diffuser outlet (h7) can
be seen in Equation (8). Equation (8) can also be obtained by
_m
m
r¼ (3) performing an energy balance on the separator. Kornhauser
_m þm
m _s
(1990) noted that in the standard two-phase ejector cycle
An energy balance on the ejector in either the COS or DOS with a liquidevapor separator, a mass balance on the separator
ejector cycle yields a relation for diffuser outlet specific can show that the quality at the diffuser outlet (x7) must be
enthalpy (h7), as shown in Equation (4). equal to the mass flow ratio r. If Equation (8) is rearranged

Fig. 3 e (a) Ejector cycle with diffuser outlet split (DOS) layout, (b) DOS ejector cycle pressureespecific enthalpy diagram.
1224 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2

to solve for the specific enthalpy at the liquid port of the liq- been shown to have the same theoretical COP. A layout dia-
uidevapor separator (h8), and the quality at the diffuser gram of this expansion valve cycle is shown in Fig. 4(a), and
outlet (x7) is replaced by the mass flow ratio r, the result is the corresponding Peh diagram is shown in Fig. 4(b). The
Equation (9). following assumptions were made in the thermodynamic
models:
h7 ¼ h8 þ x7 ðh1  h8 Þ (8)
1. Pressure drop in heat exchangers and tubing is neglected.
h7  rh1 2. Heat transfer to or from tubing is neglected.
h8 ¼ (9)
1r 3. Temperature difference between air and refrigerant
streams does not affect heat transfer in the heat ex-
Equation (9) can then be substituted into Equation (7) to
changers (0 K LMTD).
obtain Equation (10).
4. Liquidevapor separator in the standard two-phase ejector
ð1  rÞh9  h7 þ rh1 cycle has perfect separation efficiency, and the vapor and
COPStandard ¼ (10)
rðh2  h1 Þ liquid at the outlets of the separator are at saturated
conditions.
Equation (4) can again be used and substituted into Equation
5. Ejector is modeled using analysis of Kornhauser (1990).
(10). The result shows that the COP of the standard two-phase
6. Compressor operates with a specified isentropic efficiency.
ejector cycle is the same as the COP of the COS and DOS
7. All valves operate isenthalpically.
ejector cycles, as seen in Equation (11).
8. Flow through the high-temperature evaporator in the
h1  h3 expansion valve cycle is throttled to the pressure of the low-
COPStandard ¼ ¼ COPDOS;COS (11)
h2  h1 temperature evaporator before entering the compressor.
Assuming that the compressor inlet state, compressor
outlet state, and condenser outlet state are the same for all The required inputs for the Kornhauser (1990) ejector
three cycles, which will be true for the thermodynamic cycle model are the motive inlet pressure (P3), motive inlet specific
models presented below, the COP of the COS ejector, DOS enthalpy (h3), suction inlet pressure (P9), suction inlet specific
ejector, and standard two-phase ejector cycles is the same. enthalpy (h9), and the ratio of motive flow rate to total flow
Thus, using an alternate two-phase ejector cycle imposes no rate, which has previously been defined as the parameter r, as
penalty on the system in terms of theoretical performance shown in Equation (3). The ejector model requires the
potential. This may be counterintuitive as one would expect assumption of isentropic efficiencies of the motive nozzle,
the wasted recovery potential in the COS ejector cycle, due to suction nozzle, and diffuser. The respective definitions of
the throttling across a larger pressure difference, to lower the these efficiencies are shown in Equation (12) through (14). The
cycle’s COP below that of the standard ejector cycle; however, ejector model also requires the assumption of a mixing sec-
as will be discussed later, this is not the case. tion pressure (P6). Fig. 5 shows the complete calculation
routine of the Kornhauser (1990) ejector model. The definition
of isentropic efficiency of the compressor is shown in Equa-
3.2. Thermodynamic cycle models tion (15). The assumed values of all of the parameters
mentioned here and used in the thermodynamic models will
Thermodynamic models were developed in order to further be discussed below.
investigate the performance of the three different two-phase
ejector cycles and compare them to an expansion valve
cycle with two evaporation temperatures in terms of the First h3  h4
hmn ¼ (12)
h3  h4;isen
Law efficiency (COP); the three ejector cycles have already

Fig. 4 e (a) Expansion valve cycle with two evaporation temperatures layout, (b) Expansion valve cycle with two evaporation
temperatures pressureespecific enthalpy diagram.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2 1225

For the standard two-phase ejector cycle, the cooling ca-


pacity of the single evaporator is determined as shown in
Equation (17). The outlet states of all evaporators in all cycles
are determined using the specified evaporation temperature
and the specified amount of superheat. The standard ejector
cycle evaporator inlet state (h8a) is determined using
the specified evaporation temperature and the saturated
liquid specific enthalpy at the separator pressure. For steady
operation of the standard ejector cycle, the ejector outlet
quality must equal the value of the parameter r, as shown in
Equation (18).

Q_ evap;Standard ¼ m
_ s ðh9  h8a Þ (17)

x7 ¼ r (18)

For the COS and DOS ejector cycles, the cooling capacity of
the low-temperature evaporator is determined as shown in
Equation (19). For the COS ejector cycle, the low-temperature
evaporator inlet specific enthalpy (h8) is equal to the
condenser outlet specific enthalpy (h3). For the DOS ejector
cycle, the low-temperature evaporator inlet specific enthalpy
is equal to the ejector outlet specific enthalpy (h7). The cooling
capacity of the high-temperature evaporator for the COS
ejector cycle is determined as shown in Equation (20), and the
cooling capacity of the high-temperature evaporator for the
DOS ejector cycle is determined as shown in Equation (21). The
high-temperature evaporator inlet state in the COS and DOS
ejector cycles are equal to the ejector outlet state (h7).

Q_ low;COS;DOS ¼ m
_ s ðh9  h8 Þ (19)

Q_ high;COS ¼ m
_ diff;out ðh1  h7 Þ (20)
Fig. 5 e Two-phase ejector calculation routine from
Kornhauser (1990). Q_ high;DOS ¼ m
_ m ðh1  h7 Þ (21)

The cooling capacities of the expansion valve cycle evapo-


rators can be calculated in a similar manner. Both of the
evaporator inlet enthalpies in the expansion valve cycle are
h9  h5 set equal to the condenser outlet enthalpy. The ratio of flow
hsn ¼ (13)
h9  h5;isen
through the evaporators in the expansion valve cycle is set to
be the same as the ratio of flow through the evaporators in the
h7  h6 DOS ejector cycle. The COP of the cycles is calculated as
hdiff ¼ (14)
0:5V62 shown in Equation (22). For the cycles with two evaporation
h2;isen  h1 temperatures, the sum of the individual cooling capacities is
hcp ¼ (15)
h2  h1 used in the COP calculation.

The cooling capacities of the evaporators as well as the Q_ evap


COP ¼ (22)
compressor power are calculated from energy balances on the W _ cp
components. The compressor power for all four cycles is
calculated as shown in Equation (16). The compressor outlet In order to fairly compare the COS ejector, DOS ejector, and
state (h2) is determined from the condensation pressure expansion valve cycle with two evaporation temperatures,
(based on the specified condensation temperature) and the both of the evaporation temperatures and the condensation
isentropic efficiency of the compressor. The compressor inlet temperature must be the same. The standard two-phase
state (h1) is assumed to be the same as the vapor outlet of the ejector cycle with a liquidevapor separator has only a single
separator in the standard two-phase ejector cycle, the outlet evaporation temperature. In order to relate this cycle to the
state of the high-temperature evaporator in the COS and DOS other two ejector cycles, the diffuser outlet pressure of the
ejector cycles, and the outlet state of the low-temperature standard two-phase ejector cycle is used as the diffuser outlet
evaporator in the expansion valve cycle. pressure in the COS and DOS ejector cycles. Because the outlet
of a two-phase ejector is saturated, matching the diffuser
outlet pressure results in matched diffuser outlet tempera-
_ cp ¼ m
W _ cp ðh2  h1 Þ (16) ture. This then specifies the higher evaporation temperature
1226 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2

in the COS ejector, DOS ejector, and expansion valve cycles, temperature was also shown experimentally by Harrell and
which is necessary in order to fully constrain the system. This Kornhauser (1995) with R134a. This value of 0.5  C drop in
is a fair way to compare the three different ejector cycles saturation temperature is used for the present simulation
because the ejector will be operating at the same conditions with R134a.
and providing the same benefit in each of the cycles. Addi-
tionally, the total cooling capacity of all cycles is set to be 3.3. Results of thermodynamic models
5 kW, and the refrigerant used for the simulation is R134a.
Klein (2012) is used to evaluate thermodynamic properties and The results of the thermodynamic cycle models for the ideal
solve the models iteratively. case are shown in Table 2. The models confirm that all three
Table 1 lists the values of the parameters used in the ejector cycles have the same theoretical COP. It can also be
thermodynamic cycle models. Two different cases are tested. seen in Table 2 that the required compressor mass flow rate to
The first case is an idealized cycle in which the ejector and achieve 5.0 kW cooling capacity is the same in all of the ejector
compressor both operate reversibly, and the outlets of all heat cycles. The mass flow rates through the ejector motive and
exchangers are saturated. The second case is a more realistic suction nozzles as well as through the low-temperature
case, in which the ejector components and the compressor evaporator differ in the different ejector cycles. However,
have isentropic efficiencies less than unity, and some amount the ratio of motive flow to total flow (defined as the parameter
of subcooling and superheat are assumed at the outlets of the r) is the same in all ejector cycles. Additional advantages and
heat exchangers. The mixing section pressure (P6) also must disadvantages of the three ejector cycles that are not
be specified in the model. For the ideal case, the mixing sec- accounted for in the calculation of their theoretical COP will be
tion pressure is chosen such that mixing losses in the ejector discussed below.
are eliminated. For the realistic case, the mixing section Table 2 also shows that the two-phase ejector cycles offer a
pressure is set to be the saturation pressure that corresponded 23% COP improvement when compared to the expansion
to a 0.5  C drop in saturation temperature from the suction valve cycle with two evaporation temperatures at the given
nozzle inlet saturation temperature. operating conditions. In this simulation, the ratio of mass flow
The values of ejector component efficiencies seen in between the high- and low-temperature evaporators in the
Table 1 will be discussed here to show that they are expansion valve cycle was the same as in the DOS ejector
reasonable efficiencies for the respective components. cycle. However, because pressure drop and LMTD effects were
Nakagawa and Takeuchi (1998) showed experimentally that not considered in the thermodynamic cycle models, the dis-
the efficiency of an R134a nozzle could reach 0.8, and this tribution of flow between the two evaporators in the expan-
will be the assumed value of motive nozzle efficiency for the sion valve cycle makes very little difference in terms of total
realistic case. No experimental data could be found in the cooling capacity or COP. The temperature difference between
open literature on the efficiency of the suction nozzle with the evaporators is small enough that there is not a significant
R134a. However, Liu et al. (2012) showed experimentally difference in outlet enthalpy (or, consequently, evaporator
with CO2 that the suction nozzle can achieve similar effi- enthalpy difference between inlet and outlet); thus, for a set
ciency as the motive nozzle. Thus, the suction nozzle is also cooling capacity, there is little advantage, in terms of reduced
assumed to have an efficiency of 0.8. Additionally, no data compressor mass flow rate, gained from using the evaporator
on the efficiency R134a diffusers was found in the open with the greater outlet enthalpy. The COP of the expansion
literature. However, Varga et al. (2009) calculated a range of valve cycle varies from 5.59, for all flow through the low-
diffuser efficiencies between 0.5 and 0.9 using a CFD model temperature evaporator, to 5.61, for all flow through the
of a steam ejector; the value of 0.75 assumed in this study is high-temperature evaporator (but still throttled to the lowest
within that range of efficiencies. Elbel (2011) showed for pressure).
several data points with CO2 that the drop in saturation It should be noted that the expansion valve cycle with a
temperature between suction nozzle inlet and mixing sec- single evaporation temperature is just the two evaporation
tion is about 0.5  C; a similar value of drop in saturation temperature cycle with all flow through the lower tempera-
ture evaporator, again resulting in a COP of 5.59. If all flow is
sent through the high temperature evaporator but not throt-
tled to a lower pressure before the compressor, then the COP
Table 1 e System operating parameters and efficiencies of the expansion valve cycle with a single evaporation tem-
of various components used in the thermodynamic cycle perature is equal to 6.9, the same as the ejector cycles’ COP.
models for both ideal and realistic cases. The expansion valve cycle’s evaporator enthalpy difference is
Ideal case Realistic case increased because of the higher evaporation temperature, but

Tevap.low [ C] 5 5
the ejector cycles’ evaporator enthalpy difference is also
Tevap,high [ C] 11.3 7.4 effectively increased because of the isentropic expansion,
DTSH [ C] 0 5 resulting in the same evaporator enthalpy difference and
Tcond [ C] 45 45 same COP for the cycles. It should also be noted that in reality,
DTSC [ C] 0 3 a higher evaporation temperature would result from a higher
hcp [e] 1 0.75
air temperature, which is not a fair way to compare cycles;
hmn [e] 1 0.8
thus, it is not completely correct to say that the COP of the
hsn [e] 1 0.8
hdiff [e] 1 0.75 expansion valve cycle can be equal to that of the ejector
cycles.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2 1227

Table 2 e COP comparison of standard two-phase ejector cycle, COS ejector cycle, DOS ejector cycle, and expansion valve
cycle with two evaporation temperatures for the ideal case.
Standard two-phase ejector COS ejector DOS ejector Expansion valve cycle with
cycle with separator cycle cycle two evaporation temperatures

Q_ total [kW] e 5.0 5.0 5.0


Q_ low [kW] 5.0 2.1 2.1 2.1
Q_ high [kW] e 2.9 2.9 2.9
COP [e] 6.9 6.9 6.9 5.6
m_ m [kg s1] 0.035 0.020 0.035 0.020
m_ s [kg s1] 0.027 0.015 0.027 0.015
m_ diff;out [kg s1] 0.062 0.035 0.062 e
m_ cp [kg s1] 0.035 0.035 0.035 0.035

Table 3 shows the results of the thermodynamic models for 101 kPa for this analysis. Equation (24) defines the availability
the realistic case. It can be seen that with the realistic as- destroyed by a component of the system ðF_ dest Þ, from Moran
sumptions, the COP of the ejector cycles is reduced by about and Shapiro (2008), derived from a steady-state availability
33% and the ejector cycles now offer about 7% COP improve- balance on the component. The first term on the right-hand-
ment compared to the expansion valve cycle. It can also be side of Equation (24) is the availability transfer associated
seen that even with non-ideal effects accounted for in the with heat transfer occurring at temperature T, with heat being
cycle models, the COP of all three ejector cycles is still about defined as positive going into the system. The temperature T
the same. The COS and DOS ejector cycles and the expansion was assumed to be 10  C greater than the evaporation tem-
valve cycle actually have slightly reduced compressor flow perature in the evaporators (15  C low-temperature evapo-
rate for the realistic case. This is due to the superheat at the rator and 21.3  C and 17.4  C for the high-temperature
outlet of the high-temperature evaporator, which causes a evaporator in the ideal and realistic cases, respectively) and
slightly larger specific enthalpy difference across this evapo- 10  C less than the condensation temperature in the
rator in the COS and DOS cycles. The compressor suction in condenser (35  C for the condenser). The second term on the
the standard cycle draws saturated vapor from the liquid- right-hand-side of the equation is the availability transfer
evapor separator, and thus, the evaporator superheat does associated with work done by the system, with work being
not reduce the compressor mass flow rate in this cycle. The defined as positive going out of the system. The third and
superheated compressor inlet state in the COS and DOS cycles fourth terms on the right-hand-side of the equation are the
will create a slightly larger specific enthalpy difference across availability transfer associated with fluid flow into and out of
the compressor in these cycles, which will partially counteract the system, respectively. The difference between the avail-
the effect of reduced compressor flow rate. ability transferred into the system and the availability trans-
ferred out of the system is the availability destroyed in the
system ðF_ dest Þ.
4. Second Law analysis of cycles f ¼ h  ho  To ðs  so Þ (23)

The specific availability of a thermodynamic state (f) is   X X


To
defined in Equation (23) from Moran and Shapiro (2008). Note F_ dest ¼ Q_ 1  _ cv þ
W _ in fin 
m _ out fout
m (24)
T
that specific availability due to kinetic and potential energy
An availability analysis on each cycle was performed along
has been neglected here. Availability must be defined in
with the thermodynamic cycle models discussed above. The
reference to the thermodynamic dead state, here specified by
availability destruction in the heat exchangers, compressor,
a subscript “o”, which has been defined as R134a at 25  C and

Table 3 e COP comparison of standard two-phase ejector cycle, COS ejector cycle, DOS ejector cycle, and expansion valve
cycle with two evaporation temperatures for the realistic case.
Standard two-phase ejector COS ejector cycle DOS ejector cycle Conventional expansion valve
cycle with separator cycle with two evaporation
temperatures

Q_ total [kW] e 5.0 5.0 5.0


Q_ low [kW] 5.0 2.1 2.1 2.1
Q_ high [kW] e 2.9 2.9 2.9
COP [e] 4.6 4.6 4.6 4.3
_ m [kg s1]
m 0.035 0.020 0.034 0.020
_ s [kg s1]
m 0.025 0.014 0.025 0.014
_ diff;out [kg s1]
m 0.060 0.034 0.058 e
_ cp [kg s1]
m 0.035 0.034 0.034 0.034
1228 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2

Table 4 e Comparison of availability destruction in individual components and total in system for standard two-phase
ejector cycle, COS ejector cycle, DOS ejector cycle, and expansion valve cycle with two evaporation temperatures for the
ideal case.
Availability destruction in Standard two-phase ejector COS ejector DOS ejector Expansion valve cycle with
each component [kW] cycle with separator cycle cycle two evaporation temperatures

Compressor 0 0 0 0
Condenser 0.175 0.175 0.175 0.183
Ejector 0 0 0 e
Expansion/metering valve(s) 0.005 0.073 0.073 0.227
High-temperature evaporator e 0.103 0.103 0.103
Low-temperature evaporator 0.186 0.078 0.078 0.078
Evaporator (total) e 0.181 0.181 0.181
System 0.365 0.429 0.429 0.590
Carnot COP 6.95 7.73 7.73 7.73
Second law efficiency 0.99 0.89 0.89 0.72

ejector, and throttling valve(s) in each cycle was calculated, place across a much larger pressure difference than in the DOS
and the results for the ideal case are shown in Table 4. The ejector cycle. In general, one may be inclined to associate
table shows that standard two-phase ejector cycle results in higher pressure difference with higher throttling loss; how-
the lowest availability destruction, the COS ejector cycle and ever, it is only fair to make this comparison about two different
the DOS ejector cycle result in the same availability destruc- throttling processes if the processes lie along the same isen-
tion, and the expansion valve cycle results in the highest trope. The slope of the isentropes is different in different areas
availability destruction. The standard two-phase ejector cycle of the Peh diagram; the isentropes increase in slope, becoming
results in 15% less availability destruction than the COS and closer to vertical, as one moves to the left on the diagram into
DOS ejector cycles at the given operating conditions, while the regions of a lower quality or subcooled fluid. Thus, the isen-
expansion valve cycle results in 38% more availability trope at the start of the throttling process in the COS cycle has
destruction than the COS ejector and DOS ejector cycles at the a greater slope, corresponding to lower throttling loss for the
given operating conditions. same pressure difference, than the isentrope at the start of the
The table also shows what causes the differences in throttling process in the DOS cycle. Additionally, because of
availability destruction in the different cycles. The ejector and the smaller enthalpy difference of the low-temperature
compressor are assumed to operate reversibly in all cycles and evaporator in the DOS ejector cycle compared to the COS
do not destroy any availability. The condenser rejects the ejector cycle, a larger low-temperature evaporator mass flow
same amount of heat at the same temperature in all three rate is required, resulting in a larger mass flow that is throttled
ejector cycles, which results in the same availability destruc- in the DOS ejector cycle. This larger mass flow rate, combined
tion. Because the expansion valve cycle has a lower suction with the effect of different isentropes, makes it possible for the
pressure, the compressor pressure ratio will be higher, the throttling processes in the COS and DOS ejector cycles to result
compressor will need to input more work, and the heat in the same amount of availability destruction; the results of
rejection in the condenser will be higher for the same cooling the numerical simulation show that this is indeed the case.
capacity, resulting in higher condenser availability destruc- The standard two-phase ejector cycle involves the throttling of
tion for the expansion valve cycle. Conversely, the evapora- a saturated liquid across a small pressure difference and, thus,
tors absorb the same amount of heat at the same results in the lowest availability destruction. In the expansion
temperatures in the COS ejector, DOS ejector, and expansion valve cycle, there is no ejector, and all of the fluid is throttled
valve cycles, which results in the same availability destruction from the highest pressure to the lowest pressure, resulting in
in each of the evaporators for these cycles. In the standard the highest availability destruction.
two-phase ejector cycle, all of the heat transfer takes place in a Table 4 also shows the Carnot COP and the Second Law
single evaporator at the lower evaporation temperature, efficiency of each cycle. In general, the Carnot COP of a cooling
resulting in slightly higher availability destruction in this cy- cycle is defined as the absolute evaporation temperature
cle’s evaporator. However, the differences in availability divided by the difference between condensation temperature
destruction in the evaporators or the condensers of the and evaporation temperature. However, this definition does
different cycles are not the major factors affecting the differ- not work when there are multiple evaporation temperatures,
ences in total availability destruction in the cycles. and a new definition of the Carnot COP must be applied for
Table 4 shows that the availability destruction caused by this case. The proposed Carnot COP of a cycle that has mul-
the throttling process of the expansion/metering valves in tiple evaporation temperatures is shown in Equation (25). The
each of the cycles is the major contributor to the difference in evaporation temperature in the conventional definition of
the total availability destruction of the cycles. The availability Carnot COP has essentially been replaced by an effective
destruction due to throttling can be referred to as throttling evaporation temperature, which is a weighted average of the
loss. Interestingly, the throttling process in the COS ejector two different evaporation temperatures. The Second Law ef-
cycle results in the same availability loss as the throttling ficiency of a refrigeration cycle is then defined as the ratio of
process in the DOS ejector cycle. This may seem counterin- the cycle’s theoretical COP, as calculated above, to the cycle’s
tuitive as the throttling process in the COS ejector cycle takes Carnot COP, as shown in Equation (26). As would be expected
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2 1229

and is shown in Table 4, Second Law efficiency decreases with different cycles are the expansion processes (through the
increasing availability destruction; the standard two-phase ejector and valve) in each cycle. It is interesting to see that the
ejector cycle has the highest Second Law efficiency and the valves in the COS and DOS ejector cycles no longer destroy the
expansion valve cycle has the lowest. same amount of availability. However, the sum of the avail-
ability destruction in the two expansion devices is the same in
rTevap;high þ ð1  rÞTevap;low
COPCarnot;2Evap ¼   (25) the COS and DOS ejector cycles. Table 5 shows that the valve in
Tcond  rTevap;high þ ð1  rÞTevap;low
the standard ejector cycle destroys less availability in the real-
istic case than in the ideal case. The reason for this is because
COP
hII ¼ (26) the pressure difference that the valve throttles across is less in
COPCarnot
the realistic case, which is again due to the lower pressure lift
It is interesting to see that while all three cycles have the provided by the ejector. The compressor destroys slightly more
same theoretical COP, the standard two-phase ejector cycle availability in the standard ejector cycle than the COS and DOS
has lower theoretical availability destruction and higher Sec- ejector cycles due to the slightly higher compressor mass flow
ond Law efficiency than the COS and DOS ejector cycles. rate in the standard ejector cycle. However, because the
Because of the higher evaporation temperature in the COS and compressor inlet state is saturated instead of superheated
DOS ejector cycles, the Carnot COP for these two cycles is vapor in the standard ejector cycle, there is less superheat at the
higher. This means that in order to have the same theoretical compressor outlet, resulting in lower availability destruction in
COP as the standard two-phase ejector cycle, the COS and DOS the condenser in the standard cycle.
ejector cycles must actually deviate further from their Carnot
cycle. This further deviation from Carnot is represented in the
increased availability losses and decreased Second Law effi- 5. Discussion
ciency. However, it is important to understand that the
theoretical COP (in terms of energy) may be a more practical Despite the fact that all three ejector cycles have the same
means to compare cycles than the theoretical availability theoretical COP, it can be argued that there are additional
destruction because energy input, and not availability input, is advantages and disadvantages of the cycles, not reflected in
what is of economic value when running a thermal cycle. the simple models used to calculate theoretical COP, that
Table 5 shows the availability destruction results for would make one cycle more attractive than the other two.
the realistic case. It can again be seen that the standard ejector
cycle results in the lowest availability destruction, the 5.1. Multiple evaporation temperatures
expansion valve cycle results in the highest availability
destruction, and the COS and DOS ejector cycles result in the The first potential advantage of the COS and DOS ejector cy-
same availability destruction. However, the differences in cles is that they offer the potential for two different evapo-
total availability destruction and Second Law efficiency are ration temperatures. Multiple evaporation temperatures can
not as pronounced for the realistic case as they were for the make heat transfer in the evaporator more effective than the
ideal case. This is because for the realistic case, the ejector single evaporation temperature if the two evaporators are
does not provide as great of a pressure (and temperature) lift, used to cool the same air stream because the average tem-
and thus, the temperature difference between high- and low- perature difference between the refrigerant and air streams
temperature evaporators is smaller. As a result, the Carnot can be reduced when multiple evaporation temperatures are
COP’s of the single and two evaporation temperature cycles used. Brodie et al. (2012) described how an ejector cycle with
are much closer. two evaporation temperatures can be used for automotive
It can again be seen from Table 5 that the major contributors cabin cooling. It is important to note that a second evapora-
to the differences in total availability destruction in the tion temperature does not necessarily mean that the

Table 5 e Comparison of availability destruction in individual components and total in system for standard two-phase
ejector cycle, COS ejector cycle, DOS ejector cycle, and expansion valve cycle with two evaporation temperatures for the
realistic case.
Availability destruction in Standard two-phase ejector COS ejector DOS ejector Conventional expansion valve
each component [kW] cycle with separator cycle cycle cycle with two evaporation
temperature

Compressor 0.247 0.242 0.242 0.262


Condenser 0.191 0.198 0.198 0.203
Ejector 0.083 0.046 0.080 e
Expansion/metering valve(s) 0.001 0.060 0.026 0.167
High-temperature evaporator e 0.105 0.105 0.105
Low-temperature evaporator 0.185 0.077 0.077 0.077
Evaporator (total) e 0.182 0.182 0.182
System 0.706 0.728 0.728 0.814
Carnot COP 6.95 7.24 7.24 7.24
Second law efficiency 0.67 0.64 0.64 0.59
1230 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2

evaporator would be larger. In the case of automotive cabin to cooling capacity decreases the pressure drop through the
cooling, for example, the same size evaporator could be used, evaporator, which will have a positive impact on system
but the refrigerant flow would be circuited such that the performance. Second, if a heat exchanger design that in-
portion of the evaporator that is downstream in the air flow corporates headers is used, a very low quality fluid would be
would have a lower evaporation temperature than the portion easier to distribute more uniformly. Microchannel heat ex-
of the evaporator that is upstream. Multiple evaporation changers are particularly susceptible to maldistribution, and a
temperatures can also be useful in applications that require flooded evaporator can significantly improve their perfor-
two separate air streams at two different temperatures, mance. Third, some fluids, such as R744, have increased heat
requiring two different refrigerant evaporation temperatures, transfer coefficient at lower qualities, though, as Elbel and
such as applications where it is desired to provide cooling Hrnjak (2004b) showed, reduced pressure drop and improved
effect at both refrigerator and freezer temperatures with a distribution are the main improvement mechanisms. It is
single compressor. important to note that the COS and DOS ejector cycles would
not benefit from this, as none of the evaporators in either of
5.2. Effect of liquidevapor separator and splitting of a the two cycles have very low quality inlet fluid.
two-phase flow Splitting a two-phase flow without phase separation can be
difficult, and if phase separation does occur at the split in the
Another advantage of the COS and DOS ejector cycles is that DOS ejector cycle, it could send a very large amount of liquid
neither of them include a liquidevapor separator. The liq- to only one of the evaporators. If the heat exchangers are not
uidevapor separator can present a problem, as poor separa- sized to accommodate this, it could result in one evaporator
tion can harm the overall performance of the system. having a very superheated exit and the other having a flooded
Specifically, liquid that leaves at the vapor port (going to the exit; neither of these evaporator outlet conditions are gener-
compressor) increases compressor work and decreases cool- ally desirable in this cycle.
ing capacity, both of which will directly contribute to
decreased COP. Liquid entering the compressor can also 5.3. Effect of poor ejector performance
damage the compressor. Vapor that leaves at the liquid port
(going to the evaporator) does not directly affect cooling ca- Operation of a two-phase ejector at off-design conditions or
pacity or compressor work. However, the increased vapor flow poor ejector design are two problems that could make the
through the evaporator can increase low-side pressure drop, ejector fail to entrain suction flow properly. In the standard
which will hurt system performance. Additionally, increased two-phase ejector cycle, the suction flow rate is also the
mass flow at the suction port of the ejector will increase the evaporator flow rate, meaning that if ejector performance is
entrainment ratio of the ejector, and because of the pump-like poor, there may be significantly reduced or close to no flow
nature of the ejector, the pressure increase provided by the through the evaporator, which could drastically harm both
ejector will not be as high; this will lead to lower compressor the cooling capacity and COP of the cycle. Similarly, in the DOS
suction pressure and lower system performance. Lawrence ejector cycle, poor ejector performance could reduce or elim-
and Elbel (2012) presented the results of numerical simula- inate flow through the low-temperature evaporator; the cycle
tions demonstrating that a modest amount inefficiency of the would not be a complete loss, however, as the flow through
liquidevapor separator (about 15% by mass of liquid and vapor the high-temperature evaporator would be affected very little.
not exiting at their respective correct ports) can actually The COS ejector cycle, on the other hand, would not lose flow
decrease the COP of the standard two-phase ejector cycle through either evaporator if the ejector failed to perform well,
below that of the expansion valve cycle. Elbel et al. (2012) as the flow through the low-temperature evaporator would
presented experimental results for a transcritical R744 still be driven by the high pressure liquid out of the condenser.
ejector system showing that an excessive amount of liquid The loss of evaporator flow in the standard and DOS ejector
leaving at the vapor port can decrease COP by as much as cycles could hurt the cycles such that their performance is
5e10%. Depending on the size and design of the liquidevapor actually below that of the expansion valve cycle. However,
separator, as well as the characteristics of the two-phase flow with the COS ejector cycle, even if the ejector does not work at
into the separator, it is possible that poor liquidevapor sepa- all, it would simply result in an isenthalpic expansion of both
ration can have a significant effect on the performance of the fluid streams, in which case the cycle would behave the same
standard two-phase ejector system. If the COS or DOS ejector as an expansion valve cycle with two evaporation tempera-
cycle is used, the issue of separator efficiency is altogether tures; thus, the COP of the COS ejector cycle, theoretically, can
avoided. The liquidevapor separator does provide a means for never be lower than that of an expansion valve cycle with two
storing charge in the standard two-phase ejector cycle. How- evaporation temperatures.
ever, this can also be accomplished in the COS and DOS One phenomenon that has been observed with ejector
ejector cycles by means of a liquid receiver on the high- operation occurs when flow through the suction nozzle is
pressure side of the system after the condenser. reversed; all flow enters the ejector through the motive
The liquidevapor separator does offer a potentially sig- nozzle, but the flow then splits and exits through both the
nificant advantage to the standard two-phase ejector cycle; diffuser and the suction nozzle. This type of operation is often
the separator allows saturated liquid or very low quality fluid referred to as “broken” ejector operation. Because of the high
to be fed into the evaporator. Elbel and Hrnjak (2004b) pointed pressure driving the flow through the low-temperature
out the potential benefits of feeding liquid into an evaporator. evaporator in the COS ejector cycle, this type of ejector oper-
First, the absence of vapor in the flow that does not contribute ation should not occur in this cycle. This type of operation can
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2 1231

occur in the DOS ejector cycle, but in this case, reversed flow introduced; one of the cycles is the standard two-phase
through the suction nozzle would actually help the DOS ejector cycle with a liquidevapor separator, which is the
ejector cycle compared to the case of no flow through the most commonly encountered of the two-phase ejector cycles,
suction nozzle. Similar to the COS ejector cycle, flow would and the other two are the COS and DOS ejector cycles, which
proceed through the low-temperature evaporator in the are encountered far less often in open literature. The cycles
opposite direction, and both flows would pass through the have been compared to each other and to an expansion valve
high-temperature evaporator and the compressor. Note that if cycle in terms of performance based on both the First Law and
the DOS ejector cycle were to operate like this, the evaporator the Second Law. The First Law analysis shows that the three
that was intended to be at a higher temperature would actu- ejector cycles all have the same theoretical COP at a given
ally be at a lower temperature; depending on the application, cooling capacity; this has been shown through numerical
operation with reversed evaporator roles may or may not be simulations as well as algebraic simplification of the COP’s.
acceptable. The three ejector cycles also showed an improved COP
compared to the expansion valve cycle. The Second Law
5.4. Compressor oil return analysis shows that the COS and DOS ejector cycles have the
same theoretical availability destruction and that the throt-
Similar to how the flow arrangement of the COS ejector cycle tling processes in the two cycles actually destroy the same
helps reduce the penalty of poor ejector performance on the amount of availability despite operating across different
cycle, this flow arrangement can also aid the cycle when it pressure differences. The two-phase ejector cycle showed less
comes to oil return. In the standard two-phase ejector cycle, theoretical availability destruction and higher Second Law
oil can collect near the bottom of the separator tank with the efficiency than the COS and DOS ejector cycles.
liquid and end up being sent to the evaporator, reducing Because the three ejector cycles have the same theoretical
evaporator capacity. This can lead to some of the oil just COP, they were analyzed in terms of advantages and disad-
remaining in the evaporator loop of the cycle and failing to vantages that are not reflected in the theoretical COP. The COS
ever return to the compressor. A similar scenario can occur in and DOS ejector cycles are advantageous because they offer
the DOS ejector cycle, especially if the two-phase flow at the the potential for more than one evaporation temperature and
outlet of the diffuser is not split correctly and a large portion of because they do not include a liquidevapor separator. The
the oil goes to the low-temperature evaporator. Too much oil standard two-phase ejector cycle with a liquid vapor separator
in an evaporator can reduce the refrigerant-side heat transfer does offer the advantage of feeding a very low quality fluid
coefficient and increase pressure drop. Not enough oil into the evaporator, potentially improving evaporator perfor-
returning to a compressor can result in dry compressor mance. When comparing the COS and DOS ejector cycles to
operation, which can be very damaging to a compressor. In each other, the COS ejector cycle offers important advantages
the COS ejector cycle, all refrigerant in the system flows when considering oil return and operation at off-design con-
through the compressor, which greatly aids oil return. ditions for the ejector; in fact, it was determined that the COS
ejector cycle COP can, theoretically, never fall below that of an
5.5. Summary of discussion points expansion valve cycle, which cannot be said of the DOS or
standard two-phase ejector cycles. Because of these advan-
It can be concluded from the above analysis that the COS and tages, it may be beneficial to further look into some of these or
DOS ejector cycles offer advantages when compared to the other alternate ejector cycles in future studies.
standard two-phase ejector cycle, namely evaporation at
multiple temperatures as well as the absence of the liquid-
evapor separator. Depending on the design of the evaporator,
Acknowledgment
the very low quality refrigerant entering the evaporator in the
standard two-phase ejector cycle may provide potential ben-
The authors of this paper would like to thank the member
efits for the evaporator not seen in the COS and DOS ejector
companies of the Air Conditioning and Refrigeration Center at
cycles: Improved refrigerant distribution, reduced pressure
the University of Illinois at Urbana-Champaign for their
drop, and (for some fluids) increased refrigerant heat transfer
support.
coefficient. When comparing the COS and DOS ejector cycles,
it is seen that the COS ejector cycle offers a significant
advantage when operating at conditions that are not favorable references
to the ejector. The flow arrangement in the COS ejector cycle
also helps oil return. Because of these advantages, and given
that all three cycles have the same theoretical COP, it seems Bergander, M.J., 2006. Refrigeration cycle with two-phase
that the COS ejector cycle or other alternate two-phase ejector condensing ejector. In: Proceedings of Int. Refrigeration and
cycles may deserve additional attention in future studies. Air Conditioning Conference at Purdue, West Lafayette, IN,
USA, Paper R008.
Brodie, B., Takano, Y., Gocho, M., 2012. Evaporator with integrated
ejector for automotive cabin cooling. In: SAE 2012 World
6. Conclusions Congress & Exhibition, Paper 2012-01-1048. Detroit, MI, USA.
Burk, R., Dürr, G., Feuerecker, G., Kohl, M., Manski, R., Strauß, T.,
Three different two-phase ejector cycles for reduction of 2006. Vorrichtung zur Luftkonditionerung für ein
throttling losses in refrigeration systems have been Kraftfahrzeug. D.E. Patent 10 2005 021 396 A1.
1232 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 2 2 0 e1 2 3 2

Deng, J., Jiang, P., Lu, T., Lu, W., 2007. Particular characteristics of Kornhauser, A.A., 1990. The use of an ejector as a refrigerant
transcritical CO2 refrigeration cycle with an ejector. Appl. expander. In: Proceedings of the 1990 USNCR/IIR-Purdue
Therm. Eng. 27, 381e388. Refrigeration Conference, West Lafayette, IN, pp. 10e19.
Disawas, S., Wongwises, S., 2004. Experimental investigation on Lawrence, N., Elbel, S., 2012. Experimental and analytical
the performance of the refrigeration cycle using a two-phase investigation of automotive ejector air conditioning cycles
ejector was an expansion device. Int. J. Refrigeration 27, using low-pressure refrigerants. In: Proceedings of Int. Air
587e594. Conditioning and Refrigeration Conference at Purdue, West
Domanski, P.A., 1995. Theoretical Evaluation of the Vapor Lafayette, IN, USA, Paper 2118.
Compression Cycle with a Liquid-line/suction-line Heat Lee, J.S., Kim, M.S., Kim, M.S., 2011. Experimental study on the
Exchanger, Economizer, and Ejector. National Institute of improvement of CO2 air conditioning system performance
Standards and Technology, Gaithersburg, MD, USA, NISTIR using an ejector. Int. J. Refrigeration 34, 1614e1625.
5606. Li, D., Groll, E.A., 2005. Transcritical CO2 refrigeration cycle with
Elbel, S., 2011. Historical and present developments of ejector ejector-expansion device. Int. J. Refrigeration 28, 766e773.
refrigeration systems with emphasis on transcritical carbon Liu, J.P., Chen, J.P., Chen, Z.J., 2002. Thermodynamic analysis on
dioxide air-conditioning applications. Int. J. Refrigeration 34, trans-critical R744 vapor-compression/ejection hybrid
1545e1561. refrigeration cycle. In: Proceedings of 5th IIR-Gustav Lorentzen
Elbel, S.W., Hrnjak, P.S., 2004a. Effect of internal heat exchanger Conference on Natural Working Fluids, Guangzhou, China, pp.
on performance of transcritical CO2 systems with ejector. In: 184e188.
Proceedings of Int. Refrigeration and Air Conditioning Liu, F., Groll, E.A., Li, D., 2012. Investigation on performance of
Conference at Purdue, West Lafayette, IN, USA, Paper R166. variable geometry ejectors for CO2 refrigeration cycles. Energy
Elbel, S., Hrnjak, P., 2004b. Flash gas bypass for improving the 45, 829e839.
performance of transcritical R744 systems that use Moran, M.J., Shapiro, H.N., 2008. Fundamentals of Engineering
microchannel heat evaporators. Int. J. Refrigeration 27, Thermodynamics, sixth ed. John Wiley & Sons, Hoboken.
724e735. Nakagawa, M., Takeuchi, H., 1998, Performance of two-phase
Elbel, S., Hrnjak, P., 2008. Experimental validation of a prototype ejector in refrigeration cycle. In: Proceedings of 3rd Int.
ejector designed to reduce throttling losses encountered in Conference on Multiphase Flow, Lyon, France, Paper 382.
transcritical R744 system operation. Int. J. Refrigeration 31, Nakagawa, M., Marasigan, A.R., Matsukawa, T., 2011.
411e422. Experimental analysis on the effect of internal heat
Elbel, S., Reichle, M., Bowers, C., Hrnjak, P., 2012. Integration of a exchangers in transcritical CO2 refrigeration cycle with two-
two-phase ejector into a compact, lightweight unitary-type phase ejector. Int. J. Refrigeration 34, 1577e1586.
air-conditioner using R744 for energy efficient operation in hot Newton, A.B., 1972a. Capacity Control for Multiple-Phase Ejector
climates. In: Proceedings of IIR-Gustav Lorentzen Conference Refrigerating Systems. U.S. 3,670,519.
on Natural Refrigerants, Delft, The Netherlands, Paper 180. Newton, A.B., 1972b. Controls for Multiple-Phase Ejector
Gay, N.H., 1931. Refrigerating System. U.S. 1,836,318. Refrigerating Systems. U.S. 3,701,264.
Harrell, G.S., Kornhauser, A.A., 1995. Performance tests of a two Oshitani, H., Yamanaka, Y., Takeuchi, H., Kusano, K., Ikegami, M.,
phase ejector. In: Proceedings of Int. Energy Conversion Takano, Y., Ishizaka, N., Sugiura, T., 2005. Vapor Compression
Engineering Conference, Orlando, Florida, USA, Paper CT-69. Cycle Having Ejector. U.S. Patent Application Publication US
Kemper, C.A., Harper, G.F., Brown, G.A., 1966. Multiple-Phase 2005/0268644 A1.
Ejector Refrigerating System. U.S. 3,277,660. Varga, S., Oliveira, A.C., Diaconu, B., 2009. Numerical assessment
Klein, S.A., 2012. Engineering Equation Solver Academic of steam ejector efficiencies using CFD. Int. J. Refrigeration 32,
Profession V9.206. F-Chart Software. 1203e1211.

You might also like