You are on page 1of 9

Hilti Technical Data for HAC-C Mounting channels (hot-rolled, straight) P1I9

HAC-C Mounting channels in combination with HBC: black channel

Installation condition: Channel directly welded to a steel construction Channel profile HBC

Naming example: Anchor channel HAC-C(-I) 40/22 300 F


Anchor channel Channel bolt
Anchor
Type Material Coating Type Size Material Steel strength
type
M10 4.6G, 4.6F, A4-70
HAC-C 40/22 Carbon HBC-40/22 M12
No or M16 Carbon or stainless steel. Steel grade according to
No coating, black channel
anchors stainless M12 EN ISO 898-1 or EN ISO 3506 8.8G, 8.8F, A4-70
HAC-C 50/30 steel HBC-50/30 M16
HAC-C 52/34
M20
Hilti Technical Data for HAC-C Mounting channels (hot-rolled, straight) P2I9

Channel profile and anchor


Table 1: Dimensions of channel profile

bch hch tnom d f A Iy Iz e2


Anchor channel
[mm] [mm2] [mm4]
HAC-C 40/22 39,5 23,0 2,4 18,0 6,0 271,9 20087 59724 12,11
HAC-C 50/30 49,0 30,0 2,75 22,5 8,1 422,8 53652 144567 15,22
HAC-C 52/34 52,5 34,0 4,0 22,5 11,5 653,2 97606 244660 16,79

HAC-C 40/22, HAC-C 50/30, HAC-C 52/34


Channel bolts
Table 2: Dimensions of channel bolt

Dimensions
Anchor Channel bolt Material/
b1 b2 k d l
channel type Coating
[mm]
10,5 10 n.a. 4.6, A4-70 1)
14,0 40,60, 80 8.8F
HAC-C 40/22 HBC-40/22 33,0 12
11,5 40, 50, 60, 80 A4-70
17,0 16 50, 60, 80, 100 8.8F, A4-70
14,5 12 50, 60, 80, 100 8.8F, A4-70
HAC-C 50/30 17,0
HBC-50/30 42,0 16 50, 60, 80, 100, 125 8.8F, A4-70
HAC-C 52/34 15,5
21,0 20 60, 80, 100, 125 8.8F, A4-70

Technical data is available for galvanized as well as for hot-dip galvanized channel bolts. Currently the galvanized channel bolts are not part of the product portfolio.
n.a: not available
1)
Technical data is available, but the product is currently not part of the portfolio
Hilti Technical Data for HAC-C Mounting channels (hot-rolled, straight) P3I9

Specifications of intended use


Table 3: Technical data and design

Technical data and design method


Region Technical data Design method Comment Base material

Europe Hilti technical data Hilti design method Static (2D) Steel construction
Hilti Technical Data for HAC-C Mounting channels (hot-rolled, straight) P4I9

HAC-C Mounting System: Hilti Technical data


Table 4: Installation parameters for anchor channel

Anchor channel HAC-C 40/22 50/30 52/34


Minimum welding spacing smin -
Maximum welding spacing smax 250

End spacing x [mm] 25 1) 35

Minimum channel length lmin 150 170

Welding minimum length lw Welding design acc. EN 1993-1-8


1) The end spacing may be increased from 25mm to 35mm

Table 5: Minimum spacing for channel bolts

Channel bolt M10 M12 M16 M20

Minimum spacing between channel bolts scbo,min [mm] 50 60 80 100


Hilti Technical Data for HAC-C Mounting channels (hot-rolled, straight) P5I9

Table 6: Required installation torque Tinst for HBC


Tinst [Nm]
Channel bolt General condition Steel - steel contact
4.6, 8.8, A4-70 4.6 8.8 A4-70
M10 15 13 - 22
40/22 M12 25 45 50
M16 30 100 90
M12 25 -
15
45 50
50/30 M16 30 100 130
M20 10 60 360 250

Key
1 washer
2 fixture
3 steel plate
4 weldings
Hilti Technical Data for HAC-C Mounting channels (hot-rolled, straight) P6I9

Table 7: Characteristic resistances under tension load (N) – steel failure of mounting channel

Anchor channel HAC-C 40/22 50/30 52/34

Steel failure: Local failure by flexure of channel lips

Characteristic spacing of the channel bolts for NRk,s,l sl,N [mm] 79 98 105

Characteristic resistance N0Rk,s,l [kN] 35 36 65

Partial safety factor Ms,l [-] 1,8

Table 8: Characteristic flexural resistance of channel under tension load (N)

Anchor channel HAC-C 40/22 50/30 52/34


Steel failure: Failure by flexure of channel
carbon steel
Characteristic flexural resistance of channel MRk,s,flex [Nm] 1013 2084 3435
stainless steel

Partial safety factor Ms,flex [-] 1,15

Table 9: Displacements under tension load (N)

Anchor channel HAC-C 40/22 50/30 52/34

Tension load N [kN] 13,9 14,3 25,8

Short time displacement 1) N0 [mm] 2,3 2,2 1,4

Long time displacement 1) N∞ [mm] 4,6 4,4 2,8


1)
Displacements in midspan of the anchor channel, including slip of channel bolt, deformation of channel lips, bending of the channel.
Hilti Technical Data for HAC-C Mounting channels (hot-rolled, straight) P7I9

Table 10: Characteristic resistances under shear load (Vy) – steel failure of anchor channel

Anchor channel HAC-C 40/22 50/30 52/34

Steel failure: Local failure by flexure of channel lips

Characteristic resistance V0Rk,s,l,y [kN] 26,0 40,3 71,5

Critical spacing scr,V [mm] 135 160 110

Partial safety factor Ms,l [-] 1,8

Table 11: Displacements under shear load (Vy)

Anchor channel HAC-C 40/22 50/30 52/34

Tension load Vy [kN]

Short time displacement 1) V0,y [mm]

Long time displacement 1) V∞,y [mm]


1)
Displacements in midspan of the anchor channel, including slip of channel bolt, deformation of channel lips, bending of the channel.

Table 12: Characteristic resistances under combined tension (N) and shear load (Vy)

Anchor channel 40/22 50/30 52/34

Steel failure of channel lips and flexural failure of channel


Product factor k13 [-] 1,0 1)
1)
k13 can be taken as 2,0 if VRd,s,l is limited to NRd,s,l
Hilti Technical Data for HAC-C Mounting channels (hot-rolled, straight) P8I9

Table 13: Characteristic resistances under tension (N) and shear (Vy) load – steel failure of Hilti channel bolt type HBC

Channel bolt M10 M12 M16 M20


Steel failure
4.6 23,2 -
HBC-40/22 8.8 - 35,4 55,8
-
A4-70 20,5 58,6 91,0
Characteristic tension resistance NRk,s [kN]
4.6 -
HBC-50/30 8.8 35,4 55,8 183,1
-
A4-70 58,6 109,0 129,0
4.6 2,00
HBC-40/22
Partial safety factor Ms [-] 8.8 1,50
HBC-50/30
A4-70 1,87
4.6 13,9 -
HBC-40/22 8.8 - 33,7 62,8
-
A4-70 24,4 35,4 65,9
Characteristic shear resistance VRk,s [kN]
4.6 -
HBC-50/30 8.8 33,7 62,8 98,0
-
A4-70 35,4 65,9 102,9
4.6 1,67
HBC-40/22
Partial safety factor Ms [-] 8.8 1,25
HBC-50/30
A4-70 1,56
Hilti Technical Data for HAC-C Mounting channels (hot-rolled, straight) P9I9

Table 14: Characteristic resistances under shear load with lever arm (Vy) – steel failure of Hilti channel bolt type HBC

Channel bolt M10 M12 M16 M20


Steel failure
4.6,1 29,9 -
HBC-40/22
Characteristic flexural resistance M0Rk,s [Nm] 8.8,2 - 104,8 266,4 519,3
HBC-50/30
A4-70 52,3 91,7 233,1 454,4
4.6 1,67
HBC-40/22
Partial safety factor Ms [-] 8.8 1,25
HBC-50/30
A4-70 1,56
HBC-40/22 40/22 24,3 25,7 27,3 -
Internal lever arm a [mm]
HBC-50/30 50/30 - 29,9 31,7 33,9