You are on page 1of 16

MiCOM P124

Self- and Dual-Powered


Overcurrent Relays

MiCOM P124
Self- and Dual-Powered
Overcurrent Relays
MICOM P124
Two protection relays to ensure 100% safety

The following two models are • a capacitance discharge output


available: capable of putting out sufficient
• Self-powered P124 power to a striker releasing the
actuating mechanism of the
• Dual-powered P124.
circuit-breaker,
The self-powered P124 model offers
• a changeover contact relay
a simple and low-cost solution when
output capable of sending an
no external auxiliary power supply
order directly to the circuit-
is available.
breaker coil.
The dual-powered P124 relay, in
The operator interface is user-
addition to its protection functions
friendly and simple to apply. A
P124 Self-powered model and when powered by an external
back-lit LCD display ensures easy
auxiliary source, transmits
reading, even when there is
recording and measuring data to a
insufficient ambient light.
supervisor via the communications.
Should the auxiliary power supply The front panel comprises an
fail, the protection and tripping electromagnetic bistable flag for
functions remain fully operational. tripping indication. As an option of
the dual-powered model, four
These two types of MiCOM P124
additional magnetic indicator flags
relays take the power necessary to
can be assigned by the user.
their operating from the line current
transformers. Depending on the model, one or
several LEDs indicate correct
The power supply to the electronic
operation of the relay and other
circuits of the MiCOM P124s has
information concerning protection
P124 Dual-powered model been optimised so as to trigger the
of the electrical system.
circuit-breaker with a load current
of 0.2 In (sensitive version) on at Even when the circuit-breaker is
least one phase. open, i.e. the relay is no longer
Description supplied with a load current,
In the MiCOM range, the P124 The hardware architecture and
settings can be applied thanks to a
overcurrent protection relays offer software algorithms have been
simple and unexpensive battery
the protection and supervision studied to operate on very short
box.
functions for a wide variety of high failure detection times, so that,
starting from a load current of 0.2 On one side, this battery box is
and medium voltage electrical connected to the RS232 port on the
networks. In for the sensitive model or 0.4 In
for the standard model; tripping relay front panel and on the other
They provide efficient protection for occurs within no more than 30 ms. to the PC containing the support
industrial plants, utilities’ distribution software.
substations or customers and can The MiCOM P124 relays are
equipped with two types of circuit- The support software allows
be used as either main or backup extraction of the data stored in the
protection. breaker trip outputs, fully
independent from an external relay for settings, measurements
They have been designed for auxiliary power supply: and fault records. The disturbance
complete, fully safe protection, and event files of the dual-powered
without requiring an auxiliary model can also be uploaded.
power supply.

2
The two models offer a wide range (MODBUS, IEC60870-5-103, etc.). The various functions provided by
of overcurrent protection functions Some of these additional functions these two models are described in
without requiring an external are operational only when an the following table.
auxiliary supply: three independent auxiliary power supply is available. The MiCOM P124 relays are
phase stages, three independent In the event of loss of this power present in the same 4U-30 TE
earth stages, eleven groups of IDMT supply, the performances of the shallow metal case for mounting
curves and two thermal overload P124 dual-powered relay become either in a rack or a cabinet.
stages. equivalent to those of the self-
The dual-powered model proposes powered P124 model.
additional protection and
automation functions, such as for
instance communications

Models available

Function ANSI Self-powered Dual-powered


Codes MiCOM MiCOM
Three-phase non directional overcurrent
3 independent thresholds 50/51 X X
Phase-earth non directional overcurrent
3 independent thresholds 50N/51N X X
Thermal overload
(true RMS) 2 independent thresholds 49 X X
Undercurrent 37 X (note 1)
Negative phase sequence overcurrent 46 X
Broken conductor detection (I2/I1) X

Blocking logic X (note 1)


Selective relay scheme logic X (note 1)
Cold load pickup X (note 1)
Setting groups 1 2
Assignable inputs/outputs X (note 1)
Autoreclose option (4 shots) 79 X (note 1)
Output for striker triggering X X
Changeover contact output for trip coil X X
Bistable magnetic indicator flag
for trip indication X X
4 extra magnetic flags option X
Output relay latching 86 X (note 1)
Circuit breaker failure 50 BF X
Circuit breaker supervision X
Measurements (true RMS) X X
Peak and rolling values X X
Event records X (note 1)
Fault records X X
Disturbance records X (note 1)
Rear port RS485 communications X (note 1)
Front port RS232 communications X X

Note 1: Function not available if auxiliary power supply fails.

3
Protection and control a load current of 0.2In on at least Thermal overload (49)
one phase (starting value of the Transformers and cables must be
Time-delayed phase
P124 relay sensitive version), or protected to account for their
overcurrent (51)
0.4In on at least one phase particular thermal characteristics.
The MiCOM P124 relays provide (starting value of P124 relay in the
three phase current inputs. Three The MiCOM P124 relays include a
standard version). This thermal overload element based on
independent stages are available.
instantaneous information is the true RMS value of the current.
For the first stage, the user may generated within 60 ms of the Alarm and overload thresholds as
select among 11 different types of circuit-breaker opening (close-on-to- well as thermal time constants are
curves (IEEE/ANSI, IEC, RI). fault case). These correspond to the fully programmable to match each
For each curve model a selection of tripping time if the corresponding device requirement.
60 different TMS values are timer is set to zero. Undercurrent (37)
available to optimise fault detection For the dual-powered model, each
and shorten tripping time in co- MiCOM P124 dual-powered relays
instantaneous item of information provide undercurrent protection.
ordination with fuses, motors,
can be assigned by the user to the This function allows typical
feeders, transformers and other
output contacts, the four LEDs and applications such as loss of load
devices.
the four magnetic indicator flags on and circuit breaker failure
The second and third stages have the front panel. detection.
independent settings with
adjustable definite time tripping. Time-delayed earth fault Negative sequence
(51N) overcurrent (46)
The time delays are programmable
from 0 to 180s thus providing Earth fault detection is identical to In order to maximise the operation
maximum selectivity. that of the time-delayed phase of electrical systems, the dual-
overcurrent. powered MiCOM P124 relays
The phase current range is
include a negative sequence
adjustable independently for each Three independent earth fault
overcurrent protection function.
stage from 0.1 to 40 times the stages can be selected. For the first
rated phase current (first threshold stage, the user can select either any This programmable function is
limited at 4In). of the 11 families of curves and particularly well suited for detecting
TMS values or a definite time any phase unbalance conditions.
All the phase overcurrent settings
setting. Instantaneous and time-delayed (DT
are fully programmable using the
or IDMT) negative sequence
front panel operator interface, the Earth current range is adjustable
overcurrent stages are the same as
support software front connection 0.002 to 40 times the rated earth for the phase overcurrent settings.
and, for the dual-powered model, current to allow maximum sensitivity
a remote communication control for earth fault detection. Broken conductor
system. One type of unbalanced fault,
The earth current originates either
Instantaneous phase from a CT core of sufficient power which may occur on the system, is
overcurrent (50) (usable with the 0.4 In starting an open circuit fault. This can arise
current standard model only), or a from broken conductors,
For each phase overcurrent stage,
maloperation of single phase
the instantaneous information is residual connection of the three line
switchgear, or the blowing of fuses.
generated within 30 ms after the CTs.
The dual-powered MiCOM P124
threshold has been exceeded, from Instantaneous earth fault relays incorporate an element
(50N) which measures the ratio of
Just as for the phase faults, the negative to positive sequence
MiCOM P124 relays generate current (I2/I1). This fully
instantaneous data for each earth programmable function allows
Ith higher sensitivity than negative
fault stage, with the same
Time

sequence overcurrent detection.


I>
characteristics.
t>
For the dual-powered model, the Blocking logic
I >> t >>
I<
I >>> t >>> instantaneous earth fault stages can When MiCOM relays are used in
be set by the user at the output electrical networks, the
Current
contacts, on the four LEDs and the management of protection relays
four magnetic indicator flags on the must take surrounding devices into
Figure 1: Overcurrent stages front panel. consideration.

4
The MiCOM P124 dual-powered This function is inactive in the event • another changeover contact
relays have two programmable of auxiliary power supply failure. relay output with a high breaking
logic inputs, which when energised capacity to trip the circuit-breaker
Setting groups
“block” the associated protection coil.
time-delays and, upon de- The dual-powered MiCOM P124
energising and if the fault is still relays have two selectable setting
present, to resume the timers counts groups including all the protection
from the “blocked” value. This and monitoring functions.
function is deactivated in the event When the auxiliary power supply is
of auxiliary power supply loss. present, group 1 is switched over to
group 2 either by energising a
dedicated logic input or through the
front panel operator interface , or
by local (RS232) or remote (RS485)
communication.
Switching from one setting group to
the other is achieved only if no
protection or control function –
except thermal overload – is
running in order to prevent
unnecessary tripping. Figure 4: MiCOM P124 adapted
to a striker
Assignable inputs and
outputs Optional autorecloser (79)
Figure 2: Broken Conductor The dual-powered MiCOM P124
Detection MiCOM P124 dual-powered relays
relays have seven output relays with include an optional 4 shot
unbiased changeover contacts and autorecloser. All programmed
Selective relay scheme logic five opto-isolated logic inputs. All protection functions may start any
the logic inputs and outputs (except of the shots independently and the
In a high performance electrical
for the hardware watchdog RL0 user can program which functions
network, the primary objective is to
relay) can be assigned by the user. are allowed to trip after any of the
reduce outages. The dual-powered
All the logic data available in the shots. Dead and reclaim times are
MiCOM P124 relays allow a logic
relays can be assigned and freely adjustable.
order sent by a downstream relay
combined with the different logic
to be considered, by increasing the The front panel LEDs can be set to
outputs.
trip time delay, in order to match the status of the autorecloser
selectively isolate the faulted A counter stores the number of
section. reclose commands, incremented
400
The selective scheme logic is an with each reclose order. This
alternative for operators more 300
information can be displayed
Current (% of In)

familiar with this type of selectivity 200 locally or remotely.


than with blocking logic . 100
Nominal setting
Naturally, this function can be
Cold load pickup activated only when the auxiliary
0 1 2 3 4 5 6 Time
power supply is present.
When a feeder is loaded after a
long outage, all connected devices Figure 3: Cold load pickup curve Output relay latching (86)
such as transformers will call for an
This function is available only for
over energisation current, over the
the dual-powered versions of the
nominal setting, during a short time.
Tripping outputs MiCOM P124 relay.
To prevent unwanted tripping,
The MiCOM P124 relays have two All the assignable output relays,
MiCOM P124 relays have a cold
types of tripping outputs that are including tripping, can be kept
load pickup function which
entirely independent from any closed after the fault has
automatically increases the
auxiliary supply: disappeared.
standard settings during a
dedicated adjustable time. After a • a capacitance discharge output This latching function can be reset
successful close, all settings are capable of supplying a striker either through the front panel, by a
returned to their nominal values. with an energy of 20mJ at 12 logic input or the local (RS232) or
volts. remote (RS485) communications.

5
Monitoring functions Disturbance recording User interface
offered by the dual- Five 3-second records can be saved
powered model in the MiCOM relays. Front panel and menus
The current sampling frequency is All functions including protection
Circuit breaker failure 1600 Hz. The different recordings automation, communication, LEDs,
protection can be extracted remotely (RS 485) inputs and outputs can be
or locally (RS232). programmed and modified using
Circuit-breaker failure protection
built into the MiCOM P124 dual- the front panel LCD and 7-key
powered relays allows tripping of keypad. The 32 alphanumerical
upstream circuit breakers to ensure back-lit LCD display provides the
fault clearance. user with key information (faults,
measurements, settings, etc.).
This function monitors the opening
time of the three poles of the circuit- The menus have a pull-down
breaker to ensure that they stay structure for easy use and quick
within a settable time window. access to any data.

Circuit-breaker maintenance Dedicated LEDs


Figure 5: Analysis of disturbance
Circuit-breaker preventive
records files with A Healthy LED on the front panel of
WINDR MANAGER
maintenance is the advanced the MiCOM P124 relays indicates
function provided by the MiCOM that the relay is correctly supplied
P124 relays. with an adequate line current.
Measurements In addition, for the dual-powered
The currents, tripping and closing
times are recorded and the user MiCOM P124 relays monitor model, three LEDs indicate the relay
can set the alarm thresholds permanently all of the current condition (Trip, Alarm, Watchdog).
according on the circuit-breaker. inputs, calculate the frequency and
Assignable LEDs
the line currents, display the values
Broken current information per (dual-powered model only)
on the LCD display and store the
phase is stored and can be To facilitate identification of
measurements in memory.
retrieved for consultation. electrical faults, 4 LEDs can be
The measured values are true RMS
programmed by the user. Each LED
Trip circuit supervision up to the 10th harmonic.
can be activated by one or a
The MiCOM P124 relay constantly The user can set the measurement combination of several thresholds or
monitors the trip circuit and ensures and regular storage of the peak by a logic input.
that it is available. The operator and rolling demand. These values
can easily view this information, are saved and sent to the operator Dedicated magnetic indicator
both locally and remotely, and upon local (RS232) or remote flag
optimise switchgear maintenance. (RS485) request. The front panel also features a
bistable magnetic flag showing
Event recording Fault recording when a tripping order has been
The dual-powered model of the The two MiCOM P124 models issued to the cirduit-breaker.
P124 relay logs the different state record the 5 most recent system
changes affecting the logic inputs faults. The faulted phase, the origin
and outputs. All these events are of the fault, together with the
time-tagged to 1ms. Up to 75 magnitude, are available on the
events are stored. That database display and can be retrieved by the
can be consulted or sent to the support software and the front
operator via a local (RS232) or panel.
remote (RS485) request.
In addition, the dual-powered
model offers the following functions:
time-tagging of all parameters,
status of logic inputs and outputs
and remote retrieval of stored
information.

6
Assignable magnetic Communication RS232 Hardware
indicator flags An RS232 port is available on the The MiCOM P124 relays are
(dual-powered model only) front panel of the MiCOM P124 numerical protection and control
In order to display the faults even relays for downloading a software relays.
when the auxiliary power is down, version (for updating, changing
Case
four additional bistable magnetic languages, etc) and connecting the
flags show an exact replica of the PC equipped with the support The relays have a drawout metal
four programmable LEDs. software. 4U shallow case. All the CT inputs
are short-circuited if the active unit
Fully WINDOWSTM compatible
is withdrawn from the case. All
(3.1, 95, 97 and NT), the support
MiCOM relays can be in panel or
software allows easy setting of
rack mounted.
MiCOM P124 relays in addition to
uploading of event records, fault They require no handling
records, disturbance records, operations, since all the settings are
settings or measurements, for onsite put in through the operator
use or ulterior processing. interface.

Battery box Wiring


In the event of the load current External connections are made via
falling to less than the minimum MIDOS type terminal blocks. Each
current needed to supply the connection includes 2 x 6.35mm
MiCOM P124 relays and the Faston and one M4 screw fixing.
Figure 6: Front panel of the auxiliary power supply failing The wiring for all both MiCOM
MICOM P124 relay,
dual-powered model simultaneously for the dual-powered P124 models is standard to provide
model, a power supply battery box maximum compatibility.
is available to the user, thus
ensuring temporary supply to the
relay to consult or modify data.
RS485 communications
The dual-powered MiCOM P124
includes an RS485 communication
rear port. This port is available for
MODBUSTM, Courier, DNP3 or
IEC 60870-5-103 protocols.
MiCOM relays can transmit to the
local monitoring system (e.g.
MiCOM S10) or remotely to the
SCADA settings, measurements,
alarms, faults, events and
disturbance records. The Figure 7: Battery box MiCOM E1
communication parameters (relay
address, data rate, parity, etc.) can
be programmed using the operator
interface front port.
A communication failure does not
affect the protection functions of the
MiCOM relays.

7
A

Variant: connection to 3 CTs and 1 core balanced CT A


P2 P1
3 phase CTs connection
B S2 S1

A
P2 P1 P2 P1 C B C
Phase rotation
B S2 S1
49
C 37
S2 S1
49 1 A or 5A 35
50
RL 0 Watchdog
1 A or 5A 36
50
44
51 51 42 Trip output
RL 1
1 A or 5A
40
1 A or 5A
52
39
52 + Trip output
53 41 for striker
1 A or 5A
-
54
53
1 A or 5A
56 54
1 A or 5 A
55
- 48
1 A or 5 A
56
47
-
55
48
CAUTION: Inputs 55/56 used in the standard 1 A or 5 A
version only (min. current for relay powering: 0.4 In) 47
-
8

Variant: connection to 2 CTs and 1 core balanced CT


Case earth
A
P2 P1 P2

S2 S1
P1

Module terminal blocks P124 connection

Self-powered model
B
C viewed from rear
S2 S1
49
1 A or 5A 29 30
50
31 32

51 33 34
1 A or 5A 35 36
52
37 38

39 40
53
1 A or 5A 41 42
54
43 44

45 46
Note s :
56 (1) (a) CT shorting links make before (b) and (c) disconnect
47 48
1 A or 5 A
55 49 50 (b) Short terminals break before (c)
- 48
51 52 (c ) Long terminals
47
53 54 (d) Pins terminals (p c b type)

55 56
CAUTION : Connection available in the standard (2) Connection between CT and ground is typical only
version only (min. current for relay powering: 0.4 In)

Relay shown unpowered (no self-powering)


Figure 8: External connection diagram for MiCOM P124, self-powered model
A
Variant: connection to 3 CTs and 1 core balanced CT A
P2

S2 S1
P1
3 phase CTs connection
B
A
P2 P1 P2 P1
C C
B 49
B S2 S1
Phase rotation
C 37
S2 S1
49
1A or 5A
50 RL0 35 Watchdog
1A or 5A 36
50
44
51 Trip output
51
42
RL1
1A or 5A 40
1A or 5A 6
52
52 4 Programmable output
RL2 2
12
53 53 10 Programmable output
RL3 8
1A or 5A
54
1A or 5A 22
54 20 Programmable output
RL4 18
56 28
1A or 5A 26 Programmable output
56 RL5
55 24
- 48 5
1A or 5A 55 3 Programmable output
RL6 1
47 48
1A or 5A
-
47 39 +
CAUTION: Inputs 55/56 used in the standard - Trip output
version only (min. current for relay powering: 0.4 In) 9+ P124 41 -
for striker

Assignable input L1 11-


13+ Dual-powered
Assignable input L2 15-
17+
model 29
Case earth
connection
Assignable input L3
9

19-
21+ * 30
Variant: connection to 2 CTs and 1 core balanced CT Assignable input L4 +
23- 31 RS485 communications port
25+ -
P2 P1 P2 P1
A Assignable input L5 32
27-
B S2 S1

C 33 34
S2 S1
49
+ -
1A or 5A Auxiliary (*) Terminating resistor for
Module terminal blocks
50 voltage the last relay to be connected
viewed from rear between 30-32
51
1 2 29 30
1A or 5A
52 3 4 31 32
5 6 33 34

53
7 8 35 36

1A or 5A 9 10 37 38
54 11 39 40
12
13 14 41 42
56
15 16 43 44
1A or 5A
55 17 18 45 46 Notes :
- 48 19 20 47 48 (1) (a) CT shorting links make before (b) and (c) disconnect
1A or 5A
21 22 49 50
47 (b) Short terminals break before (c)
23 24 51 52
(c) Long terminals
25 26 53 54 (d) Pins terminals (p c b type)
CAUTION : Connection available in the standard
27 28 55 56
version only (min. current for relay powering: 0.4 In)
(2) Connection between CT and ground is typical only

Relay shown unpowered (no external power supply nor self-powering)


Figure9 : External connection diagram for MiCOM P124, dual-powered model
Technical data Accuracy Thermal overload

Inputs Protection thresholds ±2% Ranges Iθ > 0.2 to 3.2In

Phase current inputs Time delay ±2% with a Alarm and trip
1A or 5A (specify on order) minimum of 10ms 50 to 200% x θ
Earth current inputs Measurements typical
Definite time 1 to 200 mn,
1A or 5A (specify on order) ±0.2% at In
in 1mn steps
Rated frequency 50/60 Hz Overcurrent settings Cold load pickup
Auxiliary power supply Uaux Phase current Range 20 to 500% of
24–60Vdc I> 0.1 to 4In earth and phase
48–150Vdc stages
I>>, I>>> 0.5 to 40In
130–250Vdc/
Earth current 0.002 to 1Ion Time-delay 0 to 3600s,
100-250Vac, 50/60Hz in 0.1s steps
0.01 to 8Ion
Minimum level of current Undercurrent
required for relay powering 0.1 to 40Ion
2 independent thresholds:
Selection on order (cortec code) Note : Some limitations exist when
range 2 to 100%In
between two versions: I> (Ie>) is used with IDMT curves
Standard version: 0.4In see Technical Guide. Negative sequence
Instantaneous time (phase & earth) overcurrent
Sensitive version: 0.2In
<30 ms for an initial Range I2> 0.1 to 40In
Burdens current of 0.2In (sensitive
Time-delays
Consumption per phase version) or of 0.4In
Definite time 0 to 150s
(standard version) Inverse time (curves identical
In=1A or In=5A
< 60ms for zero initial to thresholds I>
Standard version at 0.4 In current
or Ie>)
Phase 2.5VA Drop-out time 30ms
Earth 2.5VA Broken conductor
Overcurrent time settings
Sensitive version at 0.2In Threshold I2/I1
Phase (tI>, tI>>, tI>>>)
Phase 5VA 20% to 200%,
0 ms to 180 s in 1% steps
Earth 5VA
Earth (tIe>, tIe>>, tIe>>>) Time-delay 0 to 14400s,
Auxiliary power supply (dual-
powered model) 0 ms to 180 s in 1s steps
dc: 3W on standby IDMT curves IEC type: Autorecloser
+0.25W per energised relay Short time inverse (A),
Dead times 1 & 2
ac: 6VA Standard Inverse (IEC),
0.01 to 300s,
Very inverse (IEC)
Logic input (dual-powered model) in 0.01s steps
Extremely inverse (IEC)
10mA per logic input Dead times 3 & 4
Long time inverse (A)
Thermal withstand 0.01 to 600s,
IEEE/ANSI type:
in 0.01s steps
Current inputs: Short time inverse (CO2)
1s 100 x In/Ion Moderately inverse (ANSI) Reclaim time
Inverse (CO8) 0.02 to 600s,
2s 40 x In/Ion in 0.01s steps
Very inverse (ANSI)
Continuous 3 x In/Ion in Extremely inverse (ANSI) Breaker failure
standard version Electromechanical type (RI) Timer tBF 10ms to 10s,
2 x In/Ion in Time multiplier setting (TMS) in 10ms steps
sensitive version 0.025 to 1.5, step 0.025 Detection <15ms
Reset time IDMT curves:
Trip circuit supervision
Short time inverse (CO2)
Moderately inverse (ANSI) Timer tSup 100ms to 10s,
Inverse (CO8) in 50 ms steps
Very inverse (ANSI)
Extremely inverse (ANSI)

10
Ancillary timers Electrostatic discharge • Thermal overload (49)
2 independent timers: IEC 61000-4-2 • Broken conductor detection
8kV, class 4
tAUX 1 and tAUX 2 • Output relay latching (86)
0 to 200s, RFI
• True RMS values display
in 10ms steps. ANSI C37.90.2 35 V/m
IEC 61000-4-3 10 V/m • Fault recorder with the last 5
Signalling output relay faults
Environment
Current With the addition of an external
Temperature IEC 60255-6
make: 30A ; 3s auxiliary source, the following
Storage –25°C to +70°C
functions become available:
carry: 5 A continuous Operating range
–25°C to +55°C • 4 independent shot autorecloser
break: 135Vdc, 0.3A (L/R=30 ms)
(79)
250Vdc, Relative humidity
50W resistive IEC 60068-2-3 56 days • Circuit breaker monitoring
25 W inductive at 93% RH and 40°C • Trip circuit supervision
(L/R=40ms) 220Vac,
Enclosure protection • Circuit breaker failure detection
5A (P.F=0,6)
IEC 60529 IP 52, IK 07 (50 BF)
Mechanical withstand
Vibration • Event recorder with the last 75
> 100,000 operations
IEC 60255-21-1 events, 1ms time stamped.
Tripping output relay (RL1) Response and endurance, class 2 • Recording of measurements and
Current Shock and bumps time-tagged records of the 5 most
make: 30A ; 3s IEC 60255-21-11 class 1 recent faults

carry: 8 A continuous Seismic • Disturbance recorder with


IEC 60255-21-3, class 1 storage of 5 records for 3
break: 300Vdc, 100W
seconds each, sampled at
resistive or 50W EMC compliance
1600Hz
inductive (L/R=40ms) LV and EMC directive in
250 V AC 5A (P.F=0,5) accordance with IEC 60947-1 • A RS485 rear port compatible
with MODBUS, Courier, DNP3
Mechanical withstand Outline description or IEC 60870-5-103
> 100,000 operations
Self-powered phase and earth The user interface includes:
Standards numerical overcurrent relay in
• A 32 characters back-lit display
Dielectric withstand IEC 60255-5 drawout 4U metal case.
• An RS232 port on the front panel
2kV common mode The following functions are
for downloading application
1kV differential mode available:
software and a setting software
High voltage impulse IEC 60255-5 • Tripping of the circuit-breaker is program on PC.
5kV common mode entirely independent from any
• Possibility of setting the relay
1kV differential mode external auxiliary supply.
with a supply device via front
Insulation resistance IEC 60255-5 • 3 independent phase stages panel RS232 port.
> 1000MΩ (instantaneous and time-delayed)
(50/51)
HF disturbance IEC 61000-4-1
2.5kV common mode, class 3 • 3 independent earth stages
1kV differential mode, class 3 (instantaneous and time-delayed)
(50N/51N)
Fast transient disturbance
IEC 61000-4-4 • Type IEC tripping curves (short
4kV auxiliary power supply, class 4 time inverse, standard inverse,
ANSI C37.90.1 very inverse, extremely inverse,
2kV other, class 4 long time inverse) and
IEEE/ANSI (short time inverse,
moderately inverse, inverse, very
inverse, extremely inverse)
• Negative sequence overcurrent
(46)
• Undercurrent (37)

11
Information required with order (CORTEC)

MiCOM P 1 2 4

Earth current input


0.1-40Ion A
0.01-8Ion B
0.002-1Ion C

Self-powered relay operation


Standard version: 0.4In 0
Sensitive version: 0.2In 1

Rated Current Ph & E/Gnd CT secondary


1A 1

5A 5

Vaux CODE
SELF POWERED (without auxiliary supply) S

DUAL POWERED (with auxiliary supply)


24-60Vdc A
48-150Vdc F
130-250Vdc / 100-250Vac M

Communication protocol
SELF POWERED (Vaux Code S) 0

No rear port communication


DUAL POWERED (Vaux Code A,F,M)
MODBUS 1
K-BUS/COURIER 2
IEC 60870-5-103 3
DNP3 4

Language
French 0
English/American 1
Spanish 2
German 3
Italian 4
Russian 5
Polish 6
Portuguese 7
Dutch 8
Czech A

OPTIONS: Magnetic Flag number & Integral Autoreclose


SELF POWERED ONLY (Vaux Code S)
STANDARD :1 flag, no Autoreclose 1
DUAL POWERED ONLY (Vaux Code A,F,M)
STANDARD :1 flag, no Autoreclose 2
OPTION with 4 additional flags, no Autoreclose 5
OPTION with 4 additional flags with Integral Autoreclose 6

12
Accessories

Please quote on order

Battery box for settings MICOM E1

129.6 11.2
4 holes dia.3.4
103.6 24.2
148.1

168 158 ± 0.,5

Flush mounting

(View from top) 150 + 0.8 -0 4 holes dia. 4.4


Front panel

155 25.1 139.8

MiCOM P124

IA = 250A

Déc
h

Alarme

Défau 177 155.2


équip

Alim.
Aux.

Déc.
1

Déc.
2
Flush mounting
Déc.
3

Déc.
4

10
(Front view) (view from right)

Figure 10: Dimensions of 30TE case


All dimensions in mm

13
ALSTOM T&D Protection & Control Business contact addresses

Western Europe PCB Head Office Middle East Asia


and Africa and Pacific
ALSTOM T&D P&C
United Kingdom and Northen Europe 3 Parc des Grillons Middle East Asia
ALSTOM T&D P&C Ltd 60 Route de Sartrouville ALSTOM T&D P&C Ltd
St Leonards Works B.P. 58. 78230 Le Pecq Cedex 12th Floor, Cresent Tower
Stafford. ST17 4LX FRANCE Buhaira Corniche
UNITED KINGDOM Tel: +33 (0)1 34 80 79 00 PO Box 25448. Sharjah
Tel: +44 (0)1785 223251 Fax: +33 (0)1 34 80 79 13 UNITED ARAB EMIRATES
Fax: +44 (0)1785 212232 protection.control@tde.alstom.com Tel: +971 6 556 3971
pcb-wea.uk@tde.alstom.com Fax: +971 6 556 1082
Germany pcb-map.uae@tde.alstom.com
And Eastern Europe
France, Belgium and Luxembourg India and South Asia
ALSTOM T&D P&C SA Germany and Switzerland ALSTOM INDIA LTD
Avenue de Figuières ALSTOM ENERGIETECHNIK GmbH Protection & Control Division
34975 Lattes Cedex Bereich Schutz- und 19/1 GST Road Pallavaram Works
FRANCE Schaltanlagenleittechnik Chennai (Madras) 600 043
Tel: +33 (0)4 67 20 54 54 Lyoner Straße 44-48 INDIA
Fax: +33 (0)4 67 20 54 99 D 60528 Frankfurt/Main Tel: +91 44 236 8621
pcb-wea.france@tde.alstom.com GERMANY Fax: +9144 236 7276
Tel: +49 69 66 32 33 33 pcb-map.india@tde.alstom.com
Fax: +49 69 66 32 25 48
Italy pcb-gee.germany@tde.alstom.com South East Asia
ALSTOM FIR S.p.A ALSTOM T&D P&C LTD
Viale Giulio Cesare, 29 South East Europe 31 Kaki Bukit Road 3
24124 -Bergamo ALSTOM AUSTRIA AG #07-03, Techlink
ITALY Hietzinger Kai 169 Singapore 417818
Tel: +39 035 5791611 A1130-Vienna SINGAPORE
Fax: +39 035 5791662 AUSTRIA Tel: +65 843 3130
pcb-wea.italy@tde.alstom.com Tel: +43 1 87893 726 Fax: +65 846 1796
Fax: +43 1 87893 750 pcb-map.singapore@tde.alstom.com
pcb-gee.austria@tde.alstom.com
China and North East Asia
Spain and Por tugal Central Europe ALSTOM T&D P&C
ALSTOM T&D, S.A. ALSTOM T&D P&C SA Room 910-912, 9th floor
Paseo de la Castellana, 257 uI. Strzegomska 23/27 New Kowloon plaza
28046 Madrid 58-160 Swiebodzice 38 Tai kok Tsui road
SPAIN POLAND Kowloon, Hong Kong
Tel: +34 1 334 59 74 Tel: +48 748 54 84 10 CHINA
Fax: +34 1 334 59 51 Fax: +48 748 54 85 48 Tel: +852 2833 6265
pcb-wea.spain@tde.alstom.com pcb-gee.poland@tde.alstom.com Fax: +852 2834 5279
pcb-map.china@tde.alstom.com
Russian Speaking Countries
Mediterranean and Africa ALSTOM ENERGIETECHNIK GmbH Australia and Pacific Islands
ALSTOM T&D P&C SA Bereich Schutz- und ALSTOM AUSTRALIA Ltd
Avenue de Figuières Schaltanlagenleittechnik Protection & Control Division
34975 Lattes Cedex Lyoner Straße 44-48 PO Box 22, 25 Princes Road
FRANCE D 60528 Frankfurt/Main Regents Park, NSW 2143 Sydney
Tel: +33 (0)4 67 20 54 54 GERMANY AUSTRALIA
Fax: +33 (0)4 67 20 54 99 Tel: +49 69 66 32 33 33 Tel: +61 29 645 0777
pcb-wea.africa@tde.alstom.com Fax: +49 69 66 32 25 48 Fax: +61 29 743 8488
pcb-gee.germany@tde.alstom.com pcb-map.australia@tde.alstom.com

North and South America

USA and Panama Mexico Brazil


ALSTOM USA INC ALSTOM T&D SA DE CV ALSTOM T&D Ltd
Protection & Control Division Alce Blanco 13-A Protecção e Control
4 Skyline Drive - Station M Naucalpan de Juarez Avenida Interlagos 4211
Hawthorne CP 53370 Mexico City CEP-04661-300 São Paulo
New York 10532-2160 MEXICO São Paulo
USA Tel: +52 5 358 27 22 BRAZIL
Tel: +1 914 347 5166 Fax: +52 5 358 83 93 Tel: +55 11 524 1044
Fax: +1 914 347 5508 pcb-nsa.mexico@tde.alstom.com Fax: +55 11 548 3429
pcb-nsa.usa@tde.alstom.com pcb-nsa.brazil@tde.alstom.com
Caribbean, Central and South America
Canada ALSTOM INTERNATIONAL (PERU) South America
ALSTOM CANADA INC Edificio Las Naciones ALSTOM ARGENTINA SA
5112 Timberlea Boulevard Avenida Central 643 - Piso 1 Proteccion y Control
Mississauga, Toronto San Isidro Av. Leandro N. Alem 896 - Piso 5
Ontario L4W 2S5 Lima 27 1001 Buenos Aires
CANADA PERU ARGENTINA
Tel: +1 800 263 0646 Tel: +51 1 221 7954 /1208 T el: +54 11 4891 9600 / 9666
Fax: +1 905 624 8855/8466 Fax: +51 1 221 1209 Fax: +54 11 4311 1040
pcb-nsa.canada@tde.alstom.com pcb-nsa.peru@tde.alstom.com pcb-nsa.argentina@tde.alstom.com

14
Notes:

Your contact:

15
T R A N S M I S S I O N & D I S T R I B U T I O N Protection & Control, HQ, 60 Route de Sartrouville, BP58, 78230 Le Pecq Cedex. France
Tel: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 Email: protection.control@tde.alstom.com Internet: www.tde.alstom.com

© 2000 ALSTOM. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
Other names mentioned, registered or not, are the property of their respectve companies.

Our policy is one of continuous develoment. Accordingly the design of our products may change at any time. Whilst every effort is made to produice up to date literature, this brochure should only
regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

Publication: N 1.1504 090002 INTEGRAL PLUS Printed in France

You might also like