CHARACTERISTICS AND ORDERING CODES 7
3
PR512/P (50-51) UNIT 11
4
PR512/P (50-51-50N-51N) UNIT 15
5
PR512/PD (50-51-50N-51N + DIALOGUE) UNIT 21
6
TIME-CURRENT CURVES 25
7
OVERALL DIMENSIONS 31
8
ELECTRICAL CIRCUIT DIAGRAM 33
1
2
1
DESCRIPTION
Special features 4
Use 5
Electromagnetic compatibility 6
Service conditions 6
Degrees of protection 6
Technical documentation 6
3
DESCRIPTION
Special features
Trip precision
Wide setting range
Operation ensured even with the primary circuit
with single-phase power supply
No limitation of the rated breaking capacity and PR512/P (50-51)
short-time withstand current of the circuit- provides the protection functions
breaker even for the lowest rated currents of the against overload (51), instantane-
relay ous or delayed short-circuit (50)
Single and simultaneous adjustment of the three displays the phase current with the
phases highest load.
Constancy of characteristics and operating
reliability
Processing of the RMS value to express the true
energy content of the current.
PR512/PD (50-51-50N-51N +
dialogue)
provides the protection functions
against overload (51), instantane-
ous or delayed short-circuit (50),
earth fault (51) and instantaneous
PR512/P (50-51-50N-51N)
of delayed earth fault (50N)
provides the protection functions
displays the phase current with the
against overload (51), instantane-
highest load
ous or delayed short-circuit (50),
has the dialogue function and
earth fault (51) and instantaneous
allows connection to the electrical
of delayed earth fault (50N)
installation management system.
displays the phase current with the
highest load.
4
1
5
1
DESCRIPTION
6
2
CHARACTERISTICS AND ORDERING CODES
Current transformers 8
Overload values 8
Power supply 8
Opening solenoid 8
TEST function 9
Signalling outputs 10
Measuring function 10
Ordering codes 10
7
CHARACTERISTICS AND ORDERING CODES
8
2
Front view of the TT2 Test Unit Rear view of the TT2 Test Unit
– Put Dip Switch 1 in position A to enable TT2 for (only for the fixed time curves) and start selected
operation. This also enables the test unit power function timing with subsequent release of the YO3
supply with the display therefore lighting up. opening solenoid and consequent circuit-breaker
In this case, it is also possible to carry out hardware opening.
resetting of the protection and resetting of the K51/ – Put Dip Switches 1, 3 and 4 in position A if the YO3
YO3 signalling relays. opening solenoid opening command is to be
– Put Dip Switches 1 and 2 in position A and press disabled during checking of function I> and I>>.
the TEST pushbutton to release the YO3 opening – To carry out self-diagnosis of the battery charge
solenoid with consequent circuit-breaker opening. and correct operation of the TT2, put Dip Switch 1
– Put Dip Switches 1 and 3 in position A and press in position A, press the CHECK pushbutton and
the TEST pushbutton to check functions I> and I>> verify that the LED lights up. If the LED is off, the
battery must be replaced.
9
2
CHARACTERISTICS AND ORDERING CODES
Ordering codes
10
3
PR512/P UNIT (50-51)
Protection functions 12
11
PR512/P UNIT (50-51)
12
3
Caption
1 Dip Switch for setting the trip threshold of protection
I>
2 Dip Switch for setting timing K of protection I>
3 Dip Switch for selecting the type of curve for
protection I>:
• DT curve with definite time
• NI curve with normal inverse time
• VI curve with very inverse time
• EI curve with extremely inverse time.
13
3
PR512/P UNIT (50-51)
14
4
PR512/P (50-51-50N-51N) UNIT
Protection functions 16
15
PR512/P (50-51-50N-51N) UNIT
16
4
The following settings are possible: Parameters a and b can take on the following
values according to the curve selected.
• 16 threshold current values (Io>) (1) • Normal inverse time curve (NI):
0.100 0.150 0.200 0.250 a = 0.02 b = 0.14.
0.350 0.400 0.450 0.500 • Very inverse time curve (VI):
0.600 0.650 0.700 0.750 a=1 b = 13.5.
• Extremely inverse time curve (EI):
0.850 0.900 0.950 1 x In
a=2 b = 80.
OFF
(1) The unit guarantees no entry in the threshold for
currents under 1.05 x Io> set and guarantees entry in
the threshold for currents higher than 1.30 x Io> set.
Selection of to> trip time
The trip time of the protection is adjusted by using
the Dip Switches as shown in the figure.
Selection of type of Io> curve By means of the Dip Switches, the value of K is set
which, when replaced in the previous relation-
Four different time-current relationships can be
ships, determines trip time to>.
selected.
The following settings are possible:
Fixed time curve (b = 2)
For protection with fixed time (DT), the trip time is
• 16 trip times (to>),
given by the following relationship.
(K = 0.1...1.6 with steps of 0.1)
to> = K x b 0.1
0.6
0.2
0.7
0.3
0.8
0.4
0.9
0.5
1.0
1.1 1.2 1.3 1.4 1.5 1.6
Definite time curve
For protection with definite time, the relationship
between trip time and overcurrent is given by the 1 2 3 4
following formula.
Caption
b 1 Dip Switch for setting
the trip threshold of
to> = K x protection Io>
a 2 Dip Switch for setting
I timing K of protection
–1 Io>
3 Dip Switch for selecting
Io> the type of curve for
protection Io>:
• DT curve with
definite time
Caption • NI curve with normal
to> trip time inverse time
k parameter set by the user to select the trip curve • VI curve with very
a, b pair of parameters, depending on the type of inverse time
protection selectable • EI curve with
I earth fault current extremely inverse
Io> trip threshold selectable by the user. time.
4 Dip Switch for selection
of type of toroid for
earth fault (internal/
external)
17
PR512/P (50-51-50N-51N) UNIT
18
4
19
20
5
PR512/PD (50-51-50N-51N + DIALOGUE) UNIT
Binary inputs 22
Dialogue function 22
21
PR512/PD (50-51-50N-51N + DIALOGUE) UNIT
22
5
1 3 2 Data transmitted
The PR512/PD unit is able to transmit the follow-
ing information:
a) number of circuit-breaker mechanical opera-
tions
b) parameters of the protection functions
c) phase and homopolar currents (with minimum
value of 5% In)
d) “Low current” indication with current less than
5% In
e) currents relative to the last trip
f) state of the protection functions:
– normal operation
– alarm (I>, I>>, Io>, Io>>)
– relay tripped
g) state of the internal bus
h) state of the circuit-breaker:
– circuit-breaker open
– circuit-breaker closed
– circuit-breaker connected or isolated
– state of the operating mechanism springs:
discharged or charged.
5 4
23
5
PR512/PD (50-51-50N-51N + DIALOGUE) UNIT
24
6
TIME-CURRENT CURVES
25
TIME-CURRENT CURVES
I>> / I>
2.5 20
t [s]
I> Definite
Time Curve (IEC 255-3)
I>>
100
10
K = 1.6
3.2
1.55
1
t>
K = 0.1
t >>
0.2
0.1
0.05
0.01
1 1.3 2 3 4 6 7 8 10 20 2 3 4 6 7 8 9
0.9 5 9 5
I/I> I [kA]
26
6
I>> / I>
2.5 20
t [s]
I>>
100
K = 1.6
10
t>
1.55
1 K = 0.1
t >>
0.1
0.05
0.01
1 1.3 2 3 4 6 7 8 10 20 2 3 4 6 7 8 9
0.9 5 9 5
I/I> I [kA]
27
TIME-CURRENT CURVES
I>> / I>
2.5 20
t [s]
I>>
100
10
K = 1.6
t>
1.55
1
K = 0.1
t >>
0.1
0.05
0.01
1 1.3 2 3 4 6 7 8 10 20 2 3 4 6 7 8 9
0.9 5 9 5
I/I> I [kA]
28
6
I>> / I>
2.5 20
t [s]
I>>
100
10
K = 1.6
1.55
1 t>
K = 0.1
t >>
0.1
0.05
0.01
1 1.3 2 3 4 6 7 8 10 20 2 3 4 6 7 8 9
0.9 5 9 5
I/I> I [kA]
29
6
TIME-CURRENT CURVES
30
7
OVERALL DIMENSIONS
31
7
OVERALL DIMENSIONS
Dimensions and fixing Threaded holes are provided on the release box
The overall dimensions are as follows: for application of the fixing brackets for assembly
– height 160 mm on the compartment door.
– width 130 mm
N.B. The dimensions indicated include the overall
– depth 160 mm.
dimensions of the connection connectors.
130
30 130
120 27,5
10
1 3 30
2
KF301
118
160 100
M4
4 23 89 18
XK6
XK5 1 5 33,7
XK4
XK2 XK3
64
M4
XK1
Caption
1 Connector area 32,3
2 Compartment door
drilling
3 Holes for fixing the
unit to the support
square
4 Rear view of connec-
tors
5 View from above.
32
8
ELECTRICAL CIRCUIT DIAGRAM
Caption 36
Notes 37
Connections 38
33
ELECTRICAL CIRCUIT DIAGRAM
PR512/P (50-51)
34
8
PR512/PD (50-51-50N-51N)
35
ELECTRICAL CIRCUIT DIAGRAM
36
8
37
ELECTRICAL CIRCUIT DIAGRAM
Mass, frame
Equipotentiality
38
8
Closing position contact (limit switch) Overcurrent unit for earth fault with short
adjustable time-delay characteristic
39
40
1VCP000055 - Rev.C, en - Technical Catalogue - 2001.03 (649092/014 PR512 )
ABB Trasmissione & Distribuzione S.p.A. ABB Calor Emag Mittelspannung GmbH
Divisione Sace T.M.S. Oberhausener Strasse, 33
Via Friuli, 4 D-40472 Ratingen
I-24044 Dalmine Tel: +49(0)2102/12-0
Tel: +39 035 395111 Fax: +49(0)2102/12-1777
Fax: +39 035 395874 E-mail: calor.info@de.abb.com
E-mail: sacetms.tipm@it.abb.com Internet://www.abb.com
Internet://www.abb.com