Dupline® Field- and Installationbus

I/O-Module for Elevators


Type G 2140 4421 700
• 2 push-button inputs
• 2 PNP-transistor outputs
• Open printed circuit board
• Small size (54 x 40 mm)
• LED-indications for supply and Dupline® carrier
• DC-supply
• 3-wire system with Dupline and supply of module
and output load through G 2196 0000 700
• Channel coding by GAP 1605

Product Description Ordering Key G 2140 4421 700


Direct interface to the I/O’s tor is connected to the same Type: Dupline®
of elevator floor stations. The 3 wires for bus communica- Open PCB
input pulses are prolonged tion with the control system I/O-module
to 0.5 s to ensure transfer of and DC power supply for the Number of I/Os
fast push-button activations. lamps. Installerfriendly mount- I/O-type
Due to the small size of the ing, operation and mainte- DC-supply
module it can be integrated nance without requirements
into most push-button pan- for any special tools or pro-
els. All modules in an eleva- gramming.

Type Selection Output Specifications


Supply Ordering no. Outputs 4 PNP-transistors
PNP-outputs Output voltage drop ≤ 2.0 V
Current per output ≤ 200 mA
10-30 VDC G 2140 4421 700 Short circuit protection None
Built-in protective diodes Yes
Off-state leakage current ≤ 200 µA
Response time 1 pulse train
(136 ms @ 128 channels)

Input Specifications Supply Specifications


Inputs 2 contacts or Power supply Overvoltage cat. III (IEC 60664)
NPN-transistor Rated operational voltage (Vin) 10-30 VDC (ripple included)
Open loop voltage 8.0 VDC Ripple ≤3V
Short circuit current 17 µA Reverse polarity protection Yes
Start peak current 20 mA Current consumption ≤ 30 mA
Contact resistance ≤ 100 Ω Inrush current ≤1A
Cable length ≤3m Transient protection voltage 800 V
Response time ≤ 156 ms @ 128 channels Dielectric voltage
Supply - Dupline® None
Input pulse prolongation Typ. 0.5 s Supply - Inputs None
Supply - Outputs None

Specifications are subject to change without notice (03.09.99) 1


G 2140 4421 700

General Specifications Wiring Diagram


Power ON delay Typ. 2 s
Indication for
Supply ON LED, green DUP
Dupline® carrier LED, yellow GND
Environment POW
Operating temperature -20° to +50°C (-4° to +122°F)
Storage temperature -50° to +85°C (-58° to +185°F)
Humidity (non-condensing) 20 - 80% CHANNEL O6
PROGRAM
PLUG O5
Mechanical resistance GND
Shock 15 G (11 ms) I2
DUPLINE
Vibration 2 G (6 to 55 Hz) I1
SUPPLY
Dimensions Open PCB 54 x 40 mm DC+
4 pcs. of nylon PA6 snap
locks are included for mount-
ing the PCB in ø 4.8 holes
Weight 50 g

Pin Allocation Programming Information


Input/Output The table below shows the relation between the inputs/out-
Terminal
puts of the G 2140 4421 and the In/Out-markings on the
Dupline® signal GAP1605.
DUP
GND Dupline® + supply GND GAP 1605 G 2140 4421
POW Supply IN
DC + DC out In/out 1 Input 1 (I1)
I1 Input 1 In/out 2 Input 2 (I2)
I2 Input 2 In/out 3 Not used
O5 Output 1 In/out 4 Not used
O6 Output 2 In/out 5 Output 1 (O5)
In/out 6 Output 2 (O6)
In/out 7 Not used
In/out 8 Not used

Mode of Operation
The I/O-units use three nel generator function and the to the address given to that assure that the changes of
wires for the communication RS485 communication link to input. Any output of an I/O- input signals (even extreme-
with all the other I/O-units of the elevator controller (please unit that is given the identi- ly short ones) are communi-
an installation, for the sup- refer to the data sheet for G cal address will now follow cated by the system.
ply of the I/O-units and for 21960 000 700 for details) that input signal and switch
the loads connected to the its output signal ON or OFF. The output status of all out-
outputs of the units. This Each I/O-unit has 2 inputs This means that a signal puts of an I/O-unit may be
implies, that the “common” (NPN/contact) and 2 PNP- which is input at one loca- pre-defined for cases like
of the communication signal outputs. Every input and tion (for example as an out- loss of power and loss of
is identical to the “minus” of output is given its individual put from the lift controller) communication. Please refer
the supply. address with the coding unit may be output wherever to the paragraph “Output
GAP 1605 (please refer to required and as many times status setting” of the data
The DC-supply voltage must the respective data sheet for as required. sheet for the GAP 1605 to
connect to the system details). The ON/OFF-signal change the default setting
through a G 2196 0000 700, that is applied to the input An input pulse stretcher is (all outputs OFF).
which also performs the chan- of an I/O-unit is associated used on every input to

2 Specifications are subject to change without notice (03.09.99)