Battery Chargers
The controllers are supplied with two fully au-
tomatic, 200 amp hour, 4 step battery chargers.
The chargers feature Switching Technology and Operator Interface
10Adc Pulse-Width Modulated Output Current. The fire pump controllers feature an opera-
The 4 step charging cycle is as follows: tor interface with user keypad. The interface
Step 1 - Qualification Stage monitors and displays motor operating condi-
During this stage, the battery charger tions, including all alarms, events, and pressure
checks the batteries to insure they can conditions. All alarms, events, and pressure
accept a fast charge. It also checks conditions are displayed with a time and date
for missing or defective batteries. If stamp. The display is a 128x64 Backlit LED ca-
a missing or defective battery is de- pable of customized graphics and Cyrillic type
tected, a fault will be given. character display. The display and interface are
Step 2 - Fast Charge Stage NEMA rated for Type 2, 3R, 4, 4X, and 12 pro-
Charges the batteries until they reach tection and is fully accessible without opening
peak voltage. the controller door. The user interface utilizes
Step 3 - Bulk Charge Stage multiple levels of password protection for sys-
Charges the batteries at a constant tem security. A minimum of 3 password levels
potential of peak voltage until current are provided.
reaches 500mA.
Step 4 - Float Charge Stage
Trickle charges the batteries to main-
tain peak potential.
Standard features include:
Approvals • AC Line and Battery Circuit Breakers
Firetrol fire pump controllers are listed by Un- • Manual-Off-Auto Selector Switch
• Manual Test Push-Button
derwriters’ Laboratories, Inc., in accordance • Two (2) Manual Crank Push-Buttons
with UL218, Standard for Fire Pump Controllers, • Two (2) 10 Amp Battery Chargers with 4 stage charging
cycle, selectable AC voltage (110/220), selectable DC
CSA, Standard for Industrial Control Equipment, voltage (12/24) and selectable battery type (Lead Acid,
Ni-Cad 9/18 Cell, Ni-Cad 10/20 Cell
and approved by Factory Mutual. They are • Minimum Run Timer/Off Delay Timer
built to meet or exceed the requirements of • Programmable Daylight Saving Time Option
• Weekly Test Timer
the approving authorities as well as NEMA and • Engine Run Time Meter
the latest editions of NFPA 20, Installation of • Digital Pressure Display
• Solid State Pressure Transducer
Centrifugal Fire Pumps, and NFPA 70, National • Door mounted display/interface panel featuring a 128 x
64 pixel backlit LED Graphical Display, Membrane Type
Electrical Code. User Control Push-buttons and easy to read LED Indica-
tors for:
• AC POWER AVAILABLE
• ALARM
• MAIN SWITCH IN AUTO
• MAIN SWITCH IN MANUAL
• SYSTEM PRESSURE LOW
• ENGINE RUNNING
• ENGINE FAIL TO START
• ENGINE TEMPERATURE HIGH
• ENGINE OIL PRESSURE LOW
• ENGINE OVERSPEED
• ENGINE ALTERNATE ECM
• ENGINE FUEL INJECTOR MALFUNCTION
Digital Status/Alarm Messages • FUEL LEVEL LOW
The digital display indicates text messages for • AUTOMATIC SHUTDOWN DISABLED
• CHARGER MALFUNCTION
the stats and alarm conditions of: • BATTERY #1 TROUBLE
• BATTERY #2 TROUBLE
• Engine Run • Sequential Start Time • USB Host Controller and Port
• Minimum Run Time • Crank/Rest Time Cycle • Data Log
• Event Log (3000 Events)
/ Off Delay Time • Remote Start • Simultaneous Display of Battery Voltages, Charging
Rates, AC Volts, System Pressure and Alarm Messages
• Engine Fail to Start • System Battery Low • Disk Error message
• Low Suction Pressure• Manual Engine Crank • Disk Near Full message
• Pressure Error message
• Drive Not Installed • Fail To Start message
• Disk Error • Low Suction Pressure message
• Crank Cycle Status Indication (Displays Cranking Bat-
• Disk Near Full tery, Number of Starting Attempts and Crank/Rest Time
Remaining
• Pressure Error • 300 psi (20.7 bar) wet parts (solid state pressure trans-
ducer, solenoid valve, plumbing) for fresh water applica-
tions
The Sequential Start Timer and Minimum Run • NEMA Type 2 enclosure
Timer/Off Delay Times are displayed as numeric • Suitable for use as Service Equipment
• Each standard controller comes with user configurable
values reflecting the value of the remaining options for:
• AC Power Loss Start • Interlock Alarm
time. •Low Pressure Audible • Low Suction Pressure
• Main Switch Mis-Set • Manual Test
• Pump Run Alarm • Remote Start
• User Defined Input • Weekly Test Setup
• Low Pump Room Temp • Low Reservoir
• Relief Valve Open • High Fuel Level
• High Reservoir
LED Visual Indicators Event Recording
LED indicators, visible with the door closed, Memory - The controller records all opera-
indicate: tional and alarm events to system memory. All
• AC Power Available • Alarm • Main Sw. in events are time and date stamped and include
Auto • Main Sw. in Manual • System Pressure an index number. The system memory has the
Low • Engine Running • Engine Fail to Start capability of storing 3000 events and allows
• Engine Temperature High • Engine Oil Pres- the user access to the event log via the user in-
sure Low • Engine Overspeed• Engine Alter- terface. The user can scroll through the stored
nate ECM • Engine Fuel Injector Malfunction • messages in groups of 1 or 10.
Fuel Level Low • Automatic Shutdown Disabled
• Charger Malfunction • Battery #1 Trouble USB Host Controller
• Battery #2 Trouble The controller is equipped with a built-in USB
Host Controller. A USB port capable of accept-
Data Logging ing a USB Flash Memory Disk is provided. The
The user interface monitors the system controller saves all operational and alarm events
and logs the following data: to the flash memory on a daily basis. Each saved
• Number Calls/Starts • Engine Total Run event is time and date stamped. The total
amount of historical data saved depends on
Time • Last Run Time • Controller Power On
the size of the flash disk utilized. The operator
Time • Last Start • Minimum System Pres-
can save settings and values to the flash disk on
sure • Maximum System Pressure • Last High
demand via the user interface.
Temperature • Last Low Oil Pressure • Last
Engine Overspeed • Last Low Fuel Level •
Last Charger Fail • Last Battery Trouble • Bat-
tery #1 Volts • Battery #2 Volts • Batter #1 USB Host Port
Amps • Battery #2 Amps and Flash Disk
CB1000-50
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2010 Emerson Electric Co.
'iretrol Brand Products Cary North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com